SMA America: STPS60US-20 {480V} outputs 60,000 W AC at 480 V, 3-phase (72.2 A continuous, 100 A OCPD), ranking #522 of 2,343 CEC inverters at 97.57% efficiency with a 415-980 V MPPT window and 980 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 60,000 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 100 A (3 AWG Cu)
- CEC Efficiency
- 97.57%
How Does SMA America: STPS60US-20 {480V} Compare Against Peer CEC Listings?
CEC efficiency rank (#522), 415-980 V MPPT tracking, and panel fit for SMA America: STPS60US-20 {480V}. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
Operating at 480 V, 3-phase, SMA America: STPS60US-20 {480V} converts DC array energy at 97.57% CEC weighted efficiency (top 22.4%; higher than 77.6% of peers) with a 980 V max DC input and 79.3484 A max input current for NEC 690.7 string safety. Compare this 60,000 W grid-tied PV inverter directly with ABB: TRIO-600-TL-OUTD-US-480 {480V} (60,000 W). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
Where Does SMA America: STPS60US-20 {480V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting SMA America: STPS60US-20 {480V} at 60,000 W continuous AC output. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
What Dataset Percentiles Define SMA America: STPS60US-20 {480V}?
Dataset percentiles comparing SMA America: STPS60US-20 {480V} against 2,343 certified grid-support inverters nationwide. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
What Do the Dataset Ranks Show for SMA America: STPS60US-20 {480V}?
Engineering highlights for SMA America: STPS60US-20 {480V} covering efficiency, 3 AWG Cu feeder, and panel compatibility. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
97.57% CEC Weighted Efficiency
-0.45 pts vs the 98.02% 480 V median; overall power rank #408 (60,000 W, top 17.8%; higher than 82.2% of peers).
100 A Required Backfeed OCPD
125% x 72.2 A = 90.2 A -> 100 A standard OCPD using 3 AWG Cu (75 C).
415 V - 980 V (Max 980 V DC)
Tracking span of 565.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 60000.0W / 480 V 3-phase -> 72.2 A | Breaker >= 1.25 * 72.2 = 90.2 A -> 100 A
CEC Inverters.csv for SMA America: STPS60US-20 {480V}: Paco=60000.0 W, Vac=480 V, Vdcmax=980.0 V, Eff=97.57%.
Result: Min 100 A breaker & 3 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SMA America: STPS60US-20 {480V}?
California Energy Commission Solar Equipment List parameters for SMA America: STPS60US-20 {480V} (grid-tied PV inverter) interconnection. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 60,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 980 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 415 V - 980 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 79.3484 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.57% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to SMA America: STPS60US-20 {480V} (480 V, 3-phase)?
Panelboard and switchgear backfeed allowances for SMA America: STPS60US-20 {480V} (100 A OCPD). All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 100 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 100 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (480V) | 120 A | 100 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 100 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 100 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SMA America: STPS60US-20 {480V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for SMA America: STPS60US-20 {480V}. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 10 to 17 panels | 10.03 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 13 to 23 panels | 10.12 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 13 to 21 panels | 8.93 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 15 to 24 panels | 4.8 kW |
Which Competing Grid-Support Inverters Compare to SMA America: STPS60US-20 {480V}?
Four alternative CEC inverters matched to SMA America: STPS60US-20 {480V} (60,000 W AC), led by ABB: TRIO-600-TL-OUTD-US-480 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: TRIO-600-TL-OUTD-US-480 {480V} ABB |
60,000 W | Tie (0 W) | 480.0 V | 800.0 V | 98.18% |
| ABB: TRIO-TM-600-US-480 {480V} ABB |
60,000 W | Tie (0 W) | 480.0 V | 800.0 V | 98.18% |
| Canadian Solar Inc: CSI-60KTL-CT {480V} Canadian Solar Inc |
60,000 W | Tie (0 W) | 480.0 V | 850.0 V | 98.24% |
| Canadian Solar Inc: CSI-60KTL-GS {480V} Canadian Solar Inc |
60,000 W | Tie (0 W) | 480.0 V | 720.0 V | 98.34% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: STPS60US-20 {480V}?
Check SMA America: STPS60US-20 {480V} (60,000 W AC, 100 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 980 V DC on SMA America: STPS60US-20 {480V}.
SMA America: STPS60US-20 {480V} Panel & Wire Spec
Size 75 C copper conductors at 3 AWG Cu on a 100 A OCPD breaker (72.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.57%) and MPPT window (415-980 V) directly against ABB: TRIO-600-TL-OUTD-US-480 {480V} (60,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: STPS60US-20 {480V} by SMA America covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does SMA America: STPS60US-20 {480V} require?
At 60,000 W continuous AC (480 V, 3-phase), continuous current is 72.2 A; 125% NEC 690.8/705.12 sizing requires a 100 A breaker and 3 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: STPS60US-20 {480V} require?
At 60,000 W AC and 480 V, 3-phase, continuous line current is 72.2 A, requiring a 100 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does SMA America: STPS60US-20 {480V} compare to ABB: TRIO-600-TL-OUTD-US-480 {480V}?
SMA America: STPS60US-20 {480V} delivers 60,000 W AC at 97.57% CEC efficiency with a 980 V DC ceiling, while ABB: TRIO-600-TL-OUTD-US-480 {480V} outputs 60,000 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)