Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} outputs 238,706 W AC at 800 V, 3-phase (172.3 A continuous, 225 A OCPD), ranking #210 of 2,343 CEC inverters at 98.26% efficiency with a 860-1,300 V MPPT window and 1,300 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 238,706 W
- AC Voltage
- 800 V, 3-phase
- Min PV Breaker
- 225 A (4/0 AWG Cu)
- CEC Efficiency
- 98.26%
How Does Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 800 V, 3-phase grid-support overview for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}.
Rated at 238,706 W AC (172.3 A continuous), Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} ranks #210 of 2,343 CEC units at 98.26% efficiency (-0.04 pts vs the 98.3% 800 V median). Minimum 75 C copper conductor sizing for its 225 A circuit is 4/0 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 1,300 V DC at record local winter lows.
Where Does Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} Fall Across Listed CEC Models?
Marks Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} (238,706 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?
Benchmarks Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} continuous AC output, 98.26% CEC weighted efficiency, and 225 A OCPD breaker demand.
What Do the Dataset Ranks Show for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?
Four key NEC 705.12 and California Energy Commission metrics defining Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} by Ginlong Technologies Co Ltd.
98.26% CEC Weighted Efficiency
-0.04 pts vs the 98.3% 800 V median; overall power rank #235 (238,706 W, top 10.0%; higher than 90.0% of peers).
225 A Required Backfeed OCPD
125% x 172.3 A = 215.4 A -> 225 A standard OCPD using 4/0 AWG Cu (75 C).
860 V - 1,300 V (Max 1,300 V DC)
Tracking span of 440.0 V; listed since 2023-01-23 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 800 V, 3-phase switchgear (200A Bus / 200A Main (800V) to 1,200A Bus / 1,200A Main (800V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 238706.0W / 800 V 3-phase -> 172.3 A | Breaker >= 1.25 * 172.3 = 215.4 A -> 225 A
CEC Inverters.csv for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}: Paco=238706.0 W, Vac=800 V, Vdcmax=1300.0 V, Eff=98.26%.
Result: Min 225 A breaker & 4/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (800V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 238,706 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 800 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,300 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 860 V - 1,300 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 205.87 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.26% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2023-01-23 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} (800 V, 3-phase)?
Evaluates Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} (225 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (800V) | 40 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (800V) | 80 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (800V) | 120 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (800V) | 160 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (800V) | 240 A | 225 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?
Sample PV string lengths aligned within 860-1,300 V MPPT and 1,300 V DC max at -10 C. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 21 to 23 panels | 13.57 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 26 to 30 panels | 13.2 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 25 to 29 panels | 12.32 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 30 to 32 panels | 6.4 kW |
Which Competing Grid-Support Inverters Compare to Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?
Competing CEC grid-support inverters near 238,706 W AC and 800 V, 3-phase, led by Sungrow Power Supply Co Ltd: SG250HX-US {800V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Sungrow Power Supply Co Ltd: SG250HX-US {800V} Sungrow Power Supply Co Ltd |
226,997 W | -11709 W | 800.0 V | 1300.0 V | 98.52% |
| CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V} CSI Solar Co Ltd |
255,013 W | +16307 W | 800.0 V | 1300.0 V | 98.34% |
| CSI Solar Co Ltd: CSI-255K-T800GL03-U {800V} CSI Solar Co Ltd |
255,013 W | +16307 W | 800.0 V | 1300.0 V | 98.34% |
| Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} Chint Power Systems America |
275,000 W | +36294 W | 800.0 V | 1300.0 V | 98.5% |
What Are the Interconnection Limits and Best-Fit Uses for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}?
Check Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} (238,706 W AC, 225 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,300 V DC on Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}.
Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} Panel & Wire Spec
Size 75 C copper conductors at 4/0 AWG Cu on a 225 A OCPD breaker (172.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.26%) and MPPT window (860-1,300 V) directly against Sungrow Power Supply Co Ltd: SG250HX-US {800V} (226,997 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} by Ginlong Technologies Co Ltd covering breaker sizing, MPPT limits, and 800 V, 3-phase interconnection.
What breaker and wire size does Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} require?
At 238,706 W continuous AC (800 V, 3-phase), continuous current is 172.3 A; 125% NEC 690.8/705.12 sizing requires a 225 A breaker and 4/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} require?
At 238,706 W AC and 800 V, 3-phase, continuous line current is 172.3 A, requiring a 225 A OCPD and 1,200A Bus / 1,200A Main (800V) or NEC 705.11 interconnection.
How does Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} compare to Sungrow Power Supply Co Ltd: SG250HX-US {800V}?
Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V} delivers 238,706 W AC at 98.26% CEC efficiency with a 1,300 V DC ceiling, while Sungrow Power Supply Co Ltd: SG250HX-US {800V} outputs 226,997 W at 800 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)