SMA America: STP50-US-40 {480V} — CEC Inverter Specifications

Manufacturer: SMA America Registry: CEC Verified Engineering Specification

SMA America: STP50-US-40 {480V} outputs 50,000 W AC at 480 V, 3-phase (60.1 A continuous, 80 A OCPD), ranking #429 of 2,343 CEC inverters at 97.79% efficiency with a 500-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
50,000 W
AC Voltage
480 V, 3-phase
Min PV Breaker
80 A (4 AWG Cu)
CEC Efficiency
97.79%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does SMA America: STP50-US-40 {480V} Compare Against Peer CEC Listings?

Breaker sizing (80 A), 4 AWG Cu wire rules, and DC input limits for SMA America: STP50-US-40 {480V}.

Classified as a grid-tied PV inverter (listed since 2019-02-15), SMA America: STP50-US-40 {480V} requires 75.1 A design capacity -> 80 A breaker using 4 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 97.79% (+0.97 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.

Where Does SMA America: STP50-US-40 {480V} Fall Across Listed CEC Models?

Output power comparison showing where SMA America: STP50-US-40 {480V} sits among all 2,343 CEC-listed grid-support inverters. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where SMA America: STP50-US-40 {480V} (50,000 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACSMA America: STP50: 50,000 W

What Dataset Percentiles Define SMA America: STP50-US-40 {480V}?

Relative ranking of SMA America: STP50-US-40 {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

SMA America: STP50-US-40 {480V} Technical ThresholdsPercentile comparison for SMA America: STP50-US-40 {480V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output50,000 WCEC Efficiency97.79%Backfeed Breaker80 A

What Do the Dataset Ranks Show for SMA America: STP50-US-40 {480V}?

Snapshot of SMA America: STP50-US-40 {480V} efficiency rank (#429), OCPD breaker size, MPPT span, and busbar verdict. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Eff #429 / 2,343

97.79% CEC Weighted Efficiency

-0.23 pts vs the 98.02% 480 V median; overall power rank #438 (50,000 W, top 19.3%; higher than 80.7% of peers).

NEC 705.12 Check

80 A Required Backfeed OCPD

125% x 60.1 A = 75.1 A -> 80 A standard OCPD using 4 AWG Cu (75 C).

MPPT Window

500 V - 800 V (Max 800 V DC)

Tracking span of 300.0 V; listed since 2019-02-15 (grid-tied PV inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 50000.0W / 480 V 3-phase -> 60.1 A | Breaker >= 1.25 * 60.1 = 75.1 A -> 80 A

CEC Inverters.csv for SMA America: STP50-US-40 {480V}: Paco=50000.0 W, Vac=480 V, Vdcmax=800.0 V, Eff=97.79%.

Result: Min 80 A breaker & 4 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for SMA America: STP50-US-40 {480V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SMA America: STP50-US-40 {480V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Official California Energy Commission (NREL SAM) test parameters for SMA America: STP50-US-40 {480V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 50,000 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 800 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 500 V - 800 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 70.5215 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 97.79% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2019-02-15 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to SMA America: STP50-US-40 {480V} (480 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for SMA America: STP50-US-40 {480V} at 480 V, 3-phase. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Evaluates SMA America: STP50-US-40 {480V} (80 A required OCPD at 480 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (480V) 40 A 80 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (480V) 80 A 80 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (480V) 120 A 80 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (480V) 160 A 80 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (480V) 240 A 80 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With SMA America: STP50-US-40 {480V}?

Minimum and maximum series solar module strings fitting SMA America: STP50-US-40 {480V} MPPT and 800 V limits. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Sampled CEC PV modules aligned within 500.0-800.0 V MPPT and 800.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 12 to 14 panels 8.26 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 15 to 18 panels 7.92 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 15 to 17 panels 7.22 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 18 to 19 panels 3.8 kW

Which Competing Grid-Support Inverters Compare to SMA America: STP50-US-40 {480V}?

Peer 480 V, 3-phase CEC inverters near 50,000 W AC output such as ABB: TRIO-500-TL-OUTD-US-480 {480V}. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
ABB: TRIO-500-TL-OUTD-US-480 {480V}
ABB
50,000 W Tie (0 W) 480.0 V 800.0 V 98.27%
Canadian Solar Inc: CSI-50KTL-CT {480V}
Canadian Solar Inc
50,000 W Tie (0 W) 480.0 V 850.0 V 98.36%
Canadian Solar Inc: CSI-50KTL-GS {480V}
Canadian Solar Inc
50,000 W Tie (0 W) 480.0 V 720.0 V 98.43%
Canadian Solar Inc: CSI-50KTL-GS-FL {480V}
Canadian Solar Inc
50,000 W Tie (0 W) 480.0 V 720.0 V 98.47%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for SMA America: STP50-US-40 {480V}?

Check SMA America: STP50-US-40 {480V} (50,000 W AC, 80 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on SMA America: STP50-US-40 {480V}.

SMA America: STP50-US-40 {480V} Panel & Wire Spec

Size 75 C copper conductors at 4 AWG Cu on an 80 A OCPD breaker (60.1 A continuous).

Alternative Inverter Comparison

Compare efficiency (97.79%) and MPPT window (500-800 V) directly against ABB: TRIO-500-TL-OUTD-US-480 {480V} (50,000 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SMA America: STP50-US-40 {480V} by SMA America covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

What breaker and wire size does SMA America: STP50-US-40 {480V} require?

At 50,000 W continuous AC (480 V, 3-phase), continuous current is 60.1 A; 125% NEC 690.8/705.12 sizing requires an 80 A breaker and 4 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does SMA America: STP50-US-40 {480V} require?

At 50,000 W AC and 480 V, 3-phase, continuous line current is 60.1 A, requiring an 80 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

How does SMA America: STP50-US-40 {480V} compare to ABB: TRIO-500-TL-OUTD-US-480 {480V}?

SMA America: STP50-US-40 {480V} delivers 50,000 W AC at 97.79% CEC efficiency with a 800 V DC ceiling, while ABB: TRIO-500-TL-OUTD-US-480 {480V} outputs 50,000 W at 480 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.