Chint Power Systems America: SCH200K-T-US-480 {480V} outputs 200,000 W AC at 480 V, 3-phase (240.6 A continuous, 400 A OCPD), ranking #459 of 2,343 CEC inverters at 97.72% efficiency with a 900-1,300 V MPPT window and 1,300 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 200,000 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 400 A (parallel Cu feeders)
- CEC Efficiency
- 97.72%
How Does Chint Power Systems America: SCH200K-T-US-480 {480V} Compare Against Peer CEC Listings?
Breaker sizing (400 A), parallel Cu feeders wire rules, and DC input limits for Chint Power Systems America: SCH200K-T-US-480 {480V}.
For NEC 705.12 solar interconnection, Chint Power Systems America: SCH200K-T-US-480 {480V} outputs 240.6 A continuous AC at 480 V, 3-phase and needs a 400 A backfeed breaker on parallel Cu feeders (75 C). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Conversion efficiency scores 97.72% (#459 of 2,343, +0.90 pts vs overall CEC median).
Where Does Chint Power Systems America: SCH200K-T-US-480 {480V} Fall Across Listed CEC Models?
Output power comparison showing where Chint Power Systems America: SCH200K-T-US-480 {480V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Chint Power Systems America: SCH200K-T-US-480 {480V}?
Relative ranking of Chint Power Systems America: SCH200K-T-US-480 {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Chint Power Systems America: SCH200K-T-US-480 {480V}?
Snapshot of Chint Power Systems America: SCH200K-T-US-480 {480V} efficiency rank (#459), OCPD breaker size, MPPT span, and busbar verdict.
97.72% CEC Weighted Efficiency
-0.30 pts vs the 98.02% 480 V median; overall power rank #247 (200,000 W, top 10.7%; higher than 89.3% of peers).
400 A Required Backfeed OCPD
125% x 240.6 A = 300.8 A -> 400 A standard OCPD using parallel Cu feeders (75 C).
900 V - 1,300 V (Max 1,300 V DC)
Tracking span of 400.0 V; listed since 2025-07-21 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 200000.0W / 480 V 3-phase -> 240.6 A | Breaker >= 1.25 * 240.6 = 300.8 A -> 400 A
CEC Inverters.csv for Chint Power Systems America: SCH200K-T-US-480 {480V}: Paco=200000.0 W, Vac=480 V, Vdcmax=1300.0 V, Eff=97.72%.
Result: Min 400 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (480V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for Chint Power Systems America: SCH200K-T-US-480 {480V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Chint Power Systems America: SCH200K-T-US-480 {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 200,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,300 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 900 V - 1,300 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 204.663 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.72% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2025-07-21 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Chint Power Systems America: SCH200K-T-US-480 {480V} (480 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Chint Power Systems America: SCH200K-T-US-480 {480V} at 480 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (480V) | 120 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (480V) | 160 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With Chint Power Systems America: SCH200K-T-US-480 {480V}?
Minimum and maximum series solar module strings fitting Chint Power Systems America: SCH200K-T-US-480 {480V} MPPT and 1,300 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 21 to 23 panels | 13.57 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 27 to 30 panels | 13.2 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 27 to 29 panels | 12.32 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 32 panels (fixed) | 6.4 kW |
Which Competing Grid-Support Inverters Compare to Chint Power Systems America: SCH200K-T-US-480 {480V}?
Peer 480 V, 3-phase CEC inverters near 200,000 W AC output such as EPC Power Corp: HY LC12/6-7 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| EPC Power Corp: HY LC12/6-7 {480V} EPC Power Corp |
220,033 W | +20033 W | 480.0 V | 600.0 V | 95.51% |
| DYNAPOWER COMPANY LLC: MPS-250 {480V} DYNAPOWER COMPANY LLC |
248,910 W | +48910 W | 480.0 V | 600.0 V | 95.24% |
| DYNAPOWER COMPANY LLC: MPS-250HV {480V} DYNAPOWER COMPANY LLC |
249,619 W | +49619 W | 480.0 V | 830.0 V | 96.2% |
| EPC Power Corp: 50-100122 {480V} EPC Power Corp |
250,190 W | +50190 W | 480.0 V | 1250.0 V | 97.11% |
What Are the Interconnection Limits and Best-Fit Uses for Chint Power Systems America: SCH200K-T-US-480 {480V}?
Check Chint Power Systems America: SCH200K-T-US-480 {480V} (200,000 W AC, 400 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,300 V DC on Chint Power Systems America: SCH200K-T-US-480 {480V}.
Chint Power Systems America: SCH200K-T-US-480 {480V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 400 A OCPD breaker (240.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.72%) and MPPT window (900-1,300 V) directly against EPC Power Corp: HY LC12/6-7 {480V} (220,033 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Chint Power Systems America: SCH200K-T-US-480 {480V} by Chint Power Systems America covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Chint Power Systems America: SCH200K-T-US-480 {480V} require?
At 200,000 W continuous AC (480 V, 3-phase), continuous current is 240.6 A; 125% NEC 690.8/705.12 sizing requires a 400 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does Chint Power Systems America: SCH200K-T-US-480 {480V} require?
At 200,000 W AC and 480 V, 3-phase, continuous line current is 240.6 A, requiring a 400 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Chint Power Systems America: SCH200K-T-US-480 {480V} compare to EPC Power Corp: HY LC12/6-7 {480V}?
Chint Power Systems America: SCH200K-T-US-480 {480V} delivers 200,000 W AC at 97.72% CEC efficiency with a 1,300 V DC ceiling, while EPC Power Corp: HY LC12/6-7 {480V} outputs 220,033 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)