Trystar LLC: OZPCS-EP40-000 {480V} outputs 39,540 W AC at 480 V, 3-phase (47.6 A continuous, 60 A OCPD), ranking #1,217 of 2,343 CEC inverters at 96.77% efficiency with a 550-820 V MPPT window and 820 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 39,540 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 96.77%
How Does Trystar LLC: OZPCS-EP40-000 {480V} Compare Against Peer CEC Listings?
CEC efficiency rank (#1,217), 550-820 V MPPT tracking, and panel fit for Trystar LLC: OZPCS-EP40-000 {480V}. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
Trystar LLC: OZPCS-EP40-000 {480V} from Trystar LLC outputs 47.6 A continuous AC at 480 V, 3-phase (39,540 W AC, rank #506). Paired with 6 AWG Cu conductors and a 60 A OCPD, its 96.77% CEC efficiency compares closely with Delta Electronics: M36U_120 {480V} (39,737 W). Keep NEC 690.7 winter string Voc below 820 V DC.
Where Does Trystar LLC: OZPCS-EP40-000 {480V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting Trystar LLC: OZPCS-EP40-000 {480V} at 39,540 W continuous AC output. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
What Dataset Percentiles Define Trystar LLC: OZPCS-EP40-000 {480V}?
Dataset percentiles comparing Trystar LLC: OZPCS-EP40-000 {480V} against 2,343 certified grid-support inverters nationwide. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
What Do the Dataset Ranks Show for Trystar LLC: OZPCS-EP40-000 {480V}?
Engineering highlights for Trystar LLC: OZPCS-EP40-000 {480V} covering efficiency, 6 AWG Cu feeder, and panel compatibility. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
96.77% CEC Weighted Efficiency
-1.25 pts vs the 98.02% 480 V median; overall power rank #506 (39,540 W, top 21.7%; higher than 78.3% of peers).
60 A Required Backfeed OCPD
125% x 47.6 A = 59.5 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
550 V - 820 V (Max 820 V DC)
Tracking span of 270.0 V; active in CEC directory (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 39540.0W / 480 V 3-phase -> 47.6 A | Breaker >= 1.25 * 47.6 = 59.5 A -> 60 A
CEC Inverters.csv for Trystar LLC: OZPCS-EP40-000 {480V}: Paco=39540.0 W, Vac=480 V, Vdcmax=820.0 V, Eff=96.77%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Trystar LLC: OZPCS-EP40-000 {480V}?
California Energy Commission Solar Equipment List parameters for Trystar LLC: OZPCS-EP40-000 {480V} (grid-tied PV inverter) interconnection. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 39,540 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 820 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 550 V - 820 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 58.3686 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.77% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Trystar LLC: OZPCS-EP40-000 {480V} (480 V, 3-phase)?
Panelboard and switchgear backfeed allowances for Trystar LLC: OZPCS-EP40-000 {480V} (60 A OCPD). Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 60 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 60 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 60 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 60 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Trystar LLC: OZPCS-EP40-000 {480V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for Trystar LLC: OZPCS-EP40-000 {480V}. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 13 to 14 panels | 8.26 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 17 to 19 panels | 8.36 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 16 to 18 panels | 7.65 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 20 panels (fixed) | 4.0 kW |
Which Competing Grid-Support Inverters Compare to Trystar LLC: OZPCS-EP40-000 {480V}?
Four alternative CEC inverters matched to Trystar LLC: OZPCS-EP40-000 {480V} (39,540 W AC), led by Delta Electronics: M36U_120 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: M36U_120 {480V} Delta Electronics |
39,737 W | +197 W | 480.0 V | 830.0 V | 97.97% |
| Delta Electronics: M36U_121 {480V} Delta Electronics |
39,737 W | +197 W | 480.0 V | 830.0 V | 97.97% |
| Delta Electronics: M36U_122 {480V} Delta Electronics |
39,737 W | +197 W | 480.0 V | 830.0 V | 97.97% |
| CSI Solar Co Ltd: CSI-40K-T480GL03-U {480V} CSI Solar Co Ltd |
39,841 W | +301 W | 480.0 V | 850.0 V | 98.02% |
What Are the Interconnection Limits and Best-Fit Uses for Trystar LLC: OZPCS-EP40-000 {480V}?
Check Trystar LLC: OZPCS-EP40-000 {480V} (39,540 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 820 V DC on Trystar LLC: OZPCS-EP40-000 {480V}.
Trystar LLC: OZPCS-EP40-000 {480V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (47.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.77%) and MPPT window (550-820 V) directly against Delta Electronics: M36U_120 {480V} (39,737 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Trystar LLC: OZPCS-EP40-000 {480V} by Trystar LLC covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Trystar LLC: OZPCS-EP40-000 {480V} require?
At 39,540 W continuous AC (480 V, 3-phase), continuous current is 47.6 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Trystar LLC: OZPCS-EP40-000 {480V} require?
At 39,540 W AC and 480 V, 3-phase, continuous line current is 47.6 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Trystar LLC: OZPCS-EP40-000 {480V} compare to Delta Electronics: M36U_120 {480V}?
Trystar LLC: OZPCS-EP40-000 {480V} delivers 39,540 W AC at 96.77% CEC efficiency with a 820 V DC ceiling, while Delta Electronics: M36U_120 {480V} outputs 39,737 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)