Canadian Solar Inc: CSI-50KTL-CT {480V} — CEC Inverter Specifications

Manufacturer: Canadian Solar Inc Registry: CEC Verified Engineering Specification

Canadian Solar Inc: CSI-50KTL-CT {480V} outputs 50,000 W AC at 480 V, 3-phase (60.1 A continuous, 80 A OCPD), ranking #142 of 2,343 CEC inverters at 98.36% efficiency with a 480-850 V MPPT window and 850 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
50,000 W
AC Voltage
480 V, 3-phase
Min PV Breaker
80 A (4 AWG Cu)
CEC Efficiency
98.36%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Canadian Solar Inc: CSI-50KTL-CT {480V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for Canadian Solar Inc: CSI-50KTL-CT {480V}.

Ranking #438 of 2,343 CEC inverters (top 19.3%; higher than 80.7% of peers), Canadian Solar Inc: CSI-50KTL-CT {480V} is a grid-tied PV inverter delivering 50,000 W continuous AC at 480 V, 3-phase (60.1 A continuous). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 98.36% (+0.34 pts vs the 98.02% 480 V median) against peers like ABB: TRIO-500-TL-OUTD-US-480 {480V} (50,000 W).

Where Does Canadian Solar Inc: CSI-50KTL-CT {480V} Fall Across Listed CEC Models?

Marks Canadian Solar Inc: CSI-50KTL-CT {480V} (50,000 W AC) across the California Energy Commission inverter AC capacity distribution.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Canadian Solar Inc: CSI-50KTL-CT {480V} (50,000 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACCanadian Solar Inc: 50,000 W

What Dataset Percentiles Define Canadian Solar Inc: CSI-50KTL-CT {480V}?

Benchmarks Canadian Solar Inc: CSI-50KTL-CT {480V} continuous AC output, 98.36% CEC weighted efficiency, and 80 A OCPD breaker demand.

Canadian Solar Inc: CSI-50KTL-CT {480V} Technical ThresholdsPercentile comparison for Canadian Solar Inc: CSI-50KTL-CT {480V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output50,000 WCEC Efficiency98.36%Backfeed Breaker80 A

What Do the Dataset Ranks Show for Canadian Solar Inc: CSI-50KTL-CT {480V}?

Four key NEC 705.12 and California Energy Commission metrics defining Canadian Solar Inc: CSI-50KTL-CT {480V} by Canadian Solar Inc.

Eff #142 / 2,343

98.36% CEC Weighted Efficiency

+0.34 pts vs the 98.02% 480 V median; overall power rank #438 (50,000 W, top 19.3%; higher than 80.7% of peers).

NEC 705.12 Check

80 A Required Backfeed OCPD

125% x 60.1 A = 75.1 A -> 80 A standard OCPD using 4 AWG Cu (75 C).

MPPT Window

480 V - 850 V (Max 850 V DC)

Tracking span of 370.0 V; listed since 2018-11-01 (grid-tied PV inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 50000.0W / 480 V 3-phase -> 60.1 A | Breaker >= 1.25 * 60.1 = 75.1 A -> 80 A

CEC Inverters.csv for Canadian Solar Inc: CSI-50KTL-CT {480V}: Paco=50000.0 W, Vac=480 V, Vdcmax=850.0 V, Eff=98.36%.

Result: Min 80 A breaker & 4 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Canadian Solar Inc: CSI-50KTL-CT {480V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Canadian Solar Inc: CSI-50KTL-CT {480V}.

Official California Energy Commission (NREL SAM) test parameters for Canadian Solar Inc: CSI-50KTL-CT {480V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 50,000 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 850 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 480 V - 850 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 69.6372 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.36% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2018-11-01 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to Canadian Solar Inc: CSI-50KTL-CT {480V} (480 V, 3-phase)?

Evaluates Canadian Solar Inc: CSI-50KTL-CT {480V} (80 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates Canadian Solar Inc: CSI-50KTL-CT {480V} (80 A required OCPD at 480 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (480V) 40 A 80 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (480V) 80 A 80 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (480V) 120 A 80 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (480V) 160 A 80 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (480V) 240 A 80 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Canadian Solar Inc: CSI-50KTL-CT {480V}?

Sample PV string lengths aligned within 480-850 V MPPT and 850 V DC max at -10 C. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Sampled CEC PV modules aligned within 480.0-850.0 V MPPT and 850.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 12 to 15 panels 8.85 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 15 to 20 panels 8.8 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 14 to 18 panels 7.65 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 17 to 20 panels 4.0 kW

Which Competing Grid-Support Inverters Compare to Canadian Solar Inc: CSI-50KTL-CT {480V}?

Competing CEC grid-support inverters near 50,000 W AC and 480 V, 3-phase, led by ABB: TRIO-500-TL-OUTD-US-480 {480V}. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
ABB: TRIO-500-TL-OUTD-US-480 {480V}
ABB
50,000 W Tie (0 W) 480.0 V 800.0 V 98.27%
Chint Power Systems America: CPS SCA50KTL-DO/US-480 {480V}
Chint Power Systems America
50,000 W Tie (0 W) 480.0 V 850.0 V 98.36%
CSI Solar Co Ltd: CSI-50KTL-GS-B {480V}
CSI Solar Co Ltd
50,000 W Tie (0 W) 480.0 V 720.0 V 98.4%
CSI Solar Co Ltd: CSI-50KTL-GS-FLB {480V}
CSI Solar Co Ltd
50,000 W Tie (0 W) 480.0 V 720.0 V 98.45%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Canadian Solar Inc: CSI-50KTL-CT {480V}?

Check Canadian Solar Inc: CSI-50KTL-CT {480V} (50,000 W AC, 80 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 850 V DC on Canadian Solar Inc: CSI-50KTL-CT {480V}.

Canadian Solar Inc: CSI-50KTL-CT {480V} Panel & Wire Spec

Size 75 C copper conductors at 4 AWG Cu on an 80 A OCPD breaker (60.1 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.36%) and MPPT window (480-850 V) directly against ABB: TRIO-500-TL-OUTD-US-480 {480V} (50,000 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Canadian Solar Inc: CSI-50KTL-CT {480V} by Canadian Solar Inc covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

What breaker and wire size does Canadian Solar Inc: CSI-50KTL-CT {480V} require?

At 50,000 W continuous AC (480 V, 3-phase), continuous current is 60.1 A; 125% NEC 690.8/705.12 sizing requires an 80 A breaker and 4 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Canadian Solar Inc: CSI-50KTL-CT {480V} require?

At 50,000 W AC and 480 V, 3-phase, continuous line current is 60.1 A, requiring an 80 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

How does Canadian Solar Inc: CSI-50KTL-CT {480V} compare to ABB: TRIO-500-TL-OUTD-US-480 {480V}?

Canadian Solar Inc: CSI-50KTL-CT {480V} delivers 50,000 W AC at 98.36% CEC efficiency with a 850 V DC ceiling, while ABB: TRIO-500-TL-OUTD-US-480 {480V} outputs 50,000 W at 480 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.