JA Solar JAM6-60-240/SI is a 240.0 W STC (212.9 W PTC) Mono-c-Si solar module ranking #20,160 of 21,677 CEC listings (below all-CEC median; higher than 6.1% of peers). It delivers 14.68% efficiency, 37.49 V Voc at 25 C, and 41.95 V cold Voc at -10 C (14 panels max per 600 V string).
- STC Wattage
- 240.0 W
- PTC Wattage
- 212.9 W
- Voc @ 25C
- 37.49 V
- Efficiency
- 14.68%
How Does JA Solar JAM6-60-240/SI Compare Against Peer CEC Listings?
Solar engineering breakdown for JA Solar JAM6-60-240/SI: PTC thermal retention, roof footprint, and cold Voc string bounds.
Measured at 240.0 W STC and 212.9 W PTC, JA Solar JAM6-60-240/SI sits -145.0 W vs all-CEC median (below all-CEC median; higher than 6.1% of peers) among 21,677 listed modules. Power density reaches 146.8 W/m2 (5.23 percentage points below 19.91% CEC median). Lower 37.49 V string voltage fits 14 panels in series at 14 F and pairs easily with microinverters, whereas 1,000 V commercial inverters handle up to 23 panels in series. Alternative peer AXITEC AC-240M/156-60S rates 240.0 W.
Where Does JA Solar JAM6-60-240/SI Fall Across Listed CEC Models?
Distribution marker showing JA Solar JAM6-60-240/SI (240.0 W) relative to the 385.0 W all-CEC solar panel median.
What Dataset Percentiles Define JA Solar JAM6-60-240/SI?
Dataset percentiles tracking JA Solar JAM6-60-240/SI power output, thermal retention ratio, and aperture efficiency against 21,677 models.
What Do the Dataset Ranks Show for JA Solar JAM6-60-240/SI?
Benchmark highlights for JA Solar JAM6-60-240/SI covering STC output, efficiency, 8 kW footprint, and OCPD breaker size.
240.0 W STC · Higher Than 6.1%
240.0 W STC (-145.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.
14.68% Aperture Efficiency
Power density 146.8 W/m2 (5.23 percentage points below 19.91% CEC median). PTC/STC ratio: 88.7% (rank #21,046).
14 Panels Max @ -10 C (600 V)
Cold Voc reaches 41.95 V at -10 C (587.3 V string) and 43.23 V at -20 C (13 max).
34 Panels = 8,160 W STC
Occupies 55.6 m2 (598 sq ft) producing 7,239 W PTC; NEC 690.8 OCPD floor is 13.32 A (15 A breaker).
NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula
Voc_cold = 37.49 * (1 + (-0.34/100) * (-10 - 25)) = 41.95 V | OCPD = 1.56 * 8.54 = 13.32 A
Inputs from CEC Modules.csv for JA Solar JAM6-60-240/SI: Voc=37.49 V, beta_Voc=-0.34%/C, Isc=8.54 A, STC=240.0 W, Area=1.635 m2.
Result: 14 panels max on 600 V (587.3 V); 34 panels for 8 kW (598 sq ft).
What Are the Published CEC Specifications for JA Solar JAM6-60-240/SI?
Official CEC datasheet figures for JA Solar JAM6-60-240/SI (Mono-c-Si) used in utility interconnection and permit reviews. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Nameplate Power (STC) | 240.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| Real-World Output (PTC) | 212.9 W (88.7% STC) | PVUSA Test Conditions rating used for utility interconnection |
| Open-Circuit Voltage (Voc) | 37.49 V | Primary cold-weather string sizing limit under NEC 690.7 |
| Short-Circuit Current (Isc) | 8.54 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| Max Power Voltage / Current | 30.56 V / 7.85 A | Inverter MPPT operating window alignment |
| Voc Temp Coefficient (beta_Voc) | -0.34 %/C | Negative slope governing voltage rise below 25C |
| Module Efficiency & Area | 14.68% (1.635 m2) | Array roof footprint density |
| Cell Count & Technology | 60 cells (Mono-c-Si) | Monofacial backsheet |
How Many JA Solar JAM6-60-240/SI Panels Build a 6 kW, 8 kW, or 10 kW Array?
