Delta Electronics: E6-TL-US {208V} outputs 4,992 W AC at 208 V, commercial single-phase (24.0 A continuous, 30 A OCPD), ranking #856 of 2,343 CEC inverters at 97.13% efficiency with a 200-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 4,992 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 30 A (10 AWG Cu)
- CEC Efficiency
- 97.13%
How Does Delta Electronics: E6-TL-US {208V} Compare Against Peer CEC Listings?
How Delta Electronics Delta Electronics: E6-TL-US {208V} compares on 97.13% efficiency, MPPT span, and 120% busbar interconnection. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
Delta Electronics certifies Delta Electronics: E6-TL-US {208V} (hybrid battery-capable inverter, listed since 2024-04-02) at 4,992 W AC (8 W below the 5,000 W 208 V median). Its 480 V DC ceiling pairs with an MPPT window of 200-480 V (span 280.0 V). Under NEC 690.8/705.12, 125% sizing demands 10 AWG Cu conductors on a 30 A OCPD.
Where Does Delta Electronics: E6-TL-US {208V} Fall Across Listed CEC Models?
Position of Delta Electronics: E6-TL-US {208V} (4,992 W AC) relative to the 7,680 W CEC median inverter. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
What Dataset Percentiles Define Delta Electronics: E6-TL-US {208V}?
Percentile placement of Delta Electronics: E6-TL-US {208V} across AC power class, conversion efficiency, and backfeed breaker size. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
What Do the Dataset Ranks Show for Delta Electronics: E6-TL-US {208V}?
Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for Delta Electronics: E6-TL-US {208V}. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
97.13% CEC Weighted Efficiency
+0.72 pts vs the 96.41% 208 V median; overall power rank #1,552 (4,992 W, below CEC median; higher than 33.8% of peers).
30 A Required Backfeed OCPD
125% x 24.0 A = 30.0 A -> 30 A standard OCPD using 10 AWG Cu (75 C).
200 V - 480 V (Max 480 V DC)
Tracking span of 280.0 V; listed since 2024-04-02 (hybrid battery-capable inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 4992.0W / 208 V -> 24.0 A | Breaker >= 1.25 * 24.0 = 30.0 A -> 30 A
CEC Inverters.csv for Delta Electronics: E6-TL-US {208V}: Paco=4992.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=97.13%.
Result: Min 30 A breaker & 10 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Delta Electronics: E6-TL-US {208V}?
Official California Energy Commission electrical test parameters, AC voltage, and DC limits for Delta Electronics: E6-TL-US {208V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 4,992 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 200 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 13.525 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.13% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2024-04-02 / Hybrid: Yes (Battery Capable) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Delta Electronics: E6-TL-US {208V} (208 V, commercial single-phase)?
Check whether Delta Electronics: E6-TL-US {208V} (30 A breaker) fits without main breaker derate or supply-side taps. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 30 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 30 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 30 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 30 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 30 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Delta Electronics: E6-TL-US {208V}?
Verified cold-weather (-10 C) series module counts matched to Delta Electronics: E6-TL-US {208V}'s 480 V DC ceiling.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 5 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 6 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 6 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 7 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to Delta Electronics: E6-TL-US {208V}?
Alternative CEC inverters comparable to Delta Electronics: E6-TL-US {208V}, including ABB: PVI-5000-OUTD-US-A {208V} (5,000 W) at 208 V, commercial single-phase.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: PVI-5000-OUTD-US-A {208V} ABB |
5,000 W | +8 W | 208.0 V | 480.0 V | 96.0% |
| ABB: PVI-5000-OUTD-US-Z-A {208V} ABB |
5,000 W | +8 W | 208.0 V | 480.0 V | 96.0% |
| ABB: PVI-5000-OUTD-US-Z-M-A {208V} ABB |
5,000 W | +8 W | 208.0 V | 480.0 V | 96.0% |
| ABB: UNO-DM-50-TL-PLUS-US-SB-RA {208V} ABB |
4,600 W | -392 W | 208.0 V | 480.0 V | 96.31% |
What Are the Interconnection Limits and Best-Fit Uses for Delta Electronics: E6-TL-US {208V}?
Check Delta Electronics: E6-TL-US {208V} (4,992 W AC, 30 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on Delta Electronics: E6-TL-US {208V}.
Delta Electronics: E6-TL-US {208V} Panel & Wire Spec
Size 75 C copper conductors at 10 AWG Cu on a 30 A OCPD breaker (24.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.13%) and MPPT window (200-480 V) directly against ABB: PVI-5000-OUTD-US-A {208V} (5,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Delta Electronics: E6-TL-US {208V} by Delta Electronics covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does Delta Electronics: E6-TL-US {208V} require?
At 4,992 W continuous AC (208 V, commercial single-phase), continuous current is 24.0 A; 125% NEC 690.8/705.12 sizing requires a 30 A breaker and 10 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Delta Electronics: E6-TL-US {208V} require?
At 4,992 W AC and 208 V, commercial single-phase, continuous line current is 24.0 A, requiring a 30 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does Delta Electronics: E6-TL-US {208V} compare to ABB: PVI-5000-OUTD-US-A {208V}?
Delta Electronics: E6-TL-US {208V} delivers 4,992 W AC at 97.13% CEC efficiency with a 480 V DC ceiling, while ABB: PVI-5000-OUTD-US-A {208V} outputs 5,000 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)