POWER ELECTRONICS: FS3820K {600V} outputs 3,825,800 W AC at 600 V, 3-phase (3681.5 A continuous, 4,650 A OCPD), ranking #394 of 2,343 CEC inverters at 97.87% efficiency with a 851-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 3,825,800 W
- AC Voltage
- 600 V, 3-phase
- Min PV Breaker
- 4,650 A (parallel Cu feeders)
- CEC Efficiency
- 97.87%
How Does POWER ELECTRONICS: FS3820K {600V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 600 V, 3-phase grid-support overview for POWER ELECTRONICS: FS3820K {600V}. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
Rated at 3,825,800 W AC (3681.5 A continuous), POWER ELECTRONICS: FS3820K {600V} ranks #394 of 2,343 CEC units at 97.87% efficiency (-0.41 pts vs the 98.28% 600 V median). Minimum 75 C copper conductor sizing for its 4,650 A circuit is parallel Cu feeders per NEC Table 310.16. Cold-weather string Voc must remain under 1,200 V DC at record local winter lows.
Where Does POWER ELECTRONICS: FS3820K {600V} Fall Across Listed CEC Models?
Marks POWER ELECTRONICS: FS3820K {600V} (3,825,800 W AC) across the California Energy Commission inverter AC capacity distribution. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
What Dataset Percentiles Define POWER ELECTRONICS: FS3820K {600V}?
Benchmarks POWER ELECTRONICS: FS3820K {600V} continuous AC output, 97.87% CEC weighted efficiency, and 4,650 A OCPD breaker demand.
What Do the Dataset Ranks Show for POWER ELECTRONICS: FS3820K {600V}?
Four key NEC 705.12 and California Energy Commission metrics defining POWER ELECTRONICS: FS3820K {600V} by POWER ELECTRONICS. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
97.87% CEC Weighted Efficiency
-0.41 pts vs the 98.28% 600 V median; overall power rank #16 (3,825,800 W, top 0.7%; higher than 99.3% of peers).
4,650 A Required Backfeed OCPD
125% x 3681.5 A = 4601.9 A -> 4,650 A standard OCPD using parallel Cu feeders (75 C).
851 V - 1,200 V (Max 1,200 V DC)
Tracking span of 349.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 3825800.0W / 600 V 3-phase -> 3681.5 A | Breaker >= 1.25 * 3681.5 = 4601.9 A -> 4,650 A
CEC Inverters.csv for POWER ELECTRONICS: FS3820K {600V}: Paco=3825800.0 W, Vac=600 V, Vdcmax=1200.0 V, Eff=97.87%.
Result: Min 4,650 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (600V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for POWER ELECTRONICS: FS3820K {600V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for POWER ELECTRONICS: FS3820K {600V}. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 3,825,800 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 851 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 3810.15 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.87% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to POWER ELECTRONICS: FS3820K {600V} (600 V, 3-phase)?
Evaluates POWER ELECTRONICS: FS3820K {600V} (4,650 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (600V) | 40 A | 4,650 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (600V) | 80 A | 4,650 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (600V) | 120 A | 4,650 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (600V) | 160 A | 4,650 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (600V) | 240 A | 4,650 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With POWER ELECTRONICS: FS3820K {600V}?
Sample PV string lengths aligned within 851-1,200 V MPPT and 1,200 V DC max at -10 C. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 20 to 21 panels | 12.39 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 26 to 28 panels | 12.32 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 25 to 26 panels | 11.05 kW |
| Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515 | 515.0 W | 53.76 V | 21 to 22 panels | 11.33 kW |
Which Competing Grid-Support Inverters Compare to POWER ELECTRONICS: FS3820K {600V}?
Competing CEC grid-support inverters near 3,825,800 W AC and 600 V, 3-phase, led by SMA America: SC 4000 UP-US 600V 3850A {600V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| SMA America: SC 4000 UP-US 600V 3850A {600V} SMA America |
3,650,134 W | -175666 W | 600.0 V | 1200.0 V | 98.07% |
| Gamesa Electric: PV4100 {600V} Gamesa Electric |
4,054,978 W | +229178 W | 600.0 V | 1300.0 V | 98.34% |
| Delta Electronics: DWE4150-EV-US {600V} Delta Electronics |
4,162,102 W | +336302 W | 600.0 V | 1350.0 V | 96.92% |
| Sungrow Power Supply Co Ltd: SG3425UD {600V} Sungrow Power Supply Co Ltd |
3,434,560 W | -391240 W | 600.0 V | 1300.0 V | 97.26% |
What Are the Interconnection Limits and Best-Fit Uses for POWER ELECTRONICS: FS3820K {600V}?
Check POWER ELECTRONICS: FS3820K {600V} (3,825,800 W AC, 4,650 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on POWER ELECTRONICS: FS3820K {600V}.
POWER ELECTRONICS: FS3820K {600V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 4,650 A OCPD breaker (3681.5 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.87%) and MPPT window (851-1,200 V) directly against SMA America: SC 4000 UP-US 600V 3850A {600V} (3,650,134 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for POWER ELECTRONICS: FS3820K {600V} by POWER ELECTRONICS covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.
What breaker and wire size does POWER ELECTRONICS: FS3820K {600V} require?
At 3,825,800 W continuous AC (600 V, 3-phase), continuous current is 3681.5 A; 125% NEC 690.8/705.12 sizing requires a 4,650 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does POWER ELECTRONICS: FS3820K {600V} require?
At 3,825,800 W AC and 600 V, 3-phase, continuous line current is 3681.5 A, requiring a 4,650 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.
How does POWER ELECTRONICS: FS3820K {600V} compare to SMA America: SC 4000 UP-US 600V 3850A {600V}?
POWER ELECTRONICS: FS3820K {600V} delivers 3,825,800 W AC at 97.87% CEC efficiency with a 1,200 V DC ceiling, while SMA America: SC 4000 UP-US 600V 3850A {600V} outputs 3,650,134 W at 600 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)