CEC Grid-Support Inverter

Canadian Solar Inc: CSI-60KTL-GS {480V} — CEC Inverter Specifications

Manufacturer: Canadian Solar Inc Registry: CEC Verified Engineering Specification

Canadian Solar Inc: CSI-60KTL-GS {480V} outputs 60,000 W AC at 480 V, 3-phase (72.2 A continuous, 100 A OCPD), ranking #155 of 2,343 CEC inverters at 98.34% efficiency with a 580-720 V MPPT window and 720 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
60,000 W
AC Voltage
480 V, 3-phase
Min PV Breaker
100 A (3 AWG Cu)
CEC Efficiency
98.34%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Canadian Solar Inc: CSI-60KTL-GS {480V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for Canadian Solar Inc: CSI-60KTL-GS {480V}.

Rated at 60,000 W AC (72.2 A continuous), Canadian Solar Inc: CSI-60KTL-GS {480V} ranks #155 of 2,343 CEC units at 98.34% efficiency (+0.32 pts vs the 98.02% 480 V median). Minimum 75 C copper conductor sizing for its 100 A circuit is 3 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 720 V DC at record local winter lows.

Where Does Canadian Solar Inc: CSI-60KTL-GS {480V} Fall Across Listed CEC Models?

Marks Canadian Solar Inc: CSI-60KTL-GS {480V} (60,000 W AC) across the California Energy Commission inverter AC capacity distribution.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Canadian Solar Inc: CSI-60KTL-GS {480V} (60,000 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACCanadian Solar Inc: 60,000 W

What Dataset Percentiles Define Canadian Solar Inc: CSI-60KTL-GS {480V}?

Benchmarks Canadian Solar Inc: CSI-60KTL-GS {480V} continuous AC output, 98.34% CEC weighted efficiency, and 100 A OCPD breaker demand.

Canadian Solar Inc: CSI-60KTL-GS {480V} Technical ThresholdsPercentile comparison for Canadian Solar Inc: CSI-60KTL-GS {480V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output60,000 WCEC Efficiency98.34%Backfeed Breaker100 A

What Do the Dataset Ranks Show for Canadian Solar Inc: CSI-60KTL-GS {480V}?

Four key NEC 705.12 and California Energy Commission metrics defining Canadian Solar Inc: CSI-60KTL-GS {480V} by Canadian Solar Inc.

Eff #155 / 2,343

98.34% CEC Weighted Efficiency

+0.32 pts vs the 98.02% 480 V median; overall power rank #408 (60,000 W, top 17.8%; higher than 82.2% of peers).

NEC 705.12 Check

100 A Required Backfeed OCPD

125% x 72.2 A = 90.2 A -> 100 A standard OCPD using 3 AWG Cu (75 C).

MPPT Window

580 V - 720 V (Max 720 V DC)

Tracking span of 140.0 V; listed since 2019-11-15 (grid-tied PV inverter).

Commercial / 3-Phase Fit

Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 60000.0W / 480 V 3-phase -> 72.2 A | Breaker >= 1.25 * 72.2 = 90.2 A -> 100 A

CEC Inverters.csv for Canadian Solar Inc: CSI-60KTL-GS {480V}: Paco=60000.0 W, Vac=480 V, Vdcmax=720.0 V, Eff=98.34%.

Result: Min 100 A breaker & 3 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Canadian Solar Inc: CSI-60KTL-GS {480V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Canadian Solar Inc: CSI-60KTL-GS {480V}.

Official California Energy Commission (NREL SAM) test parameters for Canadian Solar Inc: CSI-60KTL-GS {480V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 60,000 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 720 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 580 V - 720 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 93.8702 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.34% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2019-11-15 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to Canadian Solar Inc: CSI-60KTL-GS {480V} (480 V, 3-phase)?

Evaluates Canadian Solar Inc: CSI-60KTL-GS {480V} (100 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates Canadian Solar Inc: CSI-60KTL-GS {480V} (100 A required OCPD at 480 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (480V) 40 A 100 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (480V) 80 A 100 A Supply-Side Tap (705.11) / Dedicated Switchboard
600A Bus / 600A Main (480V) 120 A 100 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (480V) 160 A 100 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (480V) 240 A 100 A PASS (120% Commercial Busbar)

Which Competing Grid-Support Inverters Compare to Canadian Solar Inc: CSI-60KTL-GS {480V}?

Competing CEC grid-support inverters near 60,000 W AC and 480 V, 3-phase, led by ABB: TRIO-600-TL-OUTD-US-480 {480V}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
ABB: TRIO-600-TL-OUTD-US-480 {480V}
ABB
60,000 W Tie (0 W) 480.0 V 800.0 V 98.18%
ABB: TRIO-TM-600-US-480 {480V}
ABB
60,000 W Tie (0 W) 480.0 V 800.0 V 98.18%
Chint Power Systems America: CPS SCA60KTL-DO/US-480 {480V}
Chint Power Systems America
60,000 W Tie (0 W) 480.0 V 850.0 V 98.25%
CSI Solar Co Ltd: CSI-60KTL-GS-B {480V}
CSI Solar Co Ltd
60,000 W Tie (0 W) 480.0 V 720.0 V 98.33%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Canadian Solar Inc: CSI-60KTL-GS {480V}?

Check Canadian Solar Inc: CSI-60KTL-GS {480V} (60,000 W AC, 100 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 720 V DC on Canadian Solar Inc: CSI-60KTL-GS {480V}.

Canadian Solar Inc: CSI-60KTL-GS {480V} Panel & Wire Spec

Size 75 C copper conductors at 3 AWG Cu on a 100 A OCPD breaker (72.2 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.34%) and MPPT window (580-720 V) directly against ABB: TRIO-600-TL-OUTD-US-480 {480V} (60,000 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Canadian Solar Inc: CSI-60KTL-GS {480V} by Canadian Solar Inc covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

What breaker and wire size does Canadian Solar Inc: CSI-60KTL-GS {480V} require?

At 60,000 W continuous AC (480 V, 3-phase), continuous current is 72.2 A; 125% NEC 690.8/705.12 sizing requires a 100 A breaker and 3 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Canadian Solar Inc: CSI-60KTL-GS {480V} require?

At 60,000 W AC and 480 V, 3-phase, continuous line current is 72.2 A, requiring a 100 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

How does Canadian Solar Inc: CSI-60KTL-GS {480V} compare to ABB: TRIO-600-TL-OUTD-US-480 {480V}?

Canadian Solar Inc: CSI-60KTL-GS {480V} delivers 60,000 W AC at 98.34% CEC efficiency with a 720 V DC ceiling, while ABB: TRIO-600-TL-OUTD-US-480 {480V} outputs 60,000 W at 480 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.