SMA America: SB60-1TP-US-40 {208V} — CEC Inverter Specifications

Manufacturer: SMA America Registry: CEC Verified Engineering Specification

SMA America: SB60-1TP-US-40 {208V} outputs 5,490 W AC at 208 V, commercial single-phase (26.4 A continuous, 35 A OCPD), ranking #1,467 of 2,343 CEC inverters at 96.56% efficiency with a 220-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
5,490 W
AC Voltage
208 V, commercial single-phase
Min PV Breaker
35 A (8 AWG Cu)
CEC Efficiency
96.56%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does SMA America: SB60-1TP-US-40 {208V} Compare Against Peer CEC Listings?

How SMA America SMA America: SB60-1TP-US-40 {208V} compares on 96.56% efficiency, MPPT span, and 120% busbar interconnection. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

With a 220-480 V MPPT tracking band and 480 V DC ceiling, SMA America: SB60-1TP-US-40 {208V} handles 5,490 W continuous AC (490 W above the 5,000 W 208 V median). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Installers comparing SMA America against Delta Electronics: SOLIVIA 52 NA G4 TL {208V} (5,200 W) should verify whether listed since 2019-02-15 grid-support firmware meets local IEEE 1547 utility rules.

Where Does SMA America: SB60-1TP-US-40 {208V} Fall Across Listed CEC Models?

Position of SMA America: SB60-1TP-US-40 {208V} (5,490 W AC) relative to the 7,680 W CEC median inverter. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where SMA America: SB60-1TP-US-40 {208V} (5,490 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACSMA America: SB60-: 5,490 W

What Dataset Percentiles Define SMA America: SB60-1TP-US-40 {208V}?

Percentile placement of SMA America: SB60-1TP-US-40 {208V} across AC power class, conversion efficiency, and backfeed breaker size. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

SMA America: SB60-1TP-US-40 {208V} Technical ThresholdsPercentile comparison for SMA America: SB60-1TP-US-40 {208V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output5,490 WCEC Efficiency96.56%Backfeed Breaker35 A

What Do the Dataset Ranks Show for SMA America: SB60-1TP-US-40 {208V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for SMA America: SB60-1TP-US-40 {208V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Eff #1,467 / 2,343

96.56% CEC Weighted Efficiency

+0.15 pts vs the 96.41% 208 V median; overall power rank #1,457 (5,490 W, below CEC median; higher than 37.8% of peers).

NEC 705.12 Check

35 A Required Backfeed OCPD

125% x 26.4 A = 33.0 A -> 35 A standard OCPD using 8 AWG Cu (75 C).

MPPT Window

220 V - 480 V (Max 480 V DC)

Tracking span of 260.0 V; listed since 2019-02-15 (grid-tied PV inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 5490.0W / 208 V -> 26.4 A | Breaker >= 1.25 * 26.4 = 33.0 A -> 35 A

CEC Inverters.csv for SMA America: SB60-1TP-US-40 {208V}: Paco=5490.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=96.56%.

Result: Min 35 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for SMA America: SB60-1TP-US-40 {208V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for SMA America: SB60-1TP-US-40 {208V}. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Official California Energy Commission (NREL SAM) test parameters for SMA America: SB60-1TP-US-40 {208V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 5,490 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 208 V, commercial single-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 480 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 220 V - 480 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 15.5769 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 96.56% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2019-02-15 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to SMA America: SB60-1TP-US-40 {208V} (208 V, commercial single-phase)?

Check whether SMA America: SB60-1TP-US-40 {208V} (35 A breaker) fits without main breaker derate or supply-side taps. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Evaluates SMA America: SB60-1TP-US-40 {208V} (35 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (208V) 40 A 35 A PASS (120% Commercial Busbar)
400A Bus / 400A Main (208V) 80 A 35 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (208V) 120 A 35 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (208V) 160 A 35 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (208V) 240 A 35 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With SMA America: SB60-1TP-US-40 {208V}?

Verified cold-weather (-10 C) series module counts matched to SMA America: SB60-1TP-US-40 {208V}'s 480 V DC ceiling.

Sampled CEC PV modules aligned within 220.0-480.0 V MPPT and 480.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 6 to 8 panels 4.72 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 7 to 11 panels 4.84 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 7 to 10 panels 4.25 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 8 to 11 panels 2.2 kW

Which Competing Grid-Support Inverters Compare to SMA America: SB60-1TP-US-40 {208V}?

Alternative CEC inverters comparable to SMA America: SB60-1TP-US-40 {208V}, including Delta Electronics: SOLIVIA 52 NA G4 TL {208V} (5,200 W) at 208 V, commercial single-phase.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Delta Electronics: SOLIVIA 52 NA G4 TL {208V}
Delta Electronics
5,200 W -290 W 208.0 V 500.0 V 97.45%
Delta Electronics: E6_BDI {208V}
Delta Electronics
5,025 W -465 W 208.0 V 480.0 V 97.13%
ABB: PVI-5000-OUTD-US-A {208V}
ABB
5,000 W -490 W 208.0 V 480.0 V 96.0%
ABB: PVI-5000-OUTD-US-Z-A {208V}
ABB
5,000 W -490 W 208.0 V 480.0 V 96.0%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for SMA America: SB60-1TP-US-40 {208V}?

Check SMA America: SB60-1TP-US-40 {208V} (5,490 W AC, 35 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on SMA America: SB60-1TP-US-40 {208V}.

SMA America: SB60-1TP-US-40 {208V} Panel & Wire Spec

Size 75 C copper conductors at 8 AWG Cu on a 35 A OCPD breaker (26.4 A continuous).

Alternative Inverter Comparison

Compare efficiency (96.56%) and MPPT window (220-480 V) directly against Delta Electronics: SOLIVIA 52 NA G4 TL {208V} (5,200 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SMA America: SB60-1TP-US-40 {208V} by SMA America covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

What breaker and wire size does SMA America: SB60-1TP-US-40 {208V} require?

At 5,490 W continuous AC (208 V, commercial single-phase), continuous current is 26.4 A; 125% NEC 690.8/705.12 sizing requires a 35 A breaker and 8 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does SMA America: SB60-1TP-US-40 {208V} require?

At 5,490 W AC and 208 V, commercial single-phase, continuous line current is 26.4 A, requiring a 35 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

How does SMA America: SB60-1TP-US-40 {208V} compare to Delta Electronics: SOLIVIA 52 NA G4 TL {208V}?

SMA America: SB60-1TP-US-40 {208V} delivers 5,490 W AC at 96.56% CEC efficiency with a 480 V DC ceiling, while Delta Electronics: SOLIVIA 52 NA G4 TL {208V} outputs 5,200 W at 208 V, commercial single-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.