Skip to main content
WireAndSun
Calculators
CEC Grid-Support Inverter

Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} — CEC Inverter Specifications

Manufacturer: Ginlong Technologies Co Ltd Registry: CEC Verified Engineering Specification

Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} outputs 238,706 W AC at 800 V, 3-phase (172.3 A continuous, 225 A OCPD), ranking #210 of 2,343 CEC inverters at 98.26% efficiency with a 860-1,300 V MPPT window and 1,300 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
238,706 W
AC Voltage
800 V, 3-phase
Min PV Breaker
225 A (4/0 AWG Cu)
CEC Efficiency
98.26%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 800 V, 3-phase grid-support overview for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}.

Rated at 238,706 W AC (172.3 A continuous), Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} ranks #210 of 2,343 CEC units at 98.26% efficiency (-0.04 pts vs the 98.3% 800 V median). Minimum 75 C copper conductor sizing for its 225 A circuit is 4/0 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 1,300 V DC at record local winter lows.

Where Does Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} Fall Across Listed CEC Models?

Marks Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} (238,706 W AC) across the California Energy Commission inverter AC capacity distribution.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} (238,706 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACGinlong Technologi: 238,706 W

What Dataset Percentiles Define Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?

Benchmarks Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} continuous AC output, 98.26% CEC weighted efficiency, and 225 A OCPD breaker demand.

Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} Technical ThresholdsPercentile comparison for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output238,706 WCEC Efficiency98.26%Backfeed Breaker225 A

What Do the Dataset Ranks Show for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?

Four key NEC 705.12 and California Energy Commission metrics defining Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} by Ginlong Technologies Co Ltd.

Eff #210 / 2,343

98.26% CEC Weighted Efficiency

-0.04 pts vs the 98.3% 800 V median; overall power rank #235 (238,706 W, top 10.0%; higher than 90.0% of peers).

NEC 705.12 Check

225 A Required Backfeed OCPD

125% x 172.3 A = 215.4 A -> 225 A standard OCPD using 4/0 AWG Cu (75 C).

MPPT Window

860 V - 1,300 V (Max 1,300 V DC)

Tracking span of 440.0 V; listed since 2023-01-23 (grid-tied PV inverter).

Commercial / 3-Phase Fit

Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 800 V, 3-phase switchgear (200A Bus / 200A Main (800V) to 1,200A Bus / 1,200A Main (800V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 238706.0W / 800 V 3-phase -> 172.3 A | Breaker >= 1.25 * 172.3 = 215.4 A -> 225 A

CEC Inverters.csv for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}: Paco=238706.0 W, Vac=800 V, Vdcmax=1300.0 V, Eff=98.26%.

Result: Min 225 A breaker & 4/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (800V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}.

Official California Energy Commission (NREL SAM) test parameters for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 238,706 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 800 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 1,300 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 860 V - 1,300 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 205.87 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.26% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2023-01-23 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} (800 V, 3-phase)?

Evaluates Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} (225 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} (225 A required OCPD at 800 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (800V) 40 A 225 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (800V) 80 A 225 A Supply-Side Tap (705.11) / Dedicated Switchboard
600A Bus / 600A Main (800V) 120 A 225 A Supply-Side Tap (705.11) / Dedicated Switchboard
800A Bus / 800A Main (800V) 160 A 225 A Supply-Side Tap (705.11) / Dedicated Switchboard
1,200A Bus / 1,200A Main (800V) 240 A 225 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?

Sample PV string lengths aligned within 860-1,300 V MPPT and 1,300 V DC max at -10 C. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Sampled CEC PV modules aligned within 860.0-1300.0 V MPPT and 1300.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 21 to 23 panels 13.57 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 26 to 30 panels 13.2 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 25 to 29 panels 12.32 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 30 to 32 panels 6.4 kW

Which Competing Grid-Support Inverters Compare to Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?

Competing CEC grid-support inverters near 238,706 W AC and 800 V, 3-phase, led by Sungrow Power Supply Co Ltd: SG250HX-US {800V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Sungrow Power Supply Co Ltd: SG250HX-US {800V}
Sungrow Power Supply Co Ltd
226,997 W -11709 W 800.0 V 1300.0 V 98.52%
CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V}
CSI Solar Co Ltd
255,013 W +16307 W 800.0 V 1300.0 V 98.34%
CSI Solar Co Ltd: CSI-255K-T800GL03-U {800V}
CSI Solar Co Ltd
255,013 W +16307 W 800.0 V 1300.0 V 98.34%
Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}
Chint Power Systems America
275,000 W +36294 W 800.0 V 1300.0 V 98.5%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?

Check Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} (238,706 W AC, 225 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,300 V DC on Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}.

Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} Panel & Wire Spec

Size 75 C copper conductors at 4/0 AWG Cu on a 225 A OCPD breaker (172.3 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.26%) and MPPT window (860-1,300 V) directly against Sungrow Power Supply Co Ltd: SG250HX-US {800V} (226,997 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} by Ginlong Technologies Co Ltd covering breaker sizing, MPPT limits, and 800 V, 3-phase interconnection.

What breaker and wire size does Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} require?

At 238,706 W continuous AC (800 V, 3-phase), continuous current is 172.3 A; 125% NEC 690.8/705.12 sizing requires a 225 A breaker and 4/0 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} require?

At 238,706 W AC and 800 V, 3-phase, continuous line current is 172.3 A, requiring a 225 A OCPD and 1,200A Bus / 1,200A Main (800V) or NEC 705.11 interconnection.

How does Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} compare to Sungrow Power Supply Co Ltd: SG250HX-US {800V}?

Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} delivers 238,706 W AC at 98.26% CEC efficiency with a 1,300 V DC ceiling, while Sungrow Power Supply Co Ltd: SG250HX-US {800V} outputs 226,997 W at 800 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.