Chint Power Systems America: SCA50K-T-US-208 {208V} outputs 50,000 W AC at 208 V, 3-phase (138.8 A continuous, 175 A OCPD), ranking #2,021 of 2,343 CEC inverters at 95.93% efficiency with a 200-700 V MPPT window and 700 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 50,000 W
- AC Voltage
- 208 V, 3-phase
- Min PV Breaker
- 175 A (2/0 AWG Cu)
- CEC Efficiency
- 95.93%
How Does Chint Power Systems America: SCA50K-T-US-208 {208V} Compare Against Peer CEC Listings?
Breaker sizing (175 A), 2/0 AWG Cu wire rules, and DC input limits for Chint Power Systems America: SCA50K-T-US-208 {208V}.
For NEC 705.12 solar interconnection, Chint Power Systems America: SCA50K-T-US-208 {208V} outputs 138.8 A continuous AC at 208 V, 3-phase and needs a 175 A backfeed breaker on 2/0 AWG Cu (75 C). Commercial 208 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Conversion efficiency scores 95.93% (#2,021 of 2,343, -0.89 pts vs overall CEC median).
Where Does Chint Power Systems America: SCA50K-T-US-208 {208V} Fall Across Listed CEC Models?
Output power comparison showing where Chint Power Systems America: SCA50K-T-US-208 {208V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Chint Power Systems America: SCA50K-T-US-208 {208V}?
Relative ranking of Chint Power Systems America: SCA50K-T-US-208 {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Chint Power Systems America: SCA50K-T-US-208 {208V}?
Snapshot of Chint Power Systems America: SCA50K-T-US-208 {208V} efficiency rank (#2,021), OCPD breaker size, MPPT span, and busbar verdict.
95.93% CEC Weighted Efficiency
-0.48 pts vs the 96.41% 208 V median; overall power rank #438 (50,000 W, top 19.3%; higher than 80.7% of peers).
175 A Required Backfeed OCPD
125% x 138.8 A = 173.5 A -> 175 A standard OCPD using 2/0 AWG Cu (75 C).
200 V - 700 V (Max 700 V DC)
Tracking span of 500.0 V; listed since 2026-04-21 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 208 V, 3-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 50000.0W / 208 V 3-phase -> 138.8 A | Breaker >= 1.25 * 138.8 = 173.5 A -> 175 A
CEC Inverters.csv for Chint Power Systems America: SCA50K-T-US-208 {208V}: Paco=50000.0 W, Vac=208 V, Vdcmax=700.0 V, Eff=95.93%.
Result: Min 175 A breaker & 2/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Chint Power Systems America: SCA50K-T-US-208 {208V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Chint Power Systems America: SCA50K-T-US-208 {208V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 50,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 700 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 200 V - 700 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 137.166 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 95.93% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2026-04-21 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Chint Power Systems America: SCA50K-T-US-208 {208V} (208 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Chint Power Systems America: SCA50K-T-US-208 {208V} at 208 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (208V) | 80 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (208V) | 120 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (208V) | 160 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 175 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Chint Power Systems America: SCA50K-T-US-208 {208V}?
Minimum and maximum series solar module strings fitting Chint Power Systems America: SCA50K-T-US-208 {208V} MPPT and 700 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 5 to 12 panels | 7.08 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 6 to 16 panels | 7.04 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 6 to 15 panels | 6.38 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 7 to 17 panels | 3.4 kW |
Which Competing Grid-Support Inverters Compare to Chint Power Systems America: SCA50K-T-US-208 {208V}?
Peer 208 V, 3-phase CEC inverters near 50,000 W AC output such as CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V} CSI Solar Co Ltd |
29,878 W | -20122 W | 208.0 V | 680.0 V | 96.38% |
| EcoFlow Inc: EF-PCS-24 {208V 24kW} EcoFlow Inc |
24,291 W | -25709 W | 208.0 V | 480.0 V | 96.01% |
| EG4 Electronics LLC: IV-16000-HYB-AW-FX-xx {208V} EG4 Electronics LLC |
13,899 W | -36101 W | 208.0 V | 440.0 V | 96.46% |
| EcoFlow Inc: EF-PCS-24 {208V 115kW} EcoFlow Inc |
11,444 W | -38556 W | 208.0 V | 480.0 V | 96.52% |
What Are the Interconnection Limits and Best-Fit Uses for Chint Power Systems America: SCA50K-T-US-208 {208V}?
Check Chint Power Systems America: SCA50K-T-US-208 {208V} (50,000 W AC, 175 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 700 V DC on Chint Power Systems America: SCA50K-T-US-208 {208V}.
Chint Power Systems America: SCA50K-T-US-208 {208V} Panel & Wire Spec
Size 75 C copper conductors at 2/0 AWG Cu on a 175 A OCPD breaker (138.8 A continuous).
Alternative Inverter Comparison
Compare efficiency (95.93%) and MPPT window (200-700 V) directly against CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V} (29,878 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Chint Power Systems America: SCA50K-T-US-208 {208V} by Chint Power Systems America covering breaker sizing, MPPT limits, and 208 V, 3-phase interconnection.
What breaker and wire size does Chint Power Systems America: SCA50K-T-US-208 {208V} require?
At 50,000 W continuous AC (208 V, 3-phase), continuous current is 138.8 A; 125% NEC 690.8/705.12 sizing requires a 175 A breaker and 2/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Chint Power Systems America: SCA50K-T-US-208 {208V} require?
At 50,000 W AC and 208 V, 3-phase, continuous line current is 138.8 A, requiring a 175 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does Chint Power Systems America: SCA50K-T-US-208 {208V} compare to CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V}?
Chint Power Systems America: SCA50K-T-US-208 {208V} delivers 50,000 W AC at 95.93% CEC efficiency with a 700 V DC ceiling, while CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V} outputs 29,878 W at 208 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)