SMA America: SC 3060 UP-US 690V 2566A {690V} — CEC Inverter Specifications

Manufacturer: SMA America Registry: CEC Verified Engineering Specification

SMA America: SC 3060 UP-US 690V 2566A {690V} outputs 2,951,143 W AC at 690 V, 3-phase (2469.4 A continuous, 3,100 A OCPD), ranking #1,246 of 2,343 CEC inverters at 96.74% efficiency with a 1,003-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
2,951,143 W
AC Voltage
690 V, 3-phase
Min PV Breaker
3,100 A (parallel Cu feeders)
CEC Efficiency
96.74%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does SMA America: SC 3060 UP-US 690V 2566A {690V} Compare Against Peer CEC Listings?

How SMA America SMA America: SC 3060 UP-US 690V 2566A {690V} compares on 96.74% efficiency, MPPT span, and 120% busbar interconnection.

With a 1,003-1,200 V MPPT tracking band and 1,200 V DC ceiling, SMA America: SC 3060 UP-US 690V 2566A {690V} handles 2,951,143 W continuous AC (1,211,185 W above the 1,739,958 W 690 V median). Commercial 690 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (690V) or NEC 705.11 supply-side tap. Installers comparing SMA America against INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C690 {690V} (2,983,400 W) should verify whether active in CEC directory grid-support firmware meets local IEEE 1547 utility rules.

Where Does SMA America: SC 3060 UP-US 690V 2566A {690V} Fall Across Listed CEC Models?

Position of SMA America: SC 3060 UP-US 690V 2566A {690V} (2,951,143 W AC) relative to the 7,680 W CEC median inverter.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where SMA America: SC 3060 UP-US 690V 2566A {690V} (2,951,143 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACSMA America: SC 30: 2,951,143 W

What Dataset Percentiles Define SMA America: SC 3060 UP-US 690V 2566A {690V}?

Percentile placement of SMA America: SC 3060 UP-US 690V 2566A {690V} across AC power class, conversion efficiency, and backfeed breaker size.

SMA America: SC 3060 UP-US 690V 2566A {690V} Technical ThresholdsPercentile comparison for SMA America: SC 3060 UP-US 690V 2566A {690V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output2,951,143 WCEC Efficiency96.74%Backfeed Breaker3,100 A

What Do the Dataset Ranks Show for SMA America: SC 3060 UP-US 690V 2566A {690V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for SMA America: SC 3060 UP-US 690V 2566A {690V}.

Eff #1,246 / 2,343

96.74% CEC Weighted Efficiency

-1.43 pts vs the 98.17% 690 V median; overall power rank #57 (2,951,143 W, top 2.4%; higher than 97.6% of peers).

NEC 705.12 Check

3,100 A Required Backfeed OCPD

125% x 2469.4 A = 3086.8 A -> 3,100 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

1,003 V - 1,200 V (Max 1,200 V DC)

Tracking span of 197.0 V; active in CEC directory (hybrid battery-capable inverter).

Commercial / 3-Phase Fit

Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 690 V, 3-phase switchgear (200A Bus / 200A Main (690V) to 1,200A Bus / 1,200A Main (690V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 2951143.0W / 690 V 3-phase -> 2469.4 A | Breaker >= 1.25 * 2469.4 = 3086.8 A -> 3,100 A

CEC Inverters.csv for SMA America: SC 3060 UP-US 690V 2566A {690V}: Paco=2951143.0 W, Vac=690 V, Vdcmax=1200.0 V, Eff=96.74%.

Result: Min 3,100 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (690V): Supply-Side Tap (705.11) / Dedicated Switchboard.

What Are the Published CEC Specifications for SMA America: SC 3060 UP-US 690V 2566A {690V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for SMA America: SC 3060 UP-US 690V 2566A {690V}.

Official California Energy Commission (NREL SAM) test parameters for SMA America: SC 3060 UP-US 690V 2566A {690V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 2,951,143 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 690 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 1,200 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 1,003 V - 1,200 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 2872.5 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 96.74% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: Yes (Battery Capable) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to SMA America: SC 3060 UP-US 690V 2566A {690V} (690 V, 3-phase)?

Check whether SMA America: SC 3060 UP-US 690V 2566A {690V} (3,100 A breaker) fits without main breaker derate or supply-side taps.

Evaluates SMA America: SC 3060 UP-US 690V 2566A {690V} (3100 A required OCPD at 690 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (690V) 40 A 3,100 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (690V) 80 A 3,100 A Supply-Side Tap (705.11) / Dedicated Switchboard
600A Bus / 600A Main (690V) 120 A 3,100 A Supply-Side Tap (705.11) / Dedicated Switchboard
800A Bus / 800A Main (690V) 160 A 3,100 A Supply-Side Tap (705.11) / Dedicated Switchboard
1,200A Bus / 1,200A Main (690V) 240 A 3,100 A Supply-Side Tap (705.11) / Dedicated Switchboard

Which Competing Grid-Support Inverters Compare to SMA America: SC 3060 UP-US 690V 2566A {690V}?

Alternative CEC inverters comparable to SMA America: SC 3060 UP-US 690V 2566A {690V}, including INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C690 {690V} (2,983,400 W) at 690 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C690 {690V}
INGETEAM POWER TECHNOLOGY SA
2,983,400 W +32257 W 690.0 V 1500.0 V 98.09%
Delta Electronics: PCSC2782 {690V}
Delta Electronics
2,813,660 W -137483 W 690.0 V 1500.0 V 98.52%
Power Electronics: FS2300CU15 {690V}
Power Electronics
2,759,490 W -191653 W 690.0 V 1200.0 V 97.96%
Power Electronics: FS2550CU15 {690V}
Power Electronics
2,759,390 W -191753 W 690.0 V 1200.0 V 97.88%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for SMA America: SC 3060 UP-US 690V 2566A {690V}?

Check SMA America: SC 3060 UP-US 690V 2566A {690V} (2,951,143 W AC, 3,100 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 690 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (690V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on SMA America: SC 3060 UP-US 690V 2566A {690V}.

SMA America: SC 3060 UP-US 690V 2566A {690V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 3,100 A OCPD breaker (2469.4 A continuous).

Alternative Inverter Comparison

Compare efficiency (96.74%) and MPPT window (1,003-1,200 V) directly against INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C690 {690V} (2,983,400 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SMA America: SC 3060 UP-US 690V 2566A {690V} by SMA America covering breaker sizing, MPPT limits, and 690 V, 3-phase interconnection.

What breaker and wire size does SMA America: SC 3060 UP-US 690V 2566A {690V} require?

At 2,951,143 W continuous AC (690 V, 3-phase), continuous current is 2469.4 A; 125% NEC 690.8/705.12 sizing requires a 3,100 A breaker and parallel Cu feeders (75 C) wire.

What commercial switchgear or feeder sizing does SMA America: SC 3060 UP-US 690V 2566A {690V} require?

At 2,951,143 W AC and 690 V, 3-phase, continuous line current is 2469.4 A, requiring a 3,100 A OCPD and 1,200A Bus / 1,200A Main (690V) or NEC 705.11 interconnection.

How does SMA America: SC 3060 UP-US 690V 2566A {690V} compare to INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C690 {690V}?

SMA America: SC 3060 UP-US 690V 2566A {690V} delivers 2,951,143 W AC at 96.74% CEC efficiency with a 1,200 V DC ceiling, while INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C690 {690V} outputs 2,983,400 W at 690 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.