How many JA Solar JAM6-60-240/SI modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.
| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| 6 kW Class | 25 | 6.0 kW | 440 sq ft | $1,502 | $2,539 |
| 8 kW Class | 34 | 8.16 kW | 598 sq ft | $2,042 | $3,454 |
| 10 kW Class | 42 | 10.08 kW | 739 sq ft | $2,523 | $4,266 |
Which Sibling Wattage & Trim Variants Belong to This JA Solar Series?
Consolidated JA Solar wattage variants sharing the JA Solar JAM6-60-240/SI mechanical and cell layout. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| JA Solar JAM6-60-235/SI | 235.0 W | 208.4 W | 37.19 V | 30.36 V | 14.37% |
| JA Solar JAM6-60-240/SI | 240.0 W | 212.9 W | 37.49 V | 30.56 V | 14.68% |
| JA Solar JAM6-60-245/SI | 245.0 W | 217.5 W | 37.74 V | 30.76 V | 14.98% |
How Many JA Solar JAM6-60-240/SI Modules Fit in a Cold-Weather String?
NEC 690.7(A) winter string table preventing overvoltage trips on JA Solar JAM6-60-240/SI (41.95 V at 14 F).
| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| -20 C (-4 F) | 43.23 V | 13 panels | 562.0 V | 23 panels |
| -10 C (14 F) | 41.95 V | 14 panels | 587.3 V | 23 panels |
| 0 C (32 F) | 40.68 V | 14 panels | 569.5 V | 24 panels |
| 25 C (77 F STC) | 37.49 V | 16 panels | 599.8 V | 26 panels |
Which Cross-Brand Solar Modules Compare Closest to JA Solar JAM6-60-240/SI?
Competing CEC solar panels closest to JA Solar JAM6-60-240/SI in nameplate wattage and Voc, starting with AXITEC AC-240M/156-60S.
| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| AXITEC AC-240M/156-60S AXITEC |
240.0 W | Tie (0 W) | 37.47 V | 14.79% | 90.4% |
| Heliene 60P240 Heliene |
240.0 W | Tie (0 W) | 37.55 V | 14.62% | 89.2% |
| AXITEC AC-240P/156-60B AXITEC |
240.0 W | Tie (0 W) | 37.4 V | 14.79% | 89.5% |
| Centrosolar America EP6 240 BW Centrosolar America |
240.0 W | Tie (0 W) | 37.64 V | 14.68% | 88.6% |
What Are the Design Limits and Best-Fit Uses for JA Solar JAM6-60-240/SI?
Evaluate JA Solar JAM6-60-240/SI (240.0 W STC, 37.49 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.
- Winter overvoltage boundary: at -20 C (-4 F), JA Solar JAM6-60-240/SI reaches 43.23 V per panel—exceeding 13 panels in series voids 600 V inverter warranties.
- Footprint constraint: 34 panels for an 8 kW build require 598 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 34 panels (598 sq ft).
- 2026 tax credit baseline: cash residential installs of JA Solar JAM6-60-240/SI carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.
JA Solar JAM6-60-240/SI 8 kW Residential Fit
Needs 34 modules (598 sq ft) with a 15 A string OCPD, offsetting ~$2,042/yr at US average tariffs.
Cold-Climate String Design (-10 C / -20 C)
Cap 600 V series strings at 14 panels (-10 C) or 13 panels (-20 C), or compare AXITEC AC-240M/156-60S.
Bifacial / High-Heat Roof Check
Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 212.9 W PTC.
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Technical answers for JA Solar JAM6-60-240/SI by JA Solar grounded in CEC test data and NEC 690.7/690.8 limits.
How many JA Solar JAM6-60-240/SI panels fit on a 600 V winter solar string?
At -10 C (14 F), JA Solar JAM6-60-240/SI cold Voc rises from 37.49 V to 41.95 V (beta_Voc -0.34%/C), capping a 600 V string at 14 panels (587.3 V).
How much roof area does an 8 kW array of JA Solar JAM6-60-240/SI need?
An 8 kW DC system uses 34 JA Solar JAM6-60-240/SI modules (8,160 W STC / 7,239 W PTC), covering roughly 598 sq ft and saving ~$2,042/yr at 18.54 c/kWh.
How does JA Solar JAM6-60-240/SI compare against AXITEC AC-240M/156-60S?
JA Solar JAM6-60-240/SI outputs 240.0 W STC (37.49 V Voc, rank #20,160 of 21,677), while AXITEC AC-240M/156-60S delivers 240.0 W STC; both comply with 2026 NEC 690.7 string sizing rules.
Sources
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)