SolarEdge Technologies Ltd: SE6000x {208V} outputs 5,330 W AC at 208 V, commercial single-phase (25.6 A continuous, 35 A OCPD), ranking #1,683 of 2,343 CEC inverters at 96.38% efficiency with a 320-500 V MPPT window and 500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 5,330 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 35 A (8 AWG Cu)
- CEC Efficiency
- 96.38%
How Does SolarEdge Technologies Ltd: SE6000x {208V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 208 V, commercial single-phase grid-support overview for SolarEdge Technologies Ltd: SE6000x {208V}.
Ranking #1,462 of 2,343 CEC inverters (below CEC median; higher than 37.6% of peers), SolarEdge Technologies Ltd: SE6000x {208V} is a grid-tied PV inverter delivering 5,330 W continuous AC at 208 V, commercial single-phase (25.6 A continuous). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 96.38% (-0.03 pts vs the 96.41% 208 V median) against peers like Delta Electronics: SOLIVIA 52 NA G4 TL {208V} (5,200 W).
Where Does SolarEdge Technologies Ltd: SE6000x {208V} Fall Across Listed CEC Models?
Marks SolarEdge Technologies Ltd: SE6000x {208V} (5,330 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define SolarEdge Technologies Ltd: SE6000x {208V}?
Benchmarks SolarEdge Technologies Ltd: SE6000x {208V} continuous AC output, 96.38% CEC weighted efficiency, and 35 A OCPD breaker demand.
What Do the Dataset Ranks Show for SolarEdge Technologies Ltd: SE6000x {208V}?
Four key NEC 705.12 and California Energy Commission metrics defining SolarEdge Technologies Ltd: SE6000x {208V} by SolarEdge Technologies Ltd.
96.38% CEC Weighted Efficiency
-0.03 pts vs the 96.41% 208 V median; overall power rank #1,462 (5,330 W, below CEC median; higher than 37.6% of peers).
35 A Required Backfeed OCPD
125% x 25.6 A = 32.0 A -> 35 A standard OCPD using 8 AWG Cu (75 C).
320 V - 500 V (Max 500 V DC)
Tracking span of 180.0 V; listed since 2018-10-15 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 5330.0W / 208 V -> 25.6 A | Breaker >= 1.25 * 25.6 = 32.0 A -> 35 A
CEC Inverters.csv for SolarEdge Technologies Ltd: SE6000x {208V}: Paco=5330.0 W, Vac=208 V, Vdcmax=500.0 V, Eff=96.38%.
Result: Min 35 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SolarEdge Technologies Ltd: SE6000x {208V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for SolarEdge Technologies Ltd: SE6000x {208V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 5,330 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 320 V - 500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 13.4881 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.38% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2018-10-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to SolarEdge Technologies Ltd: SE6000x {208V} (208 V, commercial single-phase)?
Evaluates SolarEdge Technologies Ltd: SE6000x {208V} (35 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 35 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 35 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 35 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 35 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 35 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SolarEdge Technologies Ltd: SE6000x {208V}?
Sample PV string lengths aligned within 320-500 V MPPT and 500 V DC max at -10 C. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 8 panels (fixed) | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 10 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 10 to 11 panels | 4.67 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 12 panels (fixed) | 2.4 kW |
Which Competing Grid-Support Inverters Compare to SolarEdge Technologies Ltd: SE6000x {208V}?
Competing CEC grid-support inverters near 5,330 W AC and 208 V, commercial single-phase, led by Delta Electronics: SOLIVIA 52 NA G4 TL {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: SOLIVIA 52 NA G4 TL {208V} Delta Electronics |
5,200 W | -130 W | 208.0 V | 500.0 V | 97.45% |
| Delta Electronics: E6_BDI {208V} Delta Electronics |
5,025 W | -305 W | 208.0 V | 480.0 V | 97.13% |
| ABB: PVI-5000-OUTD-US-A {208V} ABB |
5,000 W | -330 W | 208.0 V | 480.0 V | 96.0% |
| ABB: PVI-5000-OUTD-US-Z-A {208V} ABB |
5,000 W | -330 W | 208.0 V | 480.0 V | 96.0% |
What Are the Interconnection Limits and Best-Fit Uses for SolarEdge Technologies Ltd: SE6000x {208V}?
Check SolarEdge Technologies Ltd: SE6000x {208V} (5,330 W AC, 35 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 500 V DC on SolarEdge Technologies Ltd: SE6000x {208V}.
SolarEdge Technologies Ltd: SE6000x {208V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 35 A OCPD breaker (25.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.38%) and MPPT window (320-500 V) directly against Delta Electronics: SOLIVIA 52 NA G4 TL {208V} (5,200 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SolarEdge Technologies Ltd: SE6000x {208V} by SolarEdge Technologies Ltd covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does SolarEdge Technologies Ltd: SE6000x {208V} require?
At 5,330 W continuous AC (208 V, commercial single-phase), continuous current is 25.6 A; 125% NEC 690.8/705.12 sizing requires a 35 A breaker and 8 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SolarEdge Technologies Ltd: SE6000x {208V} require?
At 5,330 W AC and 208 V, commercial single-phase, continuous line current is 25.6 A, requiring a 35 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does SolarEdge Technologies Ltd: SE6000x {208V} compare to Delta Electronics: SOLIVIA 52 NA G4 TL {208V}?
SolarEdge Technologies Ltd: SE6000x {208V} delivers 5,330 W AC at 96.38% CEC efficiency with a 500 V DC ceiling, while Delta Electronics: SOLIVIA 52 NA G4 TL {208V} outputs 5,200 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)