PANASONIC CORPORATION OF NORTH AMERICA EVPV380 is a 380.0 W STC (361.5 W PTC) Mono-c-Si solar module ranking #11,043 of 21,677 CEC listings (below all-CEC median; higher than 47.6% of peers). It delivers 22.49% efficiency, 44.3 V Voc at 25 C, and 47.96 V cold Voc at -10 C (12 panels max per 600 V string).
- STC Wattage
- 380.0 W
- PTC Wattage
- 361.5 W
- Voc @ 25C
- 44.3 V
- Efficiency
- 22.49%
How Does PANASONIC CORPORATION OF NORTH AMERICA EVPV380 Compare Against Peer CEC Listings?
Solar engineering breakdown for PANASONIC CORPORATION OF NORTH AMERICA EVPV380: PTC thermal retention, roof footprint, and cold Voc string bounds.
Measured at 380.0 W STC and 361.5 W PTC, PANASONIC CORPORATION OF NORTH AMERICA EVPV380 sits -5.0 W vs all-CEC median (below all-CEC median; higher than 47.6% of peers) among 21,677 listed modules. Power density reaches 224.9 W/m2 (2.58 percentage points above 19.91% CEC median). Mid-range 44.3 V open-circuit voltage allows up to 12 panels per 600 V string at 14 F, whereas 1,000 V commercial inverters handle up to 20 panels in series. Alternative peer CSI Solar Co Ltd CS3N-385MS {Blk} rates 385.0 W.
Where Does PANASONIC CORPORATION OF NORTH AMERICA EVPV380 Fall Across Listed CEC Models?
Distribution marker showing PANASONIC CORPORATION OF NORTH AMERICA EVPV380 (380.0 W) relative to the 385.0 W all-CEC solar panel median.
What Dataset Percentiles Define PANASONIC CORPORATION OF NORTH AMERICA EVPV380?
Dataset percentiles tracking PANASONIC CORPORATION OF NORTH AMERICA EVPV380 power output, thermal retention ratio, and aperture efficiency against 21,677 models.
What Do the Dataset Ranks Show for PANASONIC CORPORATION OF NORTH AMERICA EVPV380?
Benchmark highlights for PANASONIC CORPORATION OF NORTH AMERICA EVPV380 covering STC output, efficiency, 8 kW footprint, and OCPD breaker size.
380.0 W STC · Higher Than 47.6%
380.0 W STC (-5.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.
22.49% Aperture Efficiency
Power density 224.9 W/m2 (2.58 percentage points above 19.91% CEC median). PTC/STC ratio: 95.1% (rank #713).
12 Panels Max @ -10 C (600 V)
Cold Voc reaches 47.96 V at -10 C (575.5 V string) and 49.0 V at -20 C (12 max).
22 Panels = 8,360 W STC
Occupies 37.2 m2 (400 sq ft) producing 7,953 W PTC; NEC 690.8 OCPD floor is 16.55 A (20 A breaker).
NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula
Voc_cold = 44.3 * (1 + (-0.236/100) * (-10 - 25)) = 47.96 V | OCPD = 1.56 * 10.61 = 16.55 A
Inputs from CEC Modules.csv for PANASONIC CORPORATION OF NORTH AMERICA EVPV380: Voc=44.3 V, beta_Voc=-0.236%/C, Isc=10.61 A, STC=380.0 W, Area=1.69 m2.
Result: 12 panels max on 600 V (575.5 V); 22 panels for 8 kW (400 sq ft).
What Are the Published CEC Specifications for PANASONIC CORPORATION OF NORTH AMERICA EVPV380?
Official CEC datasheet figures for PANASONIC CORPORATION OF NORTH AMERICA EVPV380 (Mono-c-Si) used in utility interconnection and permit reviews.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Nameplate Power (STC) | 380.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| Real-World Output (PTC) | 361.5 W (95.1% STC) | PVUSA Test Conditions rating used for utility interconnection |
| Open-Circuit Voltage (Voc) | 44.3 V | Primary cold-weather string sizing limit under NEC 690.7 |
| Short-Circuit Current (Isc) | 10.61 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| Max Power Voltage / Current | 38.1 V / 9.98 A | Inverter MPPT operating window alignment |
| Voc Temp Coefficient (beta_Voc) | -0.236 %/C | Negative slope governing voltage rise below 25C |
| Module Efficiency & Area | 22.49% (1.69 m2) | Array roof footprint density |
| Cell Count & Technology | 60 cells (Mono-c-Si) | Monofacial backsheet |
How Many PANASONIC CORPORATION OF NORTH AMERICA EVPV380 Panels Build a 6 kW, 8 kW, or 10 kW Array?
