SolarEdge Technologies Ltd: SE120KUS {480V} — CEC Inverter Specifications

Manufacturer: SolarEdge Technologies Ltd Registry: CEC Verified Engineering Specification

SolarEdge Technologies Ltd: SE120KUS {480V} outputs 40,252 W AC at 480 V, 3-phase (48.4 A continuous, 70 A OCPD), ranking #263 of 2,343 CEC inverters at 98.17% efficiency with a 790-950 V MPPT window and 950 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
40,252 W
AC Voltage
480 V, 3-phase
Min PV Breaker
70 A (4 AWG Cu)
CEC Efficiency
98.17%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does SolarEdge Technologies Ltd: SE120KUS {480V} Compare Against Peer CEC Listings?

Breaker sizing (70 A), 4 AWG Cu wire rules, and DC input limits for SolarEdge Technologies Ltd: SE120KUS {480V}.

For NEC 705.12 solar interconnection, SolarEdge Technologies Ltd: SE120KUS {480V} outputs 48.4 A continuous AC at 480 V, 3-phase and needs a 70 A backfeed breaker on 4 AWG Cu (75 C). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Conversion efficiency scores 98.17% (#263 of 2,343, +1.35 pts vs overall CEC median).

Where Does SolarEdge Technologies Ltd: SE120KUS {480V} Fall Across Listed CEC Models?

Output power comparison showing where SolarEdge Technologies Ltd: SE120KUS {480V} sits among all 2,343 CEC-listed grid-support inverters. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where SolarEdge Technologies Ltd: SE120KUS {480V} (40,252 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACSolarEdge Technolo: 40,252 W

What Dataset Percentiles Define SolarEdge Technologies Ltd: SE120KUS {480V}?

Relative ranking of SolarEdge Technologies Ltd: SE120KUS {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

SolarEdge Technologies Ltd: SE120KUS {480V} Technical ThresholdsPercentile comparison for SolarEdge Technologies Ltd: SE120KUS {480V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output40,252 WCEC Efficiency98.17%Backfeed Breaker70 A

What Do the Dataset Ranks Show for SolarEdge Technologies Ltd: SE120KUS {480V}?

Snapshot of SolarEdge Technologies Ltd: SE120KUS {480V} efficiency rank (#263), OCPD breaker size, MPPT span, and busbar verdict.

Eff #263 / 2,343

98.17% CEC Weighted Efficiency

+0.15 pts vs the 98.02% 480 V median; overall power rank #476 (40,252 W, top 20.4%; higher than 79.6% of peers).

NEC 705.12 Check

70 A Required Backfeed OCPD

125% x 48.4 A = 60.5 A -> 70 A standard OCPD using 4 AWG Cu (75 C).

MPPT Window

790 V - 950 V (Max 950 V DC)

Tracking span of 160.0 V; listed since 2023-02-01 (grid-tied PV inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 40252.0W / 480 V 3-phase -> 48.4 A | Breaker >= 1.25 * 48.4 = 60.5 A -> 70 A

CEC Inverters.csv for SolarEdge Technologies Ltd: SE120KUS {480V}: Paco=40252.0 W, Vac=480 V, Vdcmax=950.0 V, Eff=98.17%.

Result: Min 70 A breaker & 4 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for SolarEdge Technologies Ltd: SE120KUS {480V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SolarEdge Technologies Ltd: SE120KUS {480V}. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Official California Energy Commission (NREL SAM) test parameters for SolarEdge Technologies Ltd: SE120KUS {480V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 40,252 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 950 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 790 V - 950 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 48.2369 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.17% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2023-02-01 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to SolarEdge Technologies Ltd: SE120KUS {480V} (480 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for SolarEdge Technologies Ltd: SE120KUS {480V} at 480 V, 3-phase.

Evaluates SolarEdge Technologies Ltd: SE120KUS {480V} (70 A required OCPD at 480 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (480V) 40 A 70 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (480V) 80 A 70 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (480V) 120 A 70 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (480V) 160 A 70 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (480V) 240 A 70 A PASS (120% Commercial Busbar)

Which Competing Grid-Support Inverters Compare to SolarEdge Technologies Ltd: SE120KUS {480V}?

Peer 480 V, 3-phase CEC inverters near 40,252 W AC output such as Canadian Solar Inc: CSI-40KTL-GS {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Canadian Solar Inc: CSI-40KTL-GS {480V}
Canadian Solar Inc
40,000 W -252 W 480.0 V 780.0 V 98.0%
Canadian Solar Inc: CSI-40KTL-GS-FL {480V}
Canadian Solar Inc
40,000 W -252 W 480.0 V 780.0 V 98.16%
CSI Solar Co Ltd: CSI-40KTL-GS-B {480V}
CSI Solar Co Ltd
40,000 W -252 W 480.0 V 780.0 V 98.19%
CSI Solar Co Ltd: CSI-40KTL-GS-FLB {480V}
CSI Solar Co Ltd
40,000 W -252 W 480.0 V 780.0 V 98.19%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for SolarEdge Technologies Ltd: SE120KUS {480V}?

Check SolarEdge Technologies Ltd: SE120KUS {480V} (40,252 W AC, 70 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 950 V DC on SolarEdge Technologies Ltd: SE120KUS {480V}.

SolarEdge Technologies Ltd: SE120KUS {480V} Panel & Wire Spec

Size 75 C copper conductors at 4 AWG Cu on a 70 A OCPD breaker (48.4 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.17%) and MPPT window (790-950 V) directly against Canadian Solar Inc: CSI-40KTL-GS {480V} (40,000 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SolarEdge Technologies Ltd: SE120KUS {480V} by SolarEdge Technologies Ltd covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

What breaker and wire size does SolarEdge Technologies Ltd: SE120KUS {480V} require?

At 40,252 W continuous AC (480 V, 3-phase), continuous current is 48.4 A; 125% NEC 690.8/705.12 sizing requires a 70 A breaker and 4 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does SolarEdge Technologies Ltd: SE120KUS {480V} require?

At 40,252 W AC and 480 V, 3-phase, continuous line current is 48.4 A, requiring a 70 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

How does SolarEdge Technologies Ltd: SE120KUS {480V} compare to Canadian Solar Inc: CSI-40KTL-GS {480V}?

SolarEdge Technologies Ltd: SE120KUS {480V} delivers 40,252 W AC at 98.17% CEC efficiency with a 950 V DC ceiling, while Canadian Solar Inc: CSI-40KTL-GS {480V} outputs 40,000 W at 480 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.