ABB: PVS-175-TL-POWER-MODULE-1-US {800V} outputs 179,574 W AC at 800 V, 3-phase (129.6 A continuous, 175 A OCPD), ranking #623 of 2,343 CEC inverters at 97.39% efficiency with a 850-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 179,574 W
- AC Voltage
- 800 V, 3-phase
- Min PV Breaker
- 175 A (2/0 AWG Cu)
- CEC Efficiency
- 97.39%
How Does ABB: PVS-175-TL-POWER-MODULE-1-US {800V} Compare Against Peer CEC Listings?
How ABB ABB: PVS-175-TL-POWER-MODULE-1-US {800V} compares on 97.39% efficiency, MPPT span, and 120% busbar interconnection. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
With a 850-1,200 V MPPT tracking band and 1,200 V DC ceiling, ABB: PVS-175-TL-POWER-MODULE-1-US {800V} handles 179,574 W continuous AC (140,426 W below the 320,000 W 800 V median). Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap. Installers comparing ABB against Chint Power Systems America: CPS ECB200KTL/US-800 {800V} (200,000 W) should verify whether listed since 2020-09-01 grid-support firmware meets local IEEE 1547 utility rules.
Where Does ABB: PVS-175-TL-POWER-MODULE-1-US {800V} Fall Across Listed CEC Models?
Position of ABB: PVS-175-TL-POWER-MODULE-1-US {800V} (179,574 W AC) relative to the 7,680 W CEC median inverter. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
What Dataset Percentiles Define ABB: PVS-175-TL-POWER-MODULE-1-US {800V}?
Percentile placement of ABB: PVS-175-TL-POWER-MODULE-1-US {800V} across AC power class, conversion efficiency, and backfeed breaker size. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
What Do the Dataset Ranks Show for ABB: PVS-175-TL-POWER-MODULE-1-US {800V}?
Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for ABB: PVS-175-TL-POWER-MODULE-1-US {800V}. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
97.39% CEC Weighted Efficiency
-0.91 pts vs the 98.3% 800 V median; overall power rank #254 (179,574 W, top 10.9%; higher than 89.1% of peers).
175 A Required Backfeed OCPD
125% x 129.6 A = 162.0 A -> 175 A standard OCPD using 2/0 AWG Cu (75 C).
850 V - 1,200 V (Max 1,200 V DC)
Tracking span of 350.0 V; listed since 2020-09-01 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 800 V, 3-phase switchgear (200A Bus / 200A Main (800V) to 1,200A Bus / 1,200A Main (800V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 179574.0W / 800 V 3-phase -> 129.6 A | Breaker >= 1.25 * 129.6 = 162.0 A -> 175 A
CEC Inverters.csv for ABB: PVS-175-TL-POWER-MODULE-1-US {800V}: Paco=179574.0 W, Vac=800 V, Vdcmax=1200.0 V, Eff=97.39%.
Result: Min 175 A breaker & 2/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (800V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for ABB: PVS-175-TL-POWER-MODULE-1-US {800V}?
Official California Energy Commission electrical test parameters, AC voltage, and DC limits for ABB: PVS-175-TL-POWER-MODULE-1-US {800V}. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 179,574 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 800 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 850 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 167.617 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.39% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2020-09-01 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to ABB: PVS-175-TL-POWER-MODULE-1-US {800V} (800 V, 3-phase)?
Check whether ABB: PVS-175-TL-POWER-MODULE-1-US {800V} (175 A breaker) fits without main breaker derate or supply-side taps. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (800V) | 40 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (800V) | 80 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (800V) | 120 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (800V) | 160 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (800V) | 240 A | 175 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With ABB: PVS-175-TL-POWER-MODULE-1-US {800V}?
Verified cold-weather (-10 C) series module counts matched to ABB: PVS-175-TL-POWER-MODULE-1-US {800V}'s 1,200 V DC ceiling. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 20 to 21 panels | 12.39 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 26 to 28 panels | 12.32 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 25 to 26 panels | 11.05 kW |
| Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515 | 515.0 W | 53.76 V | 21 to 22 panels | 11.33 kW |
Which Competing Grid-Support Inverters Compare to ABB: PVS-175-TL-POWER-MODULE-1-US {800V}?
Alternative CEC inverters comparable to ABB: PVS-175-TL-POWER-MODULE-1-US {800V}, including Chint Power Systems America: CPS ECB200KTL/US-800 {800V} (200,000 W) at 800 V, 3-phase.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chint Power Systems America: CPS ECB200KTL/US-800 {800V} Chint Power Systems America |
200,000 W | +20426 W | 800.0 V | 1500.0 V | 97.55% |
| Sungrow Power Supply Co Ltd: SG250HX-US {800V} Sungrow Power Supply Co Ltd |
226,997 W | +47423 W | 800.0 V | 1300.0 V | 98.52% |
| Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} Ginlong Technologies Co Ltd |
238,706 W | +59132 W | 800.0 V | 1300.0 V | 98.26% |
| CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V} CSI Solar Co Ltd |
255,013 W | +75439 W | 800.0 V | 1300.0 V | 98.34% |
What Are the Interconnection Limits and Best-Fit Uses for ABB: PVS-175-TL-POWER-MODULE-1-US {800V}?
Check ABB: PVS-175-TL-POWER-MODULE-1-US {800V} (179,574 W AC, 175 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on ABB: PVS-175-TL-POWER-MODULE-1-US {800V}.
ABB: PVS-175-TL-POWER-MODULE-1-US {800V} Panel & Wire Spec
Size 75 C copper conductors at 2/0 AWG Cu on a 175 A OCPD breaker (129.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.39%) and MPPT window (850-1,200 V) directly against Chint Power Systems America: CPS ECB200KTL/US-800 {800V} (200,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for ABB: PVS-175-TL-POWER-MODULE-1-US {800V} by ABB covering breaker sizing, MPPT limits, and 800 V, 3-phase interconnection. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
What breaker and wire size does ABB: PVS-175-TL-POWER-MODULE-1-US {800V} require?
At 179,574 W continuous AC (800 V, 3-phase), continuous current is 129.6 A; 125% NEC 690.8/705.12 sizing requires a 175 A breaker and 2/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does ABB: PVS-175-TL-POWER-MODULE-1-US {800V} require?
At 179,574 W AC and 800 V, 3-phase, continuous line current is 129.6 A, requiring a 175 A OCPD and 1,200A Bus / 1,200A Main (800V) or NEC 705.11 interconnection.
How does ABB: PVS-175-TL-POWER-MODULE-1-US {800V} compare to Chint Power Systems America: CPS ECB200KTL/US-800 {800V}?
ABB: PVS-175-TL-POWER-MODULE-1-US {800V} delivers 179,574 W AC at 97.39% CEC efficiency with a 1,200 V DC ceiling, while Chint Power Systems America: CPS ECB200KTL/US-800 {800V} outputs 200,000 W at 800 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)