SMA America: SB50-1TP-US-40 {208V} outputs 5,000 W AC at 208 V, commercial single-phase (24.0 A continuous, 30 A OCPD), ranking #1,430 of 2,343 CEC inverters at 96.57% efficiency with a 220-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 5,000 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 30 A (10 AWG Cu)
- CEC Efficiency
- 96.57%
How Does SMA America: SB50-1TP-US-40 {208V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 208 V, commercial single-phase grid-support overview for SMA America: SB50-1TP-US-40 {208V}.
Rated at 5,000 W AC (24.0 A continuous), SMA America: SB50-1TP-US-40 {208V} ranks #1,430 of 2,343 CEC units at 96.57% efficiency (+0.16 pts vs the 96.41% 208 V median). Minimum 75 C copper conductor sizing for its 30 A circuit is 10 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 480 V DC at record local winter lows.
Where Does SMA America: SB50-1TP-US-40 {208V} Fall Across Listed CEC Models?
Marks SMA America: SB50-1TP-US-40 {208V} (5,000 W AC) across the California Energy Commission inverter AC capacity distribution. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
What Dataset Percentiles Define SMA America: SB50-1TP-US-40 {208V}?
Benchmarks SMA America: SB50-1TP-US-40 {208V} continuous AC output, 96.57% CEC weighted efficiency, and 30 A OCPD breaker demand.
What Do the Dataset Ranks Show for SMA America: SB50-1TP-US-40 {208V}?
Four key NEC 705.12 and California Energy Commission metrics defining SMA America: SB50-1TP-US-40 {208V} by SMA America. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
96.57% CEC Weighted Efficiency
+0.16 pts vs the 96.41% 208 V median; overall power rank #1,516 (5,000 W, below CEC median; higher than 33.9% of peers).
30 A Required Backfeed OCPD
125% x 24.0 A = 30.0 A -> 30 A standard OCPD using 10 AWG Cu (75 C).
220 V - 480 V (Max 480 V DC)
Tracking span of 260.0 V; listed since 2019-02-15 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 5000.0W / 208 V -> 24.0 A | Breaker >= 1.25 * 24.0 = 30.0 A -> 30 A
CEC Inverters.csv for SMA America: SB50-1TP-US-40 {208V}: Paco=5000.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=96.57%.
Result: Min 30 A breaker & 10 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SMA America: SB50-1TP-US-40 {208V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for SMA America: SB50-1TP-US-40 {208V}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 5,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 220 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 14.1849 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.57% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2019-02-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to SMA America: SB50-1TP-US-40 {208V} (208 V, commercial single-phase)?
Evaluates SMA America: SB50-1TP-US-40 {208V} (30 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 30 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 30 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 30 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 30 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 30 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SMA America: SB50-1TP-US-40 {208V}?
Sample PV string lengths aligned within 220-480 V MPPT and 480 V DC max at -10 C. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 6 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 7 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 7 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 8 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to SMA America: SB50-1TP-US-40 {208V}?
Competing CEC grid-support inverters near 5,000 W AC and 208 V, commercial single-phase, led by ABB: PVI-5000-OUTD-US-A {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: PVI-5000-OUTD-US-A {208V} ABB |
5,000 W | Tie (0 W) | 208.0 V | 480.0 V | 96.0% |
| ABB: PVI-5000-OUTD-US-Z-A {208V} ABB |
5,000 W | Tie (0 W) | 208.0 V | 480.0 V | 96.0% |
| ABB: PVI-5000-OUTD-US-Z-M-A {208V} ABB |
5,000 W | Tie (0 W) | 208.0 V | 480.0 V | 96.0% |
| Delta Electronics: E6-TL-US(AC) {208V} Delta Electronics |
5,000 W | Tie (0 W) | 208.0 V | 480.0 V | 97.6% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: SB50-1TP-US-40 {208V}?
Check SMA America: SB50-1TP-US-40 {208V} (5,000 W AC, 30 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on SMA America: SB50-1TP-US-40 {208V}.
SMA America: SB50-1TP-US-40 {208V} Panel & Wire Spec
Size 75 C copper conductors at 10 AWG Cu on a 30 A OCPD breaker (24.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.57%) and MPPT window (220-480 V) directly against ABB: PVI-5000-OUTD-US-A {208V} (5,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: SB50-1TP-US-40 {208V} by SMA America covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does SMA America: SB50-1TP-US-40 {208V} require?
At 5,000 W continuous AC (208 V, commercial single-phase), continuous current is 24.0 A; 125% NEC 690.8/705.12 sizing requires a 30 A breaker and 10 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: SB50-1TP-US-40 {208V} require?
At 5,000 W AC and 208 V, commercial single-phase, continuous line current is 24.0 A, requiring a 30 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does SMA America: SB50-1TP-US-40 {208V} compare to ABB: PVI-5000-OUTD-US-A {208V}?
SMA America: SB50-1TP-US-40 {208V} delivers 5,000 W AC at 96.57% CEC efficiency with a 480 V DC ceiling, while ABB: PVI-5000-OUTD-US-A {208V} outputs 5,000 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)