SolarEdge Technologies Ltd: SE120KUS {480V} outputs 40,252 W AC at 480 V, 3-phase (48.4 A continuous, 70 A OCPD), ranking #263 of 2,343 CEC inverters at 98.17% efficiency with a 790-950 V MPPT window and 950 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 40,252 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 70 A (4 AWG Cu)
- CEC Efficiency
- 98.17%
How Does SolarEdge Technologies Ltd: SE120KUS {480V} Compare Against Peer CEC Listings?
Breaker sizing (70 A), 4 AWG Cu wire rules, and DC input limits for SolarEdge Technologies Ltd: SE120KUS {480V}.
For NEC 705.12 solar interconnection, SolarEdge Technologies Ltd: SE120KUS {480V} outputs 48.4 A continuous AC at 480 V, 3-phase and needs a 70 A backfeed breaker on 4 AWG Cu (75 C). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Conversion efficiency scores 98.17% (#263 of 2,343, +1.35 pts vs overall CEC median).
Where Does SolarEdge Technologies Ltd: SE120KUS {480V} Fall Across Listed CEC Models?
Output power comparison showing where SolarEdge Technologies Ltd: SE120KUS {480V} sits among all 2,343 CEC-listed grid-support inverters. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
What Dataset Percentiles Define SolarEdge Technologies Ltd: SE120KUS {480V}?
Relative ranking of SolarEdge Technologies Ltd: SE120KUS {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for SolarEdge Technologies Ltd: SE120KUS {480V}?
Snapshot of SolarEdge Technologies Ltd: SE120KUS {480V} efficiency rank (#263), OCPD breaker size, MPPT span, and busbar verdict.
98.17% CEC Weighted Efficiency
+0.15 pts vs the 98.02% 480 V median; overall power rank #476 (40,252 W, top 20.4%; higher than 79.6% of peers).
70 A Required Backfeed OCPD
125% x 48.4 A = 60.5 A -> 70 A standard OCPD using 4 AWG Cu (75 C).
790 V - 950 V (Max 950 V DC)
Tracking span of 160.0 V; listed since 2023-02-01 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 40252.0W / 480 V 3-phase -> 48.4 A | Breaker >= 1.25 * 48.4 = 60.5 A -> 70 A
CEC Inverters.csv for SolarEdge Technologies Ltd: SE120KUS {480V}: Paco=40252.0 W, Vac=480 V, Vdcmax=950.0 V, Eff=98.17%.
Result: Min 70 A breaker & 4 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SolarEdge Technologies Ltd: SE120KUS {480V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SolarEdge Technologies Ltd: SE120KUS {480V}. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 40,252 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 950 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 790 V - 950 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 48.2369 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.17% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2023-02-01 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to SolarEdge Technologies Ltd: SE120KUS {480V} (480 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for SolarEdge Technologies Ltd: SE120KUS {480V} at 480 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 70 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 70 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 70 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 70 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 70 A | PASS (120% Commercial Busbar) |
Which Competing Grid-Support Inverters Compare to SolarEdge Technologies Ltd: SE120KUS {480V}?
Peer 480 V, 3-phase CEC inverters near 40,252 W AC output such as Canadian Solar Inc: CSI-40KTL-GS {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Canadian Solar Inc: CSI-40KTL-GS {480V} Canadian Solar Inc |
40,000 W | -252 W | 480.0 V | 780.0 V | 98.0% |
| Canadian Solar Inc: CSI-40KTL-GS-FL {480V} Canadian Solar Inc |
40,000 W | -252 W | 480.0 V | 780.0 V | 98.16% |
| CSI Solar Co Ltd: CSI-40KTL-GS-B {480V} CSI Solar Co Ltd |
40,000 W | -252 W | 480.0 V | 780.0 V | 98.19% |
| CSI Solar Co Ltd: CSI-40KTL-GS-FLB {480V} CSI Solar Co Ltd |
40,000 W | -252 W | 480.0 V | 780.0 V | 98.19% |
What Are the Interconnection Limits and Best-Fit Uses for SolarEdge Technologies Ltd: SE120KUS {480V}?
Check SolarEdge Technologies Ltd: SE120KUS {480V} (40,252 W AC, 70 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 950 V DC on SolarEdge Technologies Ltd: SE120KUS {480V}.
SolarEdge Technologies Ltd: SE120KUS {480V} Panel & Wire Spec
Size 75 C copper conductors at 4 AWG Cu on a 70 A OCPD breaker (48.4 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.17%) and MPPT window (790-950 V) directly against Canadian Solar Inc: CSI-40KTL-GS {480V} (40,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SolarEdge Technologies Ltd: SE120KUS {480V} by SolarEdge Technologies Ltd covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does SolarEdge Technologies Ltd: SE120KUS {480V} require?
At 40,252 W continuous AC (480 V, 3-phase), continuous current is 48.4 A; 125% NEC 690.8/705.12 sizing requires a 70 A breaker and 4 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SolarEdge Technologies Ltd: SE120KUS {480V} require?
At 40,252 W AC and 480 V, 3-phase, continuous line current is 48.4 A, requiring a 70 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does SolarEdge Technologies Ltd: SE120KUS {480V} compare to Canadian Solar Inc: CSI-40KTL-GS {480V}?
SolarEdge Technologies Ltd: SE120KUS {480V} delivers 40,252 W AC at 98.17% CEC efficiency with a 950 V DC ceiling, while Canadian Solar Inc: CSI-40KTL-GS {480V} outputs 40,000 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)