ABB: PVS-60-TL-S-R-US {480V} — CEC Inverter Specifications

Manufacturer: ABB Registry: CEC Verified Engineering Specification

ABB: PVS-60-TL-S-R-US {480V} outputs 60,033 W AC at 480 V, 3-phase (72.2 A continuous, 100 A OCPD), ranking #255 of 2,343 CEC inverters at 98.18% efficiency with a 570-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
60,033 W
AC Voltage
480 V, 3-phase
Min PV Breaker
100 A (3 AWG Cu)
CEC Efficiency
98.18%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does ABB: PVS-60-TL-S-R-US {480V} Compare Against Peer CEC Listings?

Breaker sizing (100 A), 3 AWG Cu wire rules, and DC input limits for ABB: PVS-60-TL-S-R-US {480V}. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

Classified as a grid-tied PV inverter (active in CEC directory), ABB: PVS-60-TL-S-R-US {480V} requires 90.2 A design capacity -> 100 A breaker using 3 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 98.18% (+1.36 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.

Where Does ABB: PVS-60-TL-S-R-US {480V} Fall Across Listed CEC Models?

Output power comparison showing where ABB: PVS-60-TL-S-R-US {480V} sits among all 2,343 CEC-listed grid-support inverters. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where ABB: PVS-60-TL-S-R-US {480V} (60,033 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACABB: PVS-60-TL-S-R: 60,033 W

What Dataset Percentiles Define ABB: PVS-60-TL-S-R-US {480V}?

Relative ranking of ABB: PVS-60-TL-S-R-US {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

ABB: PVS-60-TL-S-R-US {480V} Technical ThresholdsPercentile comparison for ABB: PVS-60-TL-S-R-US {480V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output60,033 WCEC Efficiency98.18%Backfeed Breaker100 A

What Do the Dataset Ranks Show for ABB: PVS-60-TL-S-R-US {480V}?

Snapshot of ABB: PVS-60-TL-S-R-US {480V} efficiency rank (#255), OCPD breaker size, MPPT span, and busbar verdict. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

Eff #255 / 2,343

98.18% CEC Weighted Efficiency

+0.16 pts vs the 98.02% 480 V median; overall power rank #401 (60,033 W, top 17.3%; higher than 82.7% of peers).

NEC 705.12 Check

100 A Required Backfeed OCPD

125% x 72.2 A = 90.2 A -> 100 A standard OCPD using 3 AWG Cu (75 C).

MPPT Window

570 V - 800 V (Max 800 V DC)

Tracking span of 230.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 60033.0W / 480 V 3-phase -> 72.2 A | Breaker >= 1.25 * 72.2 = 90.2 A -> 100 A

CEC Inverters.csv for ABB: PVS-60-TL-S-R-US {480V}: Paco=60033.0 W, Vac=480 V, Vdcmax=800.0 V, Eff=98.18%.

Result: Min 100 A breaker & 3 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for ABB: PVS-60-TL-S-R-US {480V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for ABB: PVS-60-TL-S-R-US {480V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Official California Energy Commission (NREL SAM) test parameters for ABB: PVS-60-TL-S-R-US {480V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 60,033 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 800 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 570 V - 800 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 84.9267 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.18% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: No (Grid-Tied PV) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to ABB: PVS-60-TL-S-R-US {480V} (480 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for ABB: PVS-60-TL-S-R-US {480V} at 480 V, 3-phase. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Evaluates ABB: PVS-60-TL-S-R-US {480V} (100 A required OCPD at 480 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (480V) 40 A 100 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (480V) 80 A 100 A Supply-Side Tap (705.11) / Dedicated Switchboard
600A Bus / 600A Main (480V) 120 A 100 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (480V) 160 A 100 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (480V) 240 A 100 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With ABB: PVS-60-TL-S-R-US {480V}?

Minimum and maximum series solar module strings fitting ABB: PVS-60-TL-S-R-US {480V} MPPT and 800 V limits. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Sampled CEC PV modules aligned within 570.0-800.0 V MPPT and 800.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 14 panels (fixed) 8.26 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 18 panels (fixed) 7.92 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 17 panels (fixed) 7.22 kW
Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515 515.0 W 53.76 V 14 panels (fixed) 7.21 kW

Which Competing Grid-Support Inverters Compare to ABB: PVS-60-TL-S-R-US {480V}?

Peer 480 V, 3-phase CEC inverters near 60,033 W AC output such as Delta Electronics: M60U_280 {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Delta Electronics: M60U_280 {480V}
Delta Electronics
60,019 W -14 W 480.0 V 840.0 V 98.51%
Canadian Solar Inc: CSI-60KTL-CT {480V}
Canadian Solar Inc
60,000 W -33 W 480.0 V 850.0 V 98.24%
Canadian Solar Inc: CSI-60KTL-GS {480V}
Canadian Solar Inc
60,000 W -33 W 480.0 V 720.0 V 98.34%
Chint Power Systems America: CPS SCA60KTL-DO/US-480 {480V}
Chint Power Systems America
60,000 W -33 W 480.0 V 850.0 V 98.25%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for ABB: PVS-60-TL-S-R-US {480V}?

Check ABB: PVS-60-TL-S-R-US {480V} (60,033 W AC, 100 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on ABB: PVS-60-TL-S-R-US {480V}.

ABB: PVS-60-TL-S-R-US {480V} Panel & Wire Spec

Size 75 C copper conductors at 3 AWG Cu on a 100 A OCPD breaker (72.2 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.18%) and MPPT window (570-800 V) directly against Delta Electronics: M60U_280 {480V} (60,019 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for ABB: PVS-60-TL-S-R-US {480V} by ABB covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

What breaker and wire size does ABB: PVS-60-TL-S-R-US {480V} require?

At 60,033 W continuous AC (480 V, 3-phase), continuous current is 72.2 A; 125% NEC 690.8/705.12 sizing requires a 100 A breaker and 3 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does ABB: PVS-60-TL-S-R-US {480V} require?

At 60,033 W AC and 480 V, 3-phase, continuous line current is 72.2 A, requiring a 100 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

How does ABB: PVS-60-TL-S-R-US {480V} compare to Delta Electronics: M60U_280 {480V}?

ABB: PVS-60-TL-S-R-US {480V} delivers 60,033 W AC at 98.18% CEC efficiency with a 800 V DC ceiling, while Delta Electronics: M60U_280 {480V} outputs 60,019 W at 480 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.