Calculators
UL Listed / UL Classified DIVQ

Circuit Breaker & Panelboard Compatibility Matrix

Standard: UL 489 / UL 67 · NEC 110.3(B) Verified: 2026-11-26

Installing an unapproved breaker into an incompatible panelboard bus stab causes arcing and voids UL listing. This cross-reference maps native UL-listed breakers, UL-Classified Eaton Type CL replacements (Category DIVQ), and obsolete FPE Stab-Lok / Zinsco hazards. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

Panel Series Covered
8
1-Inch UL Classified
Eaton Type CL (DIVQ)
3/4-Inch Proprietary
Square D QO / Eaton CH
Obsolete Fire Hazards
FPE Stab-Lok / Zinsco
Macro detail of copper panelboard busbar stabs and circuit breaker clip engagement mechanics
Macro detail of copper panelboard busbar stabs and circuit breaker clip engagement mechanics

Which Circuit Breakers Fit Square D, Eaton, Siemens, GE, or Obsolete Panels?

Compare UL Listed OEM breaker series, UL Classified DIVQ cross-brand substitutes, and obsolete load centers flagged for full replacement under NEC 110.3(B).

UL Listed native breaker lines, UL Classified (Category DIVQ) replacements, and obsolete panel safety tiers.
Brand & Series Bus Format Native UL Listed UL Classified / Replacement Safety Notes
Square D QO / QOB Load Centers 0.75 in (3/4-inch proprietary) Square D QO, QOB (bolt-on), QO-AFI, QO-GFI, QO-DF, QOT (tandem) No third-party 1-inch UL DIVQ classified swap; use genuine Square D QO or QOB Standard safe panel when maintained; incompatible with Square D Homeline 1-inch breakers.
Square D Homeline (HOM) Load Centers 1.00 in Square D HOM, HOMT (tandem), HOM-AFI, HOM-GFI, HOM-DF Eaton Type CL (UL Classified DIVQ for listed Homeline catalog numbers) Never force QO breakers onto Homeline bus stabs; check door label for tandem CTL slots.
Eaton / Cutler-Hammer Type CH (Tan Handle) 0.75 in (3/4-inch proprietary) Eaton CH, CHF, CHAF, CHGF, CHDF, CHT (tandem) Native Eaton CH only Incompatible with 1-inch Eaton Type BR/BD or Siemens QP breakers.
Eaton / Cutler-Hammer Type BR (Legacy Bryant / Westinghouse / Challenger) 1.00 in Eaton BR, BD (tandem), BRAF, BRGF, BRN Eaton BR is UL Listed replacement for Bryant, Westinghouse BR, and Challenger Type C/A Verify CTL rejection clip alignment on older non-CTL load centers.
Siemens / Murray QP / QT / MP Load Centers 1.00 in Siemens QP, QT (tandem), QAF2, QFGA2, QDF2 (Murray MP phased into Siemens QP) Eaton Type CL (UL Classified DIVQ for listed Siemens/Murray panels) Confirm exact catalog cross-reference table inside load center door.
GE / ABB PowerMark Gold / Pro (THQL / THQP) 1.00 in full / 0.50 in thin THQP GE / ABB THQL (1-in), THQP (1/2-in slim), THQL-AF2, THQL-GF2 Eaton Type CL (UL Classified DIVQ for listed 1-inch GE panels) Half-inch THQP breakers fit only panel bus positions with horizontal slot notches.
Federal Pacific Electric (FPE) Stab-Lok (NA / NC / NB) Proprietary Stab-Lok clip Discontinued (original FPE Stab-Lok NA/NC) ETL-listed Connecticut Electric UBI FPE replacements exist for emergency repair only; panel replacement strongly advised CPSC closed its investigation in 1983 without issuing a mandatory recall, yet independent testing and property insurers flag elevated non-trip failure rates and require licensed panel replacement.
Zinsco / GTE-Sylvania Zinsco Magnetrip / Type R / RC Proprietary aluminum clip-on bus Discontinued ETL-listed Connecticut Electric UBIZ replacements for temporary maintenance only Aluminum busbar oxidation and loose clip jaws cause overheating, arcing, and breaker seizure; insurers frequently mandate full panelboard replacement.

Does Your Panel Pass the NEC 705.12 120% Solar Busbar Rule?

Calculates the largest solar and battery backfeed breaker your panel allows using (1.20 × Busbar) - Main Breaker under NEC 705.12(B)(3)(2).

  • 100 A Busbar
  • 125 A Busbar
  • 150 A Busbar
  • 200 A Busbar
  • 225 A Busbar
  • 100 A Main Breaker
  • 125 A Main Breaker
  • 150 A Main Breaker
  • 175 A Derated Main Breaker
  • 200 A Main Breaker
  • 225 A Main Breaker
NEC 705.12(B)(3)(2)
40 A
Max Solar AC @ 240V 7.68 kW AC
Required PV Breaker (125%) 40 A

PASS (NEC 705.12(B)(3)(2)): 40A breaker fits within 40A limit.

What Do UL and NEC Rules Say About Breaker Compatibility?

