SMA America: SHP FLEX-US-21 {208V} outputs 55,076 W AC at 208 V, 3-phase (152.9 A continuous, 200 A OCPD), ranking #1,808 of 2,343 CEC inverters at 96.26% efficiency with a 372-1,195 V MPPT window and 1,195 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 55,076 W
- AC Voltage
- 208 V, 3-phase
- Min PV Breaker
- 200 A (3/0 AWG Cu)
- CEC Efficiency
- 96.26%
How Does SMA America: SHP FLEX-US-21 {208V} Compare Against Peer CEC Listings?
Breaker sizing (200 A), 3/0 AWG Cu wire rules, and DC input limits for SMA America: SHP FLEX-US-21 {208V}.
Classified as a grid-tied PV inverter (listed since 2025-01-02), SMA America: SHP FLEX-US-21 {208V} requires 191.1 A design capacity -> 200 A breaker using 3/0 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 96.26% (-0.56 pts vs overall CEC median) across 2,343 CEC models, while commercial 208 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (208v) or nec 705.11 supply-side tap.
Where Does SMA America: SHP FLEX-US-21 {208V} Fall Across Listed CEC Models?
Output power comparison showing where SMA America: SHP FLEX-US-21 {208V} sits among all 2,343 CEC-listed grid-support inverters. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
What Dataset Percentiles Define SMA America: SHP FLEX-US-21 {208V}?
Relative ranking of SMA America: SHP FLEX-US-21 {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for SMA America: SHP FLEX-US-21 {208V}?
Snapshot of SMA America: SHP FLEX-US-21 {208V} efficiency rank (#1,808), OCPD breaker size, MPPT span, and busbar verdict.
96.26% CEC Weighted Efficiency
-0.15 pts vs the 96.41% 208 V median; overall power rank #432 (55,076 W, top 18.4%; higher than 81.6% of peers).
200 A Required Backfeed OCPD
125% x 152.9 A = 191.1 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).
372 V - 1,195 V (Max 1,195 V DC)
Tracking span of 823.0 V; listed since 2025-01-02 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 208 V, 3-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 55076.0W / 208 V 3-phase -> 152.9 A | Breaker >= 1.25 * 152.9 = 191.1 A -> 200 A
CEC Inverters.csv for SMA America: SHP FLEX-US-21 {208V}: Paco=55076.0 W, Vac=208 V, Vdcmax=1195.0 V, Eff=96.26%.
Result: Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SMA America: SHP FLEX-US-21 {208V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SMA America: SHP FLEX-US-21 {208V}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 55,076 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,195 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 372 V - 1,195 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 98.1407 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.26% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2025-01-02 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to SMA America: SHP FLEX-US-21 {208V} (208 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for SMA America: SHP FLEX-US-21 {208V} at 208 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (208V) | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (208V) | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (208V) | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 200 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SMA America: SHP FLEX-US-21 {208V}?
Minimum and maximum series solar module strings fitting SMA America: SHP FLEX-US-21 {208V} MPPT and 1,195 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 9 to 21 panels | 12.39 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 12 to 28 panels | 12.32 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 11 to 26 panels | 11.05 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 13 to 29 panels | 5.8 kW |
Which Competing Grid-Support Inverters Compare to SMA America: SHP FLEX-US-21 {208V}?
Peer 208 V, 3-phase CEC inverters near 55,076 W AC output such as Chint Power Systems America: SCA50K-T-US-208 {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chint Power Systems America: SCA50K-T-US-208 {208V} Chint Power Systems America |
50,000 W | -5076 W | 208.0 V | 700.0 V | 95.93% |
| CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V} CSI Solar Co Ltd |
29,878 W | -25198 W | 208.0 V | 680.0 V | 96.38% |
| Chint Power Systems America: CPS SCA25KTL-DO/US-208 {208V} Chint Power Systems America |
25,000 W | -30076 W | 208.0 V | 850.0 V | 96.26% |
| EcoFlow Inc: EF-PCS-24 {208V 24kW} EcoFlow Inc |
24,291 W | -30785 W | 208.0 V | 480.0 V | 96.01% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: SHP FLEX-US-21 {208V}?
Check SMA America: SHP FLEX-US-21 {208V} (55,076 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,195 V DC on SMA America: SHP FLEX-US-21 {208V}.
SMA America: SHP FLEX-US-21 {208V} Panel & Wire Spec
Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (152.9 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.26%) and MPPT window (372-1,195 V) directly against Chint Power Systems America: SCA50K-T-US-208 {208V} (50,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: SHP FLEX-US-21 {208V} by SMA America covering breaker sizing, MPPT limits, and 208 V, 3-phase interconnection.
What breaker and wire size does SMA America: SHP FLEX-US-21 {208V} require?
At 55,076 W continuous AC (208 V, 3-phase), continuous current is 152.9 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: SHP FLEX-US-21 {208V} require?
At 55,076 W AC and 208 V, 3-phase, continuous line current is 152.9 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does SMA America: SHP FLEX-US-21 {208V} compare to Chint Power Systems America: SCA50K-T-US-208 {208V}?
SMA America: SHP FLEX-US-21 {208V} delivers 55,076 W AC at 96.26% CEC efficiency with a 1,195 V DC ceiling, while Chint Power Systems America: SCA50K-T-US-208 {208V} outputs 50,000 W at 208 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)