Manufacturer: Chint Power Systems America Registry: CEC Verified Engineering Specification

Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} outputs 320,000 W AC at 800 V, 3-phase (230.9 A continuous, 300 A OCPD), ranking #188 of 2,343 CEC inverters at 98.3% efficiency with a 880-1,300 V MPPT window and 1,300 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
320,000 W
AC Voltage
800 V, 3-phase
Min PV Breaker
300 A (parallel Cu feeders)
CEC Efficiency
98.3%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} Compare Against Peer CEC Listings?

CEC efficiency rank (#188), 880-1,300 V MPPT tracking, and panel fit for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}.

Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} from Chint Power Systems America outputs 230.9 A continuous AC at 800 V, 3-phase (320,000 W AC, rank #214). Paired with parallel Cu feeders conductors and a 300 A OCPD, its 98.3% CEC efficiency compares closely with Sungrow Power Supply Co Ltd: SG350HX-US {800V} (320,865 W). Keep NEC 690.7 winter string Voc below 1,300 V DC.

Where Does Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} at 320,000 W continuous AC output.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} (320,000 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACChint Power System: 320,000 W

What Dataset Percentiles Define Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}?

Dataset percentiles comparing Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} against 2,343 certified grid-support inverters nationwide. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} Technical ThresholdsPercentile comparison for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output320,000 WCEC Efficiency98.3%Backfeed Breaker300 A

What Do the Dataset Ranks Show for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}?

Engineering highlights for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} covering efficiency, parallel Cu feeders feeder, and panel compatibility.

Eff #188 / 2,343

98.3% CEC Weighted Efficiency

equal to the 98.3% 800 V median; overall power rank #214 (320,000 W, top 9.1%; higher than 90.9% of peers).

NEC 705.12 Check

300 A Required Backfeed OCPD

125% x 230.9 A = 288.6 A -> 300 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

880 V - 1,300 V (Max 1,300 V DC)

Tracking span of 420.0 V; listed since 2024-07-01 (grid-tied PV inverter).

Commercial / 3-Phase Fit

Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 800 V, 3-phase switchgear (200A Bus / 200A Main (800V) to 1,200A Bus / 1,200A Main (800V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 320000.0W / 800 V 3-phase -> 230.9 A | Breaker >= 1.25 * 230.9 = 288.6 A -> 300 A

CEC Inverters.csv for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}: Paco=320000.0 W, Vac=800 V, Vdcmax=1300.0 V, Eff=98.3%.

Result: Min 300 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (800V): Supply-Side Tap (705.11) / Dedicated Switchboard.

What Are the Published CEC Specifications for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}?

California Energy Commission Solar Equipment List parameters for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} (grid-tied PV inverter) interconnection.

Official California Energy Commission (NREL SAM) test parameters for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 320,000 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 800 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 1,300 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 880 V - 1,300 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 273.567 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.3% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2024-07-01 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} (800 V, 3-phase)?

Panelboard and switchgear backfeed allowances for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} (300 A OCPD). Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

Evaluates Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} (300 A required OCPD at 800 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (800V) 40 A 300 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (800V) 80 A 300 A Supply-Side Tap (705.11) / Dedicated Switchboard
600A Bus / 600A Main (800V) 120 A 300 A Supply-Side Tap (705.11) / Dedicated Switchboard
800A Bus / 800A Main (800V) 160 A 300 A Supply-Side Tap (705.11) / Dedicated Switchboard
1,200A Bus / 1,200A Main (800V) 240 A 300 A Supply-Side Tap (705.11) / Dedicated Switchboard

Which CEC PV Module Strings Pair With Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}?

Representative PV panel pairings verified under NEC 690.7 cold Voc for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}.

Sampled CEC PV modules aligned within 880.0-1300.0 V MPPT and 1300.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 21 to 23 panels 13.57 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 27 to 30 panels 13.2 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 26 to 29 panels 12.32 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 31 to 32 panels 6.4 kW

Which Competing Grid-Support Inverters Compare to Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}?

Four alternative CEC inverters matched to Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} (320,000 W AC), led by Sungrow Power Supply Co Ltd: SG350HX-US {800V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Sungrow Power Supply Co Ltd: SG350HX-US {800V}
Sungrow Power Supply Co Ltd
320,865 W +865 W 800.0 V 1330.0 V 98.28%
Ginlong Technologies Co Ltd: S6-GU350K-EHV-US-M12 {800V}
Ginlong Technologies Co Ltd
348,153 W +28153 W 800.0 V 1300.0 V 98.47%
Ginlong Technologies Co Ltd: S6-GU350K-EHV-US-M16 {800V}
Ginlong Technologies Co Ltd
348,488 W +28488 W 800.0 V 1300.0 V 98.47%
Delta Electronics: DP350U-US-XX {800V}
Delta Electronics
352,401 W +32401 W 800.0 V 1330.0 V 98.48%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}?

Check Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} (320,000 W AC, 300 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,300 V DC on Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}.

Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 300 A OCPD breaker (230.9 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.3%) and MPPT window (880-1,300 V) directly against Sungrow Power Supply Co Ltd: SG350HX-US {800V} (320,865 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} by Chint Power Systems America covering breaker sizing, MPPT limits, and 800 V, 3-phase interconnection.

What breaker and wire size does Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} require?

At 320,000 W continuous AC (800 V, 3-phase), continuous current is 230.9 A; 125% NEC 690.8/705.12 sizing requires a 300 A breaker and parallel Cu feeders (75 C) wire.

What commercial switchgear or feeder sizing does Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} require?

At 320,000 W AC and 800 V, 3-phase, continuous line current is 230.9 A, requiring a 300 A OCPD and 1,200A Bus / 1,200A Main (800V) or NEC 705.11 interconnection.

How does Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} compare to Sungrow Power Supply Co Ltd: SG350HX-US {800V}?

Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V} delivers 320,000 W AC at 98.3% CEC efficiency with a 1,300 V DC ceiling, while Sungrow Power Supply Co Ltd: SG350HX-US {800V} outputs 320,865 W at 800 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.