SMA America: SC 2930 UP-US 660V 2566A {660V} outputs 2,841,880 W AC at 660 V, 3-phase (2486.1 A continuous, 3,150 A OCPD), ranking #1,281 of 2,343 CEC inverters at 96.68% efficiency with a 962-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 2,841,880 W
- AC Voltage
- 660 V, 3-phase
- Min PV Breaker
- 3,150 A (parallel Cu feeders)
- CEC Efficiency
- 96.68%
How Does SMA America: SC 2930 UP-US 660V 2566A {660V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 660 V, 3-phase grid-support overview for SMA America: SC 2930 UP-US 660V 2566A {660V}.
Rated at 2,841,880 W AC (2486.1 A continuous), SMA America: SC 2930 UP-US 660V 2566A {660V} ranks #1,281 of 2,343 CEC units at 96.68% efficiency (-1.53 pts vs the 98.21% 660 V median). Minimum 75 C copper conductor sizing for its 3,150 A circuit is parallel Cu feeders per NEC Table 310.16. Cold-weather string Voc must remain under 1,200 V DC at record local winter lows.
Where Does SMA America: SC 2930 UP-US 660V 2566A {660V} Fall Across Listed CEC Models?
Marks SMA America: SC 2930 UP-US 660V 2566A {660V} (2,841,880 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define SMA America: SC 2930 UP-US 660V 2566A {660V}?
Benchmarks SMA America: SC 2930 UP-US 660V 2566A {660V} continuous AC output, 96.68% CEC weighted efficiency, and 3,150 A OCPD breaker demand.
What Do the Dataset Ranks Show for SMA America: SC 2930 UP-US 660V 2566A {660V}?
Four key NEC 705.12 and California Energy Commission metrics defining SMA America: SC 2930 UP-US 660V 2566A {660V} by SMA America.
96.68% CEC Weighted Efficiency
-1.53 pts vs the 98.21% 660 V median; overall power rank #61 (2,841,880 W, top 2.6%; higher than 97.4% of peers).
3,150 A Required Backfeed OCPD
125% x 2486.1 A = 3107.6 A -> 3,150 A standard OCPD using parallel Cu feeders (75 C).
962 V - 1,200 V (Max 1,200 V DC)
Tracking span of 238.0 V; active in CEC directory (hybrid battery-capable inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 660 V, 3-phase switchgear (200A Bus / 200A Main (660V) to 1,200A Bus / 1,200A Main (660V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 2841880.0W / 660 V 3-phase -> 2486.1 A | Breaker >= 1.25 * 2486.1 = 3107.6 A -> 3,150 A
CEC Inverters.csv for SMA America: SC 2930 UP-US 660V 2566A {660V}: Paco=2841880.0 W, Vac=660 V, Vdcmax=1200.0 V, Eff=96.68%.
Result: Min 3,150 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (660V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for SMA America: SC 2930 UP-US 660V 2566A {660V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for SMA America: SC 2930 UP-US 660V 2566A {660V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 2,841,880 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 660 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 962 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 2853.99 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.68% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to SMA America: SC 2930 UP-US 660V 2566A {660V} (660 V, 3-phase)?
Evaluates SMA America: SC 2930 UP-US 660V 2566A {660V} (3,150 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (660V) | 40 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (660V) | 80 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (660V) | 120 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (660V) | 160 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (660V) | 240 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which Competing Grid-Support Inverters Compare to SMA America: SC 2930 UP-US 660V 2566A {660V}?
Competing CEC grid-support inverters near 2,841,880 W AC and 660 V, 3-phase, led by POWER ELECTRONICS: FP3151K {660V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| POWER ELECTRONICS: FP3151K {660V} POWER ELECTRONICS |
3,145,170 W | +303290 W | 660.0 V | 1200.0 V | 98.6% |
| INGETEAM POWER TECHNOLOGY SA: INGECON SUN 3825TL U C660 {660V} INGETEAM POWER TECHNOLOGY SA |
3,377,600 W | +535720 W | 660.0 V | 1300.0 V | 97.8% |
| INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3660TL U C660 {660V} INGETEAM POWER TECHNOLOGY SA |
3,377,600 W | +535720 W | 660.0 V | 1300.0 V | 97.8% |
| Gamesa Electric: PV4200 {660V} Gamesa Electric |
3,767,352 W | +925472 W | 660.0 V | 1300.0 V | 97.78% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: SC 2930 UP-US 660V 2566A {660V}?
Check SMA America: SC 2930 UP-US 660V 2566A {660V} (2,841,880 W AC, 3,150 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 660 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (660V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on SMA America: SC 2930 UP-US 660V 2566A {660V}.
SMA America: SC 2930 UP-US 660V 2566A {660V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 3,150 A OCPD breaker (2486.1 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.68%) and MPPT window (962-1,200 V) directly against POWER ELECTRONICS: FP3151K {660V} (3,145,170 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: SC 2930 UP-US 660V 2566A {660V} by SMA America covering breaker sizing, MPPT limits, and 660 V, 3-phase interconnection.
What breaker and wire size does SMA America: SC 2930 UP-US 660V 2566A {660V} require?
At 2,841,880 W continuous AC (660 V, 3-phase), continuous current is 2486.1 A; 125% NEC 690.8/705.12 sizing requires a 3,150 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: SC 2930 UP-US 660V 2566A {660V} require?
At 2,841,880 W AC and 660 V, 3-phase, continuous line current is 2486.1 A, requiring a 3,150 A OCPD and 1,200A Bus / 1,200A Main (660V) or NEC 705.11 interconnection.
How does SMA America: SC 2930 UP-US 660V 2566A {660V} compare to POWER ELECTRONICS: FP3151K {660V}?
SMA America: SC 2930 UP-US 660V 2566A {660V} delivers 2,841,880 W AC at 96.68% CEC efficiency with a 1,200 V DC ceiling, while POWER ELECTRONICS: FP3151K {660V} outputs 3,145,170 W at 660 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)