SMA America: SC 4000 UP-US 600V 3850A {600V} outputs 3,650,134 W AC at 600 V, 3-phase (3512.4 A continuous, 4,400 A OCPD), ranking #311 of 2,343 CEC inverters at 98.07% efficiency with a 880-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 3,650,134 W
- AC Voltage
- 600 V, 3-phase
- Min PV Breaker
- 4,400 A (parallel Cu feeders)
- CEC Efficiency
- 98.07%
How Does SMA America: SC 4000 UP-US 600V 3850A {600V} Compare Against Peer CEC Listings?
CEC efficiency rank (#311), 880-1,200 V MPPT tracking, and panel fit for SMA America: SC 4000 UP-US 600V 3850A {600V}.
Operating at 600 V, 3-phase, SMA America: SC 4000 UP-US 600V 3850A {600V} converts DC array energy at 98.07% CEC weighted efficiency (top 13.4%; higher than 86.6% of peers) with a 1,200 V max DC input and 3837.22 A max input current for NEC 690.7 string safety. Compare this 3,650,134 W hybrid battery-capable inverter directly with POWER ELECTRONICS: FS3820K {600V} (3,825,800 W). Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
Where Does SMA America: SC 4000 UP-US 600V 3850A {600V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting SMA America: SC 4000 UP-US 600V 3850A {600V} at 3,650,134 W continuous AC output.
What Dataset Percentiles Define SMA America: SC 4000 UP-US 600V 3850A {600V}?
Dataset percentiles comparing SMA America: SC 4000 UP-US 600V 3850A {600V} against 2,343 certified grid-support inverters nationwide. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
What Do the Dataset Ranks Show for SMA America: SC 4000 UP-US 600V 3850A {600V}?
Engineering highlights for SMA America: SC 4000 UP-US 600V 3850A {600V} covering efficiency, parallel Cu feeders feeder, and panel compatibility.
98.07% CEC Weighted Efficiency
-0.21 pts vs the 98.28% 600 V median; overall power rank #19 (3,650,134 W, top 0.8%; higher than 99.2% of peers).
4,400 A Required Backfeed OCPD
125% x 3512.4 A = 4390.5 A -> 4,400 A standard OCPD using parallel Cu feeders (75 C).
880 V - 1,200 V (Max 1,200 V DC)
Tracking span of 320.0 V; active in CEC directory (hybrid battery-capable inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 3650134.0W / 600 V 3-phase -> 3512.4 A | Breaker >= 1.25 * 3512.4 = 4390.5 A -> 4,400 A
CEC Inverters.csv for SMA America: SC 4000 UP-US 600V 3850A {600V}: Paco=3650134.0 W, Vac=600 V, Vdcmax=1200.0 V, Eff=98.07%.
Result: Min 4,400 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (600V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for SMA America: SC 4000 UP-US 600V 3850A {600V}?
California Energy Commission Solar Equipment List parameters for SMA America: SC 4000 UP-US 600V 3850A {600V} (hybrid battery-capable inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 3,650,134 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 880 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 3837.22 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.07% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to SMA America: SC 4000 UP-US 600V 3850A {600V} (600 V, 3-phase)?
Panelboard and switchgear backfeed allowances for SMA America: SC 4000 UP-US 600V 3850A {600V} (4,400 A OCPD). Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (600V) | 40 A | 4,400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (600V) | 80 A | 4,400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (600V) | 120 A | 4,400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (600V) | 160 A | 4,400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (600V) | 240 A | 4,400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With SMA America: SC 4000 UP-US 600V 3850A {600V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for SMA America: SC 4000 UP-US 600V 3850A {600V}.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 21 panels (fixed) | 12.39 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 27 to 28 panels | 12.32 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 26 panels (fixed) | 11.05 kW |
| Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515 | 515.0 W | 53.76 V | 22 panels (fixed) | 11.33 kW |
Which Competing Grid-Support Inverters Compare to SMA America: SC 4000 UP-US 600V 3850A {600V}?
Four alternative CEC inverters matched to SMA America: SC 4000 UP-US 600V 3850A {600V} (3,650,134 W AC), led by POWER ELECTRONICS: FS3820K {600V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| POWER ELECTRONICS: FS3820K {600V} POWER ELECTRONICS |
3,825,800 W | +175666 W | 600.0 V | 1200.0 V | 97.87% |
| Sungrow Power Supply Co Ltd: SG3425UD {600V} Sungrow Power Supply Co Ltd |
3,434,560 W | -215574 W | 600.0 V | 1300.0 V | 97.26% |
| Gamesa Electric: PV3800 {600V} Gamesa Electric |
3,418,394 W | -231740 W | 600.0 V | 1300.0 V | 97.53% |
| Gamesa Electric: PV4100 {600V} Gamesa Electric |
4,054,978 W | +404844 W | 600.0 V | 1300.0 V | 98.34% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: SC 4000 UP-US 600V 3850A {600V}?
Check SMA America: SC 4000 UP-US 600V 3850A {600V} (3,650,134 W AC, 4,400 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on SMA America: SC 4000 UP-US 600V 3850A {600V}.
SMA America: SC 4000 UP-US 600V 3850A {600V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 4,400 A OCPD breaker (3512.4 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.07%) and MPPT window (880-1,200 V) directly against POWER ELECTRONICS: FS3820K {600V} (3,825,800 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: SC 4000 UP-US 600V 3850A {600V} by SMA America covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.
What breaker and wire size does SMA America: SC 4000 UP-US 600V 3850A {600V} require?
At 3,650,134 W continuous AC (600 V, 3-phase), continuous current is 3512.4 A; 125% NEC 690.8/705.12 sizing requires a 4,400 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: SC 4000 UP-US 600V 3850A {600V} require?
At 3,650,134 W AC and 600 V, 3-phase, continuous line current is 3512.4 A, requiring a 4,400 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.
How does SMA America: SC 4000 UP-US 600V 3850A {600V} compare to POWER ELECTRONICS: FS3820K {600V}?
SMA America: SC 4000 UP-US 600V 3850A {600V} delivers 3,650,134 W AC at 98.07% CEC efficiency with a 1,200 V DC ceiling, while POWER ELECTRONICS: FS3820K {600V} outputs 3,825,800 W at 600 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)