Trystar LLC: OZPCS-RS40-FB1 {480V} outputs 39,540 W AC at 480 V, 3-phase (47.6 A continuous, 60 A OCPD), ranking #1,217 of 2,343 CEC inverters at 96.77% efficiency with a 550-820 V MPPT window and 820 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 39,540 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 96.77%
How Does Trystar LLC: OZPCS-RS40-FB1 {480V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for Trystar LLC: OZPCS-RS40-FB1 {480V}. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
Ranking #506 of 2,343 CEC inverters (top 21.7%; higher than 78.3% of peers), Trystar LLC: OZPCS-RS40-FB1 {480V} is a grid-tied PV inverter delivering 39,540 W continuous AC at 480 V, 3-phase (47.6 A continuous). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 96.77% (-1.25 pts vs the 98.02% 480 V median) against peers like Delta Electronics: M36U_120 {480V} (39,737 W).
Where Does Trystar LLC: OZPCS-RS40-FB1 {480V} Fall Across Listed CEC Models?
Marks Trystar LLC: OZPCS-RS40-FB1 {480V} (39,540 W AC) across the California Energy Commission inverter AC capacity distribution. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
What Dataset Percentiles Define Trystar LLC: OZPCS-RS40-FB1 {480V}?
Benchmarks Trystar LLC: OZPCS-RS40-FB1 {480V} continuous AC output, 96.77% CEC weighted efficiency, and 60 A OCPD breaker demand.
What Do the Dataset Ranks Show for Trystar LLC: OZPCS-RS40-FB1 {480V}?
Four key NEC 705.12 and California Energy Commission metrics defining Trystar LLC: OZPCS-RS40-FB1 {480V} by Trystar LLC. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
96.77% CEC Weighted Efficiency
-1.25 pts vs the 98.02% 480 V median; overall power rank #506 (39,540 W, top 21.7%; higher than 78.3% of peers).
60 A Required Backfeed OCPD
125% x 47.6 A = 59.5 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
550 V - 820 V (Max 820 V DC)
Tracking span of 270.0 V; active in CEC directory (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 39540.0W / 480 V 3-phase -> 47.6 A | Breaker >= 1.25 * 47.6 = 59.5 A -> 60 A
CEC Inverters.csv for Trystar LLC: OZPCS-RS40-FB1 {480V}: Paco=39540.0 W, Vac=480 V, Vdcmax=820.0 V, Eff=96.77%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Trystar LLC: OZPCS-RS40-FB1 {480V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Trystar LLC: OZPCS-RS40-FB1 {480V}. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 39,540 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 820 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 550 V - 820 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 58.3686 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.77% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Trystar LLC: OZPCS-RS40-FB1 {480V} (480 V, 3-phase)?
Evaluates Trystar LLC: OZPCS-RS40-FB1 {480V} (60 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 60 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 60 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 60 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 60 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Trystar LLC: OZPCS-RS40-FB1 {480V}?
Sample PV string lengths aligned within 550-820 V MPPT and 820 V DC max at -10 C. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 13 to 14 panels | 8.26 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 17 to 19 panels | 8.36 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 16 to 18 panels | 7.65 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 20 panels (fixed) | 4.0 kW |
Which Competing Grid-Support Inverters Compare to Trystar LLC: OZPCS-RS40-FB1 {480V}?
Competing CEC grid-support inverters near 39,540 W AC and 480 V, 3-phase, led by Delta Electronics: M36U_120 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: M36U_120 {480V} Delta Electronics |
39,737 W | +197 W | 480.0 V | 830.0 V | 97.97% |
| Delta Electronics: M36U_121 {480V} Delta Electronics |
39,737 W | +197 W | 480.0 V | 830.0 V | 97.97% |
| Delta Electronics: M36U_122 {480V} Delta Electronics |
39,737 W | +197 W | 480.0 V | 830.0 V | 97.97% |
| CSI Solar Co Ltd: CSI-40K-T480GL03-U {480V} CSI Solar Co Ltd |
39,841 W | +301 W | 480.0 V | 850.0 V | 98.02% |
What Are the Interconnection Limits and Best-Fit Uses for Trystar LLC: OZPCS-RS40-FB1 {480V}?
Check Trystar LLC: OZPCS-RS40-FB1 {480V} (39,540 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 820 V DC on Trystar LLC: OZPCS-RS40-FB1 {480V}.
Trystar LLC: OZPCS-RS40-FB1 {480V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (47.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.77%) and MPPT window (550-820 V) directly against Delta Electronics: M36U_120 {480V} (39,737 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Trystar LLC: OZPCS-RS40-FB1 {480V} by Trystar LLC covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Trystar LLC: OZPCS-RS40-FB1 {480V} require?
At 39,540 W continuous AC (480 V, 3-phase), continuous current is 47.6 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Trystar LLC: OZPCS-RS40-FB1 {480V} require?
At 39,540 W AC and 480 V, 3-phase, continuous line current is 47.6 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Trystar LLC: OZPCS-RS40-FB1 {480V} compare to Delta Electronics: M36U_120 {480V}?
Trystar LLC: OZPCS-RS40-FB1 {480V} delivers 39,540 W AC at 96.77% CEC efficiency with a 820 V DC ceiling, while Delta Electronics: M36U_120 {480V} outputs 39,737 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)