JA Solar JAM6-60-235 — CEC Solar Module Specifications

Manufacturer: JA Solar Registry: CEC Verified Engineering Specification

JA Solar JAM6-60-235 is a 235.0 W STC (210.7 W PTC) Mono-c-Si solar module ranking #20,368 of 21,677 CEC listings (below all-CEC median; higher than 5.4% of peers). It delivers 14.37% efficiency, 37.31 V Voc at 25 C, and 41.49 V cold Voc at -10 C (14 panels max per 600 V string).

STC Wattage
235.0 W
PTC Wattage
210.7 W
Voc @ 25C
37.31 V
Efficiency
14.37%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does JA Solar JAM6-60-235 Compare Against Peer CEC Listings?

CEC rank, roof space requirements, and NEC 690.7/690.8 limits for JA Solar JAM6-60-235 (Mono-c-Si) residential solar systems.

JA Solar JAM6-60-235 delivers 143.7 W/m2 (5.54 percentage points below 19.91% CEC median) and typical 89.7% PTC-to-STC thermal output (210.7 W real-world rating), placing it as a compact residential or specialty off-grid module useful on tight dormer roofs or battery cabins, though 8 kW requires 35 panels (616 sq ft). At -4 F (-20 C), string voltage climbs to 42.68 V per unit, capping 600 V circuits at 14 panels. Compare specs directly with Gintech Energy GTE 235M (235.0 W).

Where Does JA Solar JAM6-60-235 Fall Across Listed CEC Models?

Comparison of JA Solar JAM6-60-235 (235.0 W STC) against all 21,677 California Energy Commission certified photovoltaic modules. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

STC Power Distribution Across 21,677 CEC Solar ModulesMarks where JA Solar JAM6-60-235 (235.0 W STC) stands relative to CEC photovoltaic modules. 18-79 W STC: 68 entries1879-140 W STC: 170 entries140-202 W STC: 413 entries202-263 W STC: 1,883 entries202263-325 W STC: 4,202 entries325-386 W STC: 4,219 entries386-448 W STC: 4,695 entries386448-509 W STC: 1,584 entries509-571 W STC: 2,290 entries571-632 W STC: 1,371 entries571632-694 W STC: 534 entries694-755 W STC: 248 entries694Median 385 W STCJA Solar JAM6-60-2: 235.0 W

What Dataset Percentiles Define JA Solar JAM6-60-235?

Relative ranking of JA Solar JAM6-60-235 across nameplate watts, 89.7% PTC thermal ratio, and module aperture efficiency. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

JA Solar JAM6-60-235 Engineering BenchmarksPercentile comparison of JA Solar JAM6-60-235 wattage, thermal retention, and efficiency. 0% (Low)50% Median100% (Top)STC Wattage235.0 WPTC/STC Retention89.7%Module Efficiency14.37%

What Do the Dataset Ranks Show for JA Solar JAM6-60-235?

Summary of JA Solar JAM6-60-235 output rank, 8 kW array size (35 panels), efficiency rating, and 600 V string limit.

Rank #20,368 / 21,677

235.0 W STC · Higher Than 5.4%

235.0 W STC (-150.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #20,552

14.37% Aperture Efficiency

Power density 143.7 W/m2 (5.54 percentage points below 19.91% CEC median). PTC/STC ratio: 89.7% (rank #19,653).

NEC 690.7 Limit

14 Panels Max @ -10 C (600 V)

Cold Voc reaches 41.49 V at -10 C (580.9 V string) and 42.68 V at -20 C (14 max).

8 kW Reference Array

35 Panels = 8,225 W STC

Occupies 57.2 m2 (616 sq ft) producing 7,374 W PTC; NEC 690.8 OCPD floor is 13.15 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 37.31 * (1 + (-0.32/100) * (-10 - 25)) = 41.49 V | OCPD = 1.56 * 8.43 = 13.15 A

Inputs from CEC Modules.csv for JA Solar JAM6-60-235: Voc=37.31 V, beta_Voc=-0.32%/C, Isc=8.43 A, STC=235.0 W, Area=1.635 m2.

Result: 14 panels max on 600 V (580.9 V); 35 panels for 8 kW (616 sq ft).

What Are the Published CEC Specifications for JA Solar JAM6-60-235?

Complete CEC test sheet for JA Solar JAM6-60-235 including Isc (8.43 A), Voc (37.31 V), and thermal temperature coefficients.

Official California Energy Commission (NREL SAM) test parameters for JA Solar JAM6-60-235.
ParameterMeasured / Listed ValueEngineering Significance
Nameplate Power (STC) 235.0 W Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell)
Real-World Output (PTC) 210.7 W (89.7% STC) PVUSA Test Conditions rating used for utility interconnection
Open-Circuit Voltage (Voc) 37.31 V Primary cold-weather string sizing limit under NEC 690.7
Short-Circuit Current (Isc) 8.43 A Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8
Max Power Voltage / Current 29.28 V / 8.03 A Inverter MPPT operating window alignment
Voc Temp Coefficient (beta_Voc) -0.32 %/C Negative slope governing voltage rise below 25C
Module Efficiency & Area 14.37% (1.635 m2) Array roof footprint density
Cell Count & Technology 60 cells (Mono-c-Si) Monofacial backsheet

How Many JA Solar JAM6-60-235 Panels Build a 6 kW, 8 kW, or 10 kW Array?

