OutBack Power: VFXR3648A {120V} outputs 3,037 W AC at 120 V (25.3 A continuous, 35 A OCPD), ranking #2,340 of 2,343 CEC inverters at 89.72% efficiency with a 40-60 V MPPT window and 60 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 3,037 W
- AC Voltage
- 120 V
- Min PV Breaker
- 35 A (8 AWG Cu)
- CEC Efficiency
- 89.72%
How Does OutBack Power: VFXR3648A {120V} Compare Against Peer CEC Listings?
Breaker sizing (35 A), 8 AWG Cu wire rules, and DC input limits for OutBack Power: VFXR3648A {120V}.
For NEC 705.12 solar interconnection, OutBack Power: VFXR3648A {120V} outputs 25.3 A continuous AC at 120 V and needs a 35 A backfeed breaker on 8 AWG Cu (75 C). Requires a 35 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit). Conversion efficiency scores 89.72% (#2,340 of 2,343, -7.10 pts vs overall CEC median).
Where Does OutBack Power: VFXR3648A {120V} Fall Across Listed CEC Models?
Output power comparison showing where OutBack Power: VFXR3648A {120V} sits among all 2,343 CEC-listed grid-support inverters. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
What Dataset Percentiles Define OutBack Power: VFXR3648A {120V}?
Relative ranking of OutBack Power: VFXR3648A {120V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for OutBack Power: VFXR3648A {120V}?
Snapshot of OutBack Power: VFXR3648A {120V} efficiency rank (#2,340), OCPD breaker size, MPPT span, and busbar verdict. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
89.72% CEC Weighted Efficiency
-5.01 pts vs the 94.73% 120 V median; overall power rank #1,726 (3,037 W, below CEC median; higher than 26.3% of peers).
35 A Required Backfeed OCPD
125% x 25.3 A = 31.6 A -> 35 A standard OCPD using 8 AWG Cu (75 C).
40 V - 60 V (Max 60 V DC)
Tracking span of 20.0 V; listed since 2018-10-15 (grid-tied PV inverter).
120V AC Coupled / Dedicated Transformer
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 3037.0W / 120 V -> 25.3 A | Breaker >= 1.25 * 25.3 = 31.6 A -> 35 A
CEC Inverters.csv for OutBack Power: VFXR3648A {120V}: Paco=3037.0 W, Vac=120 V, Vdcmax=60.0 V, Eff=89.72%.
Result: Min 35 A breaker & 8 AWG Cu (75 C); 200A Bus / 200A Main: 120V AC Coupled / Dedicated Transformer.
What Are the Published CEC Specifications for OutBack Power: VFXR3648A {120V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for OutBack Power: VFXR3648A {120V}. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 3,037 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 120 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 60 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 40 V - 60 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 66.1133 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 89.72% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2018-10-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
Can a Residential Panel Meet 120% Busbar Limits for OutBack Power: VFXR3648A {120V}?
NEC 705.12(B)(3)(2) backfeed compliance table for OutBack Power: VFXR3648A {120V} at 120 V. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 35 A | 120V AC Coupled / Dedicated Transformer |
| 150A Bus / 150A Main | 30 A | 35 A | 120V AC Coupled / Dedicated Transformer |
| 200A Bus / 200A Main | 40 A | 35 A | 120V AC Coupled / Dedicated Transformer |
| 200A Bus / 175A Main | 65 A | 35 A | 120V AC Coupled / Dedicated Transformer |
| 225A Bus / 200A Main | 70 A | 35 A | 120V AC Coupled / Dedicated Transformer |
Which CEC PV Module Strings Pair With OutBack Power: VFXR3648A {120V}?
Minimum and maximum series solar module strings fitting OutBack Power: VFXR3648A {120V} MPPT and 60 V limits. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 1 panel (micro/module) | 0.59 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 1 panel (micro/module) | 0.44 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 1 panel (micro/module) | 0.42 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 1 panel (micro/module) | 0.2 kW |
Which Competing Grid-Support Inverters Compare to OutBack Power: VFXR3648A {120V}?
Peer 120 V CEC inverters near 3,037 W AC output such as Northern Electric & Power Co Ltd: BDM-1600-LV {120V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Northern Electric & Power Co Ltd: BDM-1600-LV {120V} Northern Electric & Power Co Ltd |
1,597 W | -1440 W | 120.0 V | 55.0 V | 96.31% |
| Power Center: Essential Hybrid 5 {120V} Power Center |
4,787 W | +1750 W | 120.0 V | 425.0 V | 95.59% |
| Sol-Ark: 5K-120V/8K-230V-1P {120V} Sol-Ark |
4,787 W | +1750 W | 120.0 V | 425.0 V | 95.59% |
| Northern Electric & Power Co Ltd: BDM-1200-LV {120V} Northern Electric & Power Co Ltd |
1,194 W | -1844 W | 120.0 V | 55.0 V | 96.23% |
What Are the Interconnection Limits and Best-Fit Uses for OutBack Power: VFXR3648A {120V}?
Check OutBack Power: VFXR3648A {120V} (3,037 W AC, 35 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Requires a 35 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit).
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 60 V DC on OutBack Power: VFXR3648A {120V}.
OutBack Power: VFXR3648A {120V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 35 A OCPD breaker (25.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (89.72%) and MPPT window (40-60 V) directly against Northern Electric & Power Co Ltd: BDM-1600-LV {120V} (1,597 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for OutBack Power: VFXR3648A {120V} by OutBack Power covering breaker sizing, MPPT limits, and 120 V interconnection.
What breaker and wire size does OutBack Power: VFXR3648A {120V} require?
At 3,037 W continuous AC (120 V), continuous current is 25.3 A; 125% NEC 690.8/705.12 sizing requires a 35 A breaker and 8 AWG Cu (75 C) wire.
Does OutBack Power: VFXR3648A {120V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 35 A at 120 V means 120V AC Coupled / Dedicated Transformer.
How does OutBack Power: VFXR3648A {120V} compare to Northern Electric & Power Co Ltd: BDM-1600-LV {120V}?
OutBack Power: VFXR3648A {120V} delivers 3,037 W AC at 89.72% CEC efficiency with a 60 V DC ceiling, while Northern Electric & Power Co Ltd: BDM-1600-LV {120V} outputs 1,597 W at 120 V.