How many PANASONIC CORPORATION OF NORTH AMERICA EVPV380 modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.
| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| 6 kW Class | 16 | 6.08 kW | 291 sq ft | $1,522 | $2,573 |
| 8 kW Class | 22 | 8.36 kW | 400 sq ft | $2,092 | $3,538 |
| 10 kW Class | 27 | 10.26 kW | 491 sq ft | $2,568 | $4,342 |
How Many PANASONIC CORPORATION OF NORTH AMERICA EVPV380 Modules Fit in a Cold-Weather String?
NEC 690.7(A) winter string table preventing overvoltage trips on PANASONIC CORPORATION OF NORTH AMERICA EVPV380 (47.96 V at 14 F).
| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| -20 C (-4 F) | 49.0 V | 12 panels | 588.0 V | 20 panels |
| -10 C (14 F) | 47.96 V | 12 panels | 575.5 V | 20 panels |
| 0 C (32 F) | 46.91 V | 12 panels | 562.9 V | 21 panels |
| 25 C (77 F STC) | 44.3 V | 13 panels | 575.9 V | 22 panels |
Which Cross-Brand Solar Modules Compare Closest to PANASONIC CORPORATION OF NORTH AMERICA EVPV380?
Competing CEC solar panels closest to PANASONIC CORPORATION OF NORTH AMERICA EVPV380 in nameplate wattage and Voc, starting with CSI Solar Co Ltd CS3N-385MS {Blk}.
| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| CSI Solar Co Ltd CS3N-385MS {Blk} CSI Solar Co Ltd |
385.0 W | +5.0 W | 43.9 V | 19.54% | 93.4% |
| CSI Solar Co Ltd CS3N-385MS {Wht} CSI Solar Co Ltd |
385.0 W | +5.0 W | 43.9 V | 19.54% | 93.4% |
| CSI Solar Co Ltd CS6XH-375M CSI Solar Co Ltd |
375.0 W | -5.0 W | 45.6 V | 20.27% | 93.0% |
| EMMVEE Photovoltaic Power Private Limited E385M72-B EMMVEE Photovoltaic Power Private Limited |
385.0 W | +5.0 W | 45.9 V | 19.32% | 91.5% |
What Are the Design Limits and Best-Fit Uses for PANASONIC CORPORATION OF NORTH AMERICA EVPV380?
Evaluate PANASONIC CORPORATION OF NORTH AMERICA EVPV380 (380.0 W STC, 44.3 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.
- Winter overvoltage boundary: at -20 C (-4 F), PANASONIC CORPORATION OF NORTH AMERICA EVPV380 reaches 49.0 V per panel—exceeding 12 panels in series voids 600 V inverter warranties.
- Footprint constraint: 22 panels for an 8 kW build require 400 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 22 panels (400 sq ft).
- 2026 tax credit baseline: cash residential installs of PANASONIC CORPORATION OF NORTH AMERICA EVPV380 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.
PANASONIC CORPORATION OF NORTH AMERICA EVPV380 8 kW Residential Fit
Needs 22 modules (400 sq ft) with a 20 A string OCPD, offsetting ~$2,092/yr at US average tariffs.
Cold-Climate String Design (-10 C / -20 C)
Cap 600 V series strings at 12 panels (-10 C) or 12 panels (-20 C), or compare CSI Solar Co Ltd CS3N-385MS {Blk}.
Bifacial / High-Heat Roof Check
Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 361.5 W PTC.
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Technical answers for PANASONIC CORPORATION OF NORTH AMERICA EVPV380 by PANASONIC CORPORATION OF NORTH AMERICA grounded in CEC test data and NEC 690.7/690.8 limits.
How many PANASONIC CORPORATION OF NORTH AMERICA EVPV380 panels fit on a 600 V winter solar string?
At -10 C (14 F), PANASONIC CORPORATION OF NORTH AMERICA EVPV380 cold Voc rises from 44.3 V to 47.96 V (beta_Voc -0.236%/C), capping a 600 V string at 12 panels (575.5 V).
How much roof area does an 8 kW array of PANASONIC CORPORATION OF NORTH AMERICA EVPV380 need?
An 8 kW DC system uses 22 PANASONIC CORPORATION OF NORTH AMERICA EVPV380 modules (8,360 W STC / 7,953 W PTC), covering roughly 400 sq ft and saving ~$2,092/yr at 18.54 c/kWh.
How does PANASONIC CORPORATION OF NORTH AMERICA EVPV380 compare against CSI Solar Co Ltd CS3N-385MS {Blk}?
PANASONIC CORPORATION OF NORTH AMERICA EVPV380 outputs 380.0 W STC (44.3 V Voc, rank #11,043 of 21,677), while CSI Solar Co Ltd CS3N-385MS {Blk} delivers 385.0 W STC; both comply with 2026 NEC 690.7 string sizing rules.
Sources
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)