Residential array count and annual electric bill savings at 18.54 c/kWh US avg vs. California tariffs using JA Solar JAM6-60-235.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).
Target ArrayPanelsActual DCRoof AreaUS Avg ($/yr)CA High ($/yr)
6 kW Class 26 6.11 kW 458 sq ft $1,529 $2,586
8 kW Class 35 8.22 kW 616 sq ft $2,057 $3,479
10 kW Class 43 10.11 kW 757 sq ft $2,530 $4,279

Which Sibling Wattage & Trim Variants Belong to This JA Solar Series?

Related JA Solar power steps and black/silver trims consolidated into this JA Solar JAM6-60-235 series guide. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Sibling CEC listings grouped into the JA Solar JAM6-60-235 wattage tier to avoid duplicate 5W/trim datasheets.
Model VariantSTC (W)PTC (W)Voc (V)Vmp (V)Eff (%)
JA Solar JAM6-60-225 225.0 W 201.5 W 36.97 V 28.88 V 13.76%
JA Solar JAM6-60-230 230.0 W 206.1 W 37.14 V 29.08 V 14.07%
JA Solar JAM6-60-235 235.0 W 210.7 W 37.31 V 29.28 V 14.37%
JA Solar JAM6-60-240 240.0 W 215.3 W 37.48 V 29.48 V 14.68%

How Many JA Solar JAM6-60-235 Modules Fit in a Cold-Weather String?

Verify freezing-morning voltage rise for JA Solar JAM6-60-235 (37.31 V STC) before wiring 600 V or 1,000 V strings.

Computed from Voc=37.31V and beta_Voc=-0.32%/C across design ambient temperatures.
Ambient Min TempCold Voc / PanelMax Panels (600 V)600 V String VocMax Panels (1000 V)
-20 C (-4 F) 42.68 V 14 panels 597.5 V 23 panels
-10 C (14 F) 41.49 V 14 panels 580.9 V 24 panels
0 C (32 F) 40.29 V 14 panels 564.1 V 24 panels
25 C (77 F STC) 37.31 V 16 panels 597.0 V 26 panels

Which Cross-Brand Solar Modules Compare Closest to JA Solar JAM6-60-235?

Four comparable CEC modules such as Gintech Energy GTE 235M (235.0 W) for side-by-side solar quote checks. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.
Alternative ModuleSTC (W)Delta vs ThisVoc (V)Eff (%)PTC/STC
Gintech Energy GTE 235M
Gintech Energy
235.0 W Tie (0 W) 37.32 V 13.97% 89.5%
APOS Energy AS235
APOS Energy
235.0 W Tie (0 W) 37.34 V 14.17% 89.7%
AXITEC AC-235P/156-60S
AXITEC
235.0 W Tie (0 W) 37.16 V 14.48% 90.0%
Advance Power API-M235
Advance Power
235.0 W Tie (0 W) 37.5 V 14.35% 89.3%
What to Check & Best-Fit Scenarios

What Are the Design Limits and Best-Fit Uses for JA Solar JAM6-60-235?

Evaluate JA Solar JAM6-60-235 (235.0 W STC, 37.31 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

  • Winter overvoltage boundary: at -20 C (-4 F), JA Solar JAM6-60-235 reaches 42.68 V per panel—exceeding 14 panels in series voids 600 V inverter warranties.
  • Footprint constraint: 35 panels for an 8 kW build require 616 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 35 panels (616 sq ft).
  • 2026 tax credit baseline: cash residential installs of JA Solar JAM6-60-235 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

JA Solar JAM6-60-235 8 kW Residential Fit

Needs 35 modules (616 sq ft) with a 15 A string OCPD, offsetting ~$2,057/yr at US average tariffs.

Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 14 panels (-10 C) or 14 panels (-20 C), or compare Gintech Energy GTE 235M.

Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 210.7 W PTC.

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for JA Solar JAM6-60-235 by JA Solar grounded in CEC test data and NEC 690.7/690.8 limits.

How many JA Solar JAM6-60-235 panels fit on a 600 V winter solar string?

At -10 C (14 F), JA Solar JAM6-60-235 cold Voc rises from 37.31 V to 41.49 V (beta_Voc -0.32%/C), capping a 600 V string at 14 panels (580.9 V).

How much roof area does an 8 kW array of JA Solar JAM6-60-235 need?

An 8 kW DC system uses 35 JA Solar JAM6-60-235 modules (8,225 W STC / 7,374 W PTC), covering roughly 616 sq ft and saving ~$2,057/yr at 18.54 c/kWh.

How does JA Solar JAM6-60-235 compare against Gintech Energy GTE 235M?

JA Solar JAM6-60-235 outputs 235.0 W STC (37.31 V Voc, rank #20,368 of 21,677), while Gintech Energy GTE 235M delivers 235.0 W STC; both comply with 2026 NEC 690.7 string sizing rules.

Sources

  1. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.