Skip to main content
WireAndSun
Calculators
CEC Grid-Support Inverter

Trystar LLC: OZPCS-RS40-Bxx {480V} — CEC Inverter Specifications

Manufacturer: Trystar LLC Registry: CEC Verified Engineering Specification

Trystar LLC: OZPCS-RS40-Bxx {480V} outputs 39,913 W AC at 480 V, 3-phase (48.0 A continuous, 60 A OCPD), ranking #918 of 2,343 CEC inverters at 97.07% efficiency with a 550-820 V MPPT window and 820 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
39,913 W
AC Voltage
480 V, 3-phase
Min PV Breaker
60 A (6 AWG Cu)
CEC Efficiency
97.07%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Trystar LLC: OZPCS-RS40-Bxx {480V} Compare Against Peer CEC Listings?

How Trystar LLC Trystar LLC: OZPCS-RS40-Bxx {480V} compares on 97.07% efficiency, MPPT span, and 120% busbar interconnection. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Trystar LLC certifies Trystar LLC: OZPCS-RS40-Bxx {480V} (grid-tied PV inverter, listed since 2024-04-02) at 39,913 W AC (10,087 W below the 50,000 W 480 V median). Its 820 V DC ceiling pairs with an MPPT window of 550-820 V (span 270.0 V). Under NEC 690.8/705.12, 125% sizing demands 6 AWG Cu conductors on a 60 A OCPD.

Where Does Trystar LLC: OZPCS-RS40-Bxx {480V} Fall Across Listed CEC Models?

Position of Trystar LLC: OZPCS-RS40-Bxx {480V} (39,913 W AC) relative to the 7,680 W CEC median inverter. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Trystar LLC: OZPCS-RS40-Bxx {480V} (39,913 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACTrystar LLC: OZPCS: 39,913 W

What Dataset Percentiles Define Trystar LLC: OZPCS-RS40-Bxx {480V}?

Percentile placement of Trystar LLC: OZPCS-RS40-Bxx {480V} across AC power class, conversion efficiency, and backfeed breaker size. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Trystar LLC: OZPCS-RS40-Bxx {480V} Technical ThresholdsPercentile comparison for Trystar LLC: OZPCS-RS40-Bxx {480V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output39,913 WCEC Efficiency97.07%Backfeed Breaker60 A

What Do the Dataset Ranks Show for Trystar LLC: OZPCS-RS40-Bxx {480V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for Trystar LLC: OZPCS-RS40-Bxx {480V}. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

Eff #918 / 2,343

97.07% CEC Weighted Efficiency

-0.95 pts vs the 98.02% 480 V median; overall power rank #492 (39,913 W, top 21.0%; higher than 79.0% of peers).

NEC 705.12 Check

60 A Required Backfeed OCPD

125% x 48.0 A = 60.0 A -> 60 A standard OCPD using 6 AWG Cu (75 C).

MPPT Window

550 V - 820 V (Max 820 V DC)

Tracking span of 270.0 V; listed since 2024-04-02 (grid-tied PV inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 39913.0W / 480 V 3-phase -> 48.0 A | Breaker >= 1.25 * 48.0 = 60.0 A -> 60 A

CEC Inverters.csv for Trystar LLC: OZPCS-RS40-Bxx {480V}: Paco=39913.0 W, Vac=480 V, Vdcmax=820.0 V, Eff=97.07%.

Result: Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Trystar LLC: OZPCS-RS40-Bxx {480V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for Trystar LLC: OZPCS-RS40-Bxx {480V}. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Official California Energy Commission (NREL SAM) test parameters for Trystar LLC: OZPCS-RS40-Bxx {480V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 39,913 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 820 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 550 V - 820 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 58.742 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 97.07% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2024-04-02 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to Trystar LLC: OZPCS-RS40-Bxx {480V} (480 V, 3-phase)?

Check whether Trystar LLC: OZPCS-RS40-Bxx {480V} (60 A breaker) fits without main breaker derate or supply-side taps. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Evaluates Trystar LLC: OZPCS-RS40-Bxx {480V} (60 A required OCPD at 480 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (480V) 40 A 60 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (480V) 80 A 60 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (480V) 120 A 60 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (480V) 160 A 60 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (480V) 240 A 60 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Trystar LLC: OZPCS-RS40-Bxx {480V}?

Verified cold-weather (-10 C) series module counts matched to Trystar LLC: OZPCS-RS40-Bxx {480V}'s 820 V DC ceiling.

Sampled CEC PV modules aligned within 550.0-820.0 V MPPT and 820.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 13 to 14 panels 8.26 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 17 to 19 panels 8.36 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 16 to 18 panels 7.65 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 20 panels (fixed) 4.0 kW

Which Competing Grid-Support Inverters Compare to Trystar LLC: OZPCS-RS40-Bxx {480V}?

Alternative CEC inverters comparable to Trystar LLC: OZPCS-RS40-Bxx {480V}, including CSI Solar Co Ltd: CSI-40K-T480GL01-UB {480V} (39,926 W) at 480 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
CSI Solar Co Ltd: CSI-40K-T480GL01-UB {480V}
CSI Solar Co Ltd
39,926 W +13 W 480.0 V 800.0 V 98.34%
Fortress Power LLC: FP-Nano-40k-N {480V}
Fortress Power LLC
39,844 W -69 W 480.0 V 850.0 V 97.38%
CSI Solar Co Ltd: CSI-40K-T480GL03-U {480V}
CSI Solar Co Ltd
39,841 W -72 W 480.0 V 850.0 V 98.02%
Canadian Solar Inc: CSI-40KTL-GS {480V}
Canadian Solar Inc
40,000 W +87 W 480.0 V 780.0 V 98.0%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Trystar LLC: OZPCS-RS40-Bxx {480V}?

Check Trystar LLC: OZPCS-RS40-Bxx {480V} (39,913 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 820 V DC on Trystar LLC: OZPCS-RS40-Bxx {480V}.

Trystar LLC: OZPCS-RS40-Bxx {480V} Panel & Wire Spec

Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (48.0 A continuous).

Alternative Inverter Comparison

Compare efficiency (97.07%) and MPPT window (550-820 V) directly against CSI Solar Co Ltd: CSI-40K-T480GL01-UB {480V} (39,926 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Trystar LLC: OZPCS-RS40-Bxx {480V} by Trystar LLC covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

What breaker and wire size does Trystar LLC: OZPCS-RS40-Bxx {480V} require?

At 39,913 W continuous AC (480 V, 3-phase), continuous current is 48.0 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Trystar LLC: OZPCS-RS40-Bxx {480V} require?

At 39,913 W AC and 480 V, 3-phase, continuous line current is 48.0 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

How does Trystar LLC: OZPCS-RS40-Bxx {480V} compare to CSI Solar Co Ltd: CSI-40K-T480GL01-UB {480V}?

Trystar LLC: OZPCS-RS40-Bxx {480V} delivers 39,913 W AC at 97.07% CEC efficiency with a 820 V DC ceiling, while CSI Solar Co Ltd: CSI-40K-T480GL01-UB {480V} outputs 39,926 W at 480 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.