Each direct answer below summarizes verified federal statistics, state contractor boards, NEC tables, and solar test data.

Panel Upgrades

When does solar or an EV charger require a 200 A electrical panel upgrade?

Under NEC 705.12(B)(3)(2), a 200 A busbar with a 200 A main breaker allows (200 x 1.20) - 200 = 40 A of solar backfeed (7.68 kW AC). Larger arrays, 60 A EVSE + heat-pump loads, or obsolete FPE Stab-Lok / Zinsco panels require a 175 A main derate, supply-side tap, or 200 A upgrade (BLS US median electrician pay: $64,810/yr).

Source: NEC 705.12, UL DIVQ & BLS May 2025 wage survey · Run 120% busbar rule checker

EV Charger Wiring

What size wire is required for a 50 A or 60 A EV charger circuit?

NEC 625.41 mandates 125% continuous sizing: a 48 A hardwired EVSE requires a 60 A breaker and 6 AWG Cu THHN/SER (65 A @ 75 C). Standard 6/2 NM-B (Romex) is capped at 55 A (60 C) under NEC 334.80 and is compliant for 50 A circuits (40 A EVSE) but NOT 60 A circuits.

Source: NFPA 70 NEC 310.16, 334.80 & 625.41 · 60 A wire chart & 6/2 NM-B rules

What to Check & Best-Fit Scenarios

What Are the Limitations of Reference Data and Who Should Not Rely on It Alone?

Published government datasets and CEC lab ratings establish baseline electrical and solar bounds, subject to field verification at your specific property.

  • Tariffs change mid-year: verify your electric utility's current net-billing export tariff and transformer capacity before signing contracts.
  • NEC edition lags: state and city building departments enforce varying NEC editions (2017, 2020, 2023, or 2026) with local amendments.
  • Not a substitute for on-site inspection: busbar pitting, ungrounded circuits, or loose neutral lugs require in-person testing by a licensed electrician.

Grid-Outage Resilience Priority

Focus on high-SAIDI utilities (>180 min/yr) and verify 120% busbar capacity for a 60 A hybrid battery or 200 A transfer switch.

Post-25D Cash Solar Payback Focus

With 0% federal 25D in 2026, prioritize higher-tariff markets above 18 c/kWh and avoid 20%-35% loan dealer fees.

EV Charging & Circuit Safety

Hardwire 48 A chargers on 6 AWG Cu THHN (75 C) rather than 6/2 NM-B, or step down to 32 A (40 A breaker) on tight 100 A panels.

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers below come directly from official California Energy Commission equipment lists, U.S. Energy Information Administration utility reports, National Electrical Code rules, IRS 2026 guidance, and state licensing boards.

Can Square D Homeline breakers fit in a Square D QO panel?

No. QO uses a proprietary 3/4-inch plug-on bus stab, whereas Homeline uses a 1-inch format. They are physically and electrically incompatible. Check local building department permit requirements for Breakers before finalizing component orders.

Did CPSC issue a mandatory recall for Federal Pacific Stab-Lok panels?

CPSC closed its investigation in 1983 without issuing a mandatory recall, but independent testing and home insurers widely flag Stab-Lok panels for non-trip risks and recommend replacement.

Why do 240 V garage EV outlets trip GFCI breakers while hardwired units do not?

NEC 210.8 and 625.54 mandate Class A GFCI protection on garage 240 V receptacles, which can conflict with an EV charger's internal CCID ground check unless hardwired.

How do you verify whether 1965-1973 aluminum branch wiring has been safely repaired?

Confirm inside junction boxes and panelboards that 15 A / 20 A solid aluminum wires use CPSC Publication 516 permanent repairs (COPALUM crimps or AlumiConn lugs) instead of standard wire nuts.

Who should NOT rely on online electrical calculators without an AHJ or PE review?

Commercial 3-phase installations, multi-family dwellings, homes with detached ADUs, and existing 100 A services adding simultaneous heat pumps and EV chargers require a formal AHJ-reviewed load calculation.

How often should Breakers panel lugs and breakers be inspected?

Inspect residential load centers alongside Breakers planning whenever major appliances, EV chargers, or solar equipment are added, or upon detecting heat under NEC 110.14(D).

What is the difference between 120% load-side solar interconnection and a supply-side tap?

Load-side interconnection under NEC 705.12 limits main plus solar breakers to 120% of the busbar rating, whereas a NEC 705.11 supply-side tap connects ahead of the main breaker.

Why does WireAndSun model 0% federal Section 25D residential tax credit in 2026?

IRS guidance under Public Law 119-21 confirms homeowner Section 25D (30% solar) and Section 25C ($600 panel upgrade) credits expired for property placed in service after December 31, 2025.

Sources

  1. UL Product iQ DIVQ Classified & Listed Circuit Breaker Compatibility Reference — UL Solutions / Panel OEM Datasheets (Square D, Eaton, Siemens, GE), 2026 OEM Cross-Reference (retrieved 2026-11-23)
  2. CPSC Publication 516: Repairing Aluminum Wiring — U.S. Consumer Product Safety Commission (CPSC), Pub. 516 (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.