SolarEdge Technologies Ltd: SE5700H-US {208V} — CEC Inverter Specifications

Manufacturer: SolarEdge Technologies Ltd Registry: CEC Verified Engineering Specification

SolarEdge Technologies Ltd: SE5700H-US {208V} outputs 4,993 W AC at 208 V, commercial single-phase (24.0 A continuous, 30 A OCPD), ranking #37 of 2,343 CEC inverters at 98.68% efficiency with a 360-460 V MPPT window and 460 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
4,993 W
AC Voltage
208 V, commercial single-phase
Min PV Breaker
30 A (10 AWG Cu)
CEC Efficiency
98.68%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does SolarEdge Technologies Ltd: SE5700H-US {208V} Compare Against Peer CEC Listings?

CEC efficiency rank (#37), 360-460 V MPPT tracking, and panel fit for SolarEdge Technologies Ltd: SE5700H-US {208V}. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Operating at 208 V, commercial single-phase, SolarEdge Technologies Ltd: SE5700H-US {208V} converts DC array energy at 98.68% CEC weighted efficiency (top 1.7%; higher than 98.3% of peers) with a 460 V max DC input and 12.8096 A max input current for NEC 690.7 string safety. Compare this 4,993 W hybrid battery-capable inverter directly with Delta Electronics: E6-TL-US {208V} (4,992 W). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.

Where Does SolarEdge Technologies Ltd: SE5700H-US {208V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting SolarEdge Technologies Ltd: SE5700H-US {208V} at 4,993 W continuous AC output. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where SolarEdge Technologies Ltd: SE5700H-US {208V} (4,993 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACSolarEdge Technolo: 4,993 W

What Dataset Percentiles Define SolarEdge Technologies Ltd: SE5700H-US {208V}?

Dataset percentiles comparing SolarEdge Technologies Ltd: SE5700H-US {208V} against 2,343 certified grid-support inverters nationwide. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

SolarEdge Technologies Ltd: SE5700H-US {208V} Technical ThresholdsPercentile comparison for SolarEdge Technologies Ltd: SE5700H-US {208V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output4,993 WCEC Efficiency98.68%Backfeed Breaker30 A

What Do the Dataset Ranks Show for SolarEdge Technologies Ltd: SE5700H-US {208V}?

Engineering highlights for SolarEdge Technologies Ltd: SE5700H-US {208V} covering efficiency, 10 AWG Cu feeder, and panel compatibility. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.

Eff #37 / 2,343

98.68% CEC Weighted Efficiency

+2.27 pts vs the 96.41% 208 V median; overall power rank #1,551 (4,993 W, below CEC median; higher than 33.8% of peers).

NEC 705.12 Check

30 A Required Backfeed OCPD

125% x 24.0 A = 30.0 A -> 30 A standard OCPD using 10 AWG Cu (75 C).

MPPT Window

360 V - 460 V (Max 460 V DC)

Tracking span of 100.0 V; active in CEC directory (hybrid battery-capable inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 4993.0W / 208 V -> 24.0 A | Breaker >= 1.25 * 24.0 = 30.0 A -> 30 A

CEC Inverters.csv for SolarEdge Technologies Ltd: SE5700H-US {208V}: Paco=4993.0 W, Vac=208 V, Vdcmax=460.0 V, Eff=98.68%.

Result: Min 30 A breaker & 10 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for SolarEdge Technologies Ltd: SE5700H-US {208V}?

California Energy Commission Solar Equipment List parameters for SolarEdge Technologies Ltd: SE5700H-US {208V} (hybrid battery-capable inverter) interconnection. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Official California Energy Commission (NREL SAM) test parameters for SolarEdge Technologies Ltd: SE5700H-US {208V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 4,993 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 208 V, commercial single-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 460 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 360 V - 460 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 12.8096 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.68% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: Yes (Battery Capable) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to SolarEdge Technologies Ltd: SE5700H-US {208V} (208 V, commercial single-phase)?

Panelboard and switchgear backfeed allowances for SolarEdge Technologies Ltd: SE5700H-US {208V} (30 A OCPD). Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Evaluates SolarEdge Technologies Ltd: SE5700H-US {208V} (30 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (208V) 40 A 30 A PASS (120% Commercial Busbar)
400A Bus / 400A Main (208V) 80 A 30 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (208V) 120 A 30 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (208V) 160 A 30 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (208V) 240 A 30 A PASS (120% Commercial Busbar)

Which Competing Grid-Support Inverters Compare to SolarEdge Technologies Ltd: SE5700H-US {208V}?

Four alternative CEC inverters matched to SolarEdge Technologies Ltd: SE5700H-US {208V} (4,993 W AC), led by Delta Electronics: E6-TL-US {208V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Delta Electronics: E6-TL-US {208V}
Delta Electronics
4,992 W -1 W 208.0 V 480.0 V 97.13%
Delta Electronics: M6-TL-US {208V}
Delta Electronics
4,990 W -3 W 208.0 V 480.0 V 97.13%
ABB: PVI-5000-OUTD-US-A {208V}
ABB
5,000 W +7 W 208.0 V 480.0 V 96.0%
ABB: PVI-5000-OUTD-US-Z-A {208V}
ABB
5,000 W +7 W 208.0 V 480.0 V 96.0%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for SolarEdge Technologies Ltd: SE5700H-US {208V}?

Check SolarEdge Technologies Ltd: SE5700H-US {208V} (4,993 W AC, 30 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 460 V DC on SolarEdge Technologies Ltd: SE5700H-US {208V}.

SolarEdge Technologies Ltd: SE5700H-US {208V} Panel & Wire Spec

Size 75 C copper conductors at 10 AWG Cu on a 30 A OCPD breaker (24.0 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.68%) and MPPT window (360-460 V) directly against Delta Electronics: E6-TL-US {208V} (4,992 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SolarEdge Technologies Ltd: SE5700H-US {208V} by SolarEdge Technologies Ltd covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

What breaker and wire size does SolarEdge Technologies Ltd: SE5700H-US {208V} require?

At 4,993 W continuous AC (208 V, commercial single-phase), continuous current is 24.0 A; 125% NEC 690.8/705.12 sizing requires a 30 A breaker and 10 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does SolarEdge Technologies Ltd: SE5700H-US {208V} require?

At 4,993 W AC and 208 V, commercial single-phase, continuous line current is 24.0 A, requiring a 30 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

How does SolarEdge Technologies Ltd: SE5700H-US {208V} compare to Delta Electronics: E6-TL-US {208V}?

SolarEdge Technologies Ltd: SE5700H-US {208V} delivers 4,993 W AC at 98.68% CEC efficiency with a 460 V DC ceiling, while Delta Electronics: E6-TL-US {208V} outputs 4,992 W at 208 V, commercial single-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.