SMA America: STP24000TL-US-10 {480V} outputs 24,000 W AC at 480 V, 3-phase (28.9 A continuous, 40 A OCPD), ranking #394 of 2,343 CEC inverters at 97.87% efficiency with a 450-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 24,000 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 40 A (8 AWG Cu)
- CEC Efficiency
- 97.87%
How Does SMA America: STP24000TL-US-10 {480V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for SMA America: STP24000TL-US-10 {480V}. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
Rated at 24,000 W AC (28.9 A continuous), SMA America: STP24000TL-US-10 {480V} ranks #394 of 2,343 CEC units at 97.87% efficiency (-0.15 pts vs the 98.02% 480 V median). Minimum 75 C copper conductor sizing for its 40 A circuit is 8 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 800 V DC at record local winter lows.
Where Does SMA America: STP24000TL-US-10 {480V} Fall Across Listed CEC Models?
Marks SMA America: STP24000TL-US-10 {480V} (24,000 W AC) across the California Energy Commission inverter AC capacity distribution. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
What Dataset Percentiles Define SMA America: STP24000TL-US-10 {480V}?
Benchmarks SMA America: STP24000TL-US-10 {480V} continuous AC output, 97.87% CEC weighted efficiency, and 40 A OCPD breaker demand.
What Do the Dataset Ranks Show for SMA America: STP24000TL-US-10 {480V}?
Four key NEC 705.12 and California Energy Commission metrics defining SMA America: STP24000TL-US-10 {480V} by SMA America. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
97.87% CEC Weighted Efficiency
-0.15 pts vs the 98.02% 480 V median; overall power rank #618 (24,000 W, top 26.4%; higher than 73.6% of peers).
40 A Required Backfeed OCPD
125% x 28.9 A = 36.1 A -> 40 A standard OCPD using 8 AWG Cu (75 C).
450 V - 800 V (Max 800 V DC)
Tracking span of 350.0 V; listed since 2019-02-15 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 24000.0W / 480 V 3-phase -> 28.9 A | Breaker >= 1.25 * 28.9 = 36.1 A -> 40 A
CEC Inverters.csv for SMA America: STP24000TL-US-10 {480V}: Paco=24000.0 W, Vac=480 V, Vdcmax=800.0 V, Eff=97.87%.
Result: Min 40 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SMA America: STP24000TL-US-10 {480V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for SMA America: STP24000TL-US-10 {480V}. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 24,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 800 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 450 V - 800 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 34.4418 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.87% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2019-02-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to SMA America: STP24000TL-US-10 {480V} (480 V, 3-phase)?
Evaluates SMA America: STP24000TL-US-10 {480V} (40 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 40 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (480V) | 80 A | 40 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 40 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 40 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 40 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SMA America: STP24000TL-US-10 {480V}?
Sample PV string lengths aligned within 450-800 V MPPT and 800 V DC max at -10 C. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 11 to 14 panels | 8.26 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 14 to 18 panels | 7.92 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 14 to 17 panels | 7.22 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 16 to 19 panels | 3.8 kW |
Which Competing Grid-Support Inverters Compare to SMA America: STP24000TL-US-10 {480V}?
Competing CEC grid-support inverters near 24,000 W AC and 480 V, 3-phase, led by Fronius International GmbH: Fronius Symo 240-3 480 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Fronius International GmbH: Fronius Symo 240-3 480 {480V} Fronius International GmbH |
24,000 W | Tie (0 W) | 480.0 V | 800.0 V | 97.67% |
| Fronius International GmbH: Fronius Symo Advanced 240-3 480 {480V} Fronius International GmbH |
24,142 W | +142 W | 480.0 V | 800.0 V | 97.67% |
| Fronius International GmbH: Fronius Symo Advanced 240-3 480 Lite {480V} Fronius International GmbH |
24,142 W | +142 W | 480.0 V | 800.0 V | 97.67% |
| CSI Solar Co Ltd: CSI-25K-T480GL03-U {480V} CSI Solar Co Ltd |
24,888 W | +888 W | 480.0 V | 850.0 V | 98.37% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: STP24000TL-US-10 {480V}?
Check SMA America: STP24000TL-US-10 {480V} (24,000 W AC, 40 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on SMA America: STP24000TL-US-10 {480V}.
SMA America: STP24000TL-US-10 {480V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 40 A OCPD breaker (28.9 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.87%) and MPPT window (450-800 V) directly against Fronius International GmbH: Fronius Symo 240-3 480 {480V} (24,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: STP24000TL-US-10 {480V} by SMA America covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does SMA America: STP24000TL-US-10 {480V} require?
At 24,000 W continuous AC (480 V, 3-phase), continuous current is 28.9 A; 125% NEC 690.8/705.12 sizing requires a 40 A breaker and 8 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: STP24000TL-US-10 {480V} require?
At 24,000 W AC and 480 V, 3-phase, continuous line current is 28.9 A, requiring a 40 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does SMA America: STP24000TL-US-10 {480V} compare to Fronius International GmbH: Fronius Symo 240-3 480 {480V}?
SMA America: STP24000TL-US-10 {480V} delivers 24,000 W AC at 97.87% CEC efficiency with a 800 V DC ceiling, while Fronius International GmbH: Fronius Symo 240-3 480 {480V} outputs 24,000 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)