Chint Power Systems America: CPS ECB200KTL/US-800 {800V} outputs 200,000 W AC at 800 V, 3-phase (144.3 A continuous, 200 A OCPD), ranking #529 of 2,343 CEC inverters at 97.55% efficiency with a 950-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 200,000 W
- AC Voltage
- 800 V, 3-phase
- Min PV Breaker
- 200 A (3/0 AWG Cu)
- CEC Efficiency
- 97.55%
How Does Chint Power Systems America: CPS ECB200KTL/US-800 {800V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 800 V, 3-phase grid-support overview for Chint Power Systems America: CPS ECB200KTL/US-800 {800V}.
Ranking #247 of 2,343 CEC inverters (top 10.7%; higher than 89.3% of peers), Chint Power Systems America: CPS ECB200KTL/US-800 {800V} is a grid-tied PV inverter delivering 200,000 W continuous AC at 800 V, 3-phase (144.3 A continuous). Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 97.55% (-0.75 pts vs the 98.3% 800 V median) against peers like ABB: PVS-175-TL-POWER-MODULE-1-US {800V} (179,574 W).
Where Does Chint Power Systems America: CPS ECB200KTL/US-800 {800V} Fall Across Listed CEC Models?
Marks Chint Power Systems America: CPS ECB200KTL/US-800 {800V} (200,000 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define Chint Power Systems America: CPS ECB200KTL/US-800 {800V}?
Benchmarks Chint Power Systems America: CPS ECB200KTL/US-800 {800V} continuous AC output, 97.55% CEC weighted efficiency, and 200 A OCPD breaker demand.
What Do the Dataset Ranks Show for Chint Power Systems America: CPS ECB200KTL/US-800 {800V}?
Four key NEC 705.12 and California Energy Commission metrics defining Chint Power Systems America: CPS ECB200KTL/US-800 {800V} by Chint Power Systems America.
97.55% CEC Weighted Efficiency
-0.75 pts vs the 98.3% 800 V median; overall power rank #247 (200,000 W, top 10.7%; higher than 89.3% of peers).
200 A Required Backfeed OCPD
125% x 144.3 A = 180.4 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).
950 V - 1,500 V (Max 1,500 V DC)
Tracking span of 550.0 V; listed since 2025-03-03 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 800 V, 3-phase switchgear (200A Bus / 200A Main (800V) to 1,200A Bus / 1,200A Main (800V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 200000.0W / 800 V 3-phase -> 144.3 A | Breaker >= 1.25 * 144.3 = 180.4 A -> 200 A
CEC Inverters.csv for Chint Power Systems America: CPS ECB200KTL/US-800 {800V}: Paco=200000.0 W, Vac=800 V, Vdcmax=1500.0 V, Eff=97.55%.
Result: Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (800V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Chint Power Systems America: CPS ECB200KTL/US-800 {800V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Chint Power Systems America: CPS ECB200KTL/US-800 {800V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 200,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 800 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 950 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 167.36 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.55% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2025-03-03 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Chint Power Systems America: CPS ECB200KTL/US-800 {800V} (800 V, 3-phase)?
Evaluates Chint Power Systems America: CPS ECB200KTL/US-800 {800V} (200 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (800V) | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (800V) | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (800V) | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (800V) | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (800V) | 240 A | 200 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Chint Power Systems America: CPS ECB200KTL/US-800 {800V}?
Sample PV string lengths aligned within 950-1,500 V MPPT and 1,500 V DC max at -10 C. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 23 to 26 panels | 15.34 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 29 to 35 panels | 15.4 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 28 to 33 panels | 14.03 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 33 to 36 panels | 7.2 kW |
Which Competing Grid-Support Inverters Compare to Chint Power Systems America: CPS ECB200KTL/US-800 {800V}?
Competing CEC grid-support inverters near 200,000 W AC and 800 V, 3-phase, led by ABB: PVS-175-TL-POWER-MODULE-1-US {800V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: PVS-175-TL-POWER-MODULE-1-US {800V} ABB |
179,574 W | -20426 W | 800.0 V | 1200.0 V | 97.39% |
| ABB: PVS-175-TL-POWER-MODULE-2-US {800V} ABB |
179,574 W | -20426 W | 800.0 V | 1200.0 V | 97.39% |
| Sungrow Power Supply Co Ltd: SG250HX-US {800V} Sungrow Power Supply Co Ltd |
226,997 W | +26997 W | 800.0 V | 1300.0 V | 98.52% |
| ABB: PVS-166-TL-POWER-MODULE-1-US {800V} ABB |
165,954 W | -34046 W | 800.0 V | 1200.0 V | 98.26% |
What Are the Interconnection Limits and Best-Fit Uses for Chint Power Systems America: CPS ECB200KTL/US-800 {800V}?
Check Chint Power Systems America: CPS ECB200KTL/US-800 {800V} (200,000 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on Chint Power Systems America: CPS ECB200KTL/US-800 {800V}.
Chint Power Systems America: CPS ECB200KTL/US-800 {800V} Panel & Wire Spec
Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (144.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.55%) and MPPT window (950-1,500 V) directly against ABB: PVS-175-TL-POWER-MODULE-1-US {800V} (179,574 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Chint Power Systems America: CPS ECB200KTL/US-800 {800V} by Chint Power Systems America covering breaker sizing, MPPT limits, and 800 V, 3-phase interconnection.
What breaker and wire size does Chint Power Systems America: CPS ECB200KTL/US-800 {800V} require?
At 200,000 W continuous AC (800 V, 3-phase), continuous current is 144.3 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Chint Power Systems America: CPS ECB200KTL/US-800 {800V} require?
At 200,000 W AC and 800 V, 3-phase, continuous line current is 144.3 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (800V) or NEC 705.11 interconnection.
How does Chint Power Systems America: CPS ECB200KTL/US-800 {800V} compare to ABB: PVS-175-TL-POWER-MODULE-1-US {800V}?
Chint Power Systems America: CPS ECB200KTL/US-800 {800V} delivers 200,000 W AC at 97.55% CEC efficiency with a 1,500 V DC ceiling, while ABB: PVS-175-TL-POWER-MODULE-1-US {800V} outputs 179,574 W at 800 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)