SMA America: STP 30-US-50 {480V} — CEC Inverter Specifications

Manufacturer: SMA America Registry: CEC Verified Engineering Specification

SMA America: STP 30-US-50 {480V} outputs 30,000 W AC at 480 V, 3-phase (36.1 A continuous, 50 A OCPD), ranking #331 of 2,343 CEC inverters at 98.04% efficiency with a 515-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
30,000 W
AC Voltage
480 V, 3-phase
Min PV Breaker
50 A (8 AWG Cu)
CEC Efficiency
98.04%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does SMA America: STP 30-US-50 {480V} Compare Against Peer CEC Listings?

Breaker sizing (50 A), 8 AWG Cu wire rules, and DC input limits for SMA America: STP 30-US-50 {480V}.

For NEC 705.12 solar interconnection, SMA America: STP 30-US-50 {480V} outputs 36.1 A continuous AC at 480 V, 3-phase and needs a 50 A backfeed breaker on 8 AWG Cu (75 C). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Conversion efficiency scores 98.04% (#331 of 2,343, +1.22 pts vs overall CEC median).

Where Does SMA America: STP 30-US-50 {480V} Fall Across Listed CEC Models?

Output power comparison showing where SMA America: STP 30-US-50 {480V} sits among all 2,343 CEC-listed grid-support inverters. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where SMA America: STP 30-US-50 {480V} (30,000 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACSMA America: STP 3: 30,000 W

What Dataset Percentiles Define SMA America: STP 30-US-50 {480V}?

Relative ranking of SMA America: STP 30-US-50 {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

SMA America: STP 30-US-50 {480V} Technical ThresholdsPercentile comparison for SMA America: STP 30-US-50 {480V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output30,000 WCEC Efficiency98.04%Backfeed Breaker50 A

What Do the Dataset Ranks Show for SMA America: STP 30-US-50 {480V}?

Snapshot of SMA America: STP 30-US-50 {480V} efficiency rank (#331), OCPD breaker size, MPPT span, and busbar verdict.

Eff #331 / 2,343

98.04% CEC Weighted Efficiency

+0.02 pts vs the 98.02% 480 V median; overall power rank #553 (30,000 W, top 23.9%; higher than 76.1% of peers).

NEC 705.12 Check

50 A Required Backfeed OCPD

125% x 36.1 A = 45.1 A -> 50 A standard OCPD using 8 AWG Cu (75 C).

MPPT Window

515 V - 800 V (Max 800 V DC)

Tracking span of 285.0 V; listed since 2023-11-01 (grid-tied PV inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 30000.0W / 480 V 3-phase -> 36.1 A | Breaker >= 1.25 * 36.1 = 45.1 A -> 50 A

CEC Inverters.csv for SMA America: STP 30-US-50 {480V}: Paco=30000.0 W, Vac=480 V, Vdcmax=800.0 V, Eff=98.04%.

Result: Min 50 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for SMA America: STP 30-US-50 {480V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SMA America: STP 30-US-50 {480V}. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Official California Energy Commission (NREL SAM) test parameters for SMA America: STP 30-US-50 {480V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 30,000 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 800 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 515 V - 800 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 42.8546 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.04% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2023-11-01 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to SMA America: STP 30-US-50 {480V} (480 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for SMA America: STP 30-US-50 {480V} at 480 V, 3-phase.

Evaluates SMA America: STP 30-US-50 {480V} (50 A required OCPD at 480 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (480V) 40 A 50 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (480V) 80 A 50 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (480V) 120 A 50 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (480V) 160 A 50 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (480V) 240 A 50 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With SMA America: STP 30-US-50 {480V}?

Minimum and maximum series solar module strings fitting SMA America: STP 30-US-50 {480V} MPPT and 800 V limits.

Sampled CEC PV modules aligned within 515.0-800.0 V MPPT and 800.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 13 to 14 panels 8.26 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 16 to 18 panels 7.92 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 15 to 17 panels 7.22 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 18 to 19 panels 3.8 kW

Which Competing Grid-Support Inverters Compare to SMA America: STP 30-US-50 {480V}?

Peer 480 V, 3-phase CEC inverters near 30,000 W AC output such as Canadian Solar Inc: CSI-30KTL-GS-FL {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Canadian Solar Inc: CSI-30KTL-GS-FL {480V}
Canadian Solar Inc
30,000 W Tie (0 W) 480.0 V 780.0 V 97.83%
CSI Solar Co Ltd: CSI-30KTL-GS-FLB {480V}
CSI Solar Co Ltd
30,000 W Tie (0 W) 480.0 V 780.0 V 97.88%
CE+T America Inc: 30C {480V}
CE+T America Inc
29,990 W -10 W 480.0 V 850.0 V 95.24%
CE+T America Inc: 30C3 {480V}
CE+T America Inc
29,990 W -10 W 480.0 V 850.0 V 95.24%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for SMA America: STP 30-US-50 {480V}?

Check SMA America: STP 30-US-50 {480V} (30,000 W AC, 50 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on SMA America: STP 30-US-50 {480V}.

SMA America: STP 30-US-50 {480V} Panel & Wire Spec

Size 75 C copper conductors at 8 AWG Cu on a 50 A OCPD breaker (36.1 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.04%) and MPPT window (515-800 V) directly against Canadian Solar Inc: CSI-30KTL-GS-FL {480V} (30,000 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SMA America: STP 30-US-50 {480V} by SMA America covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

What breaker and wire size does SMA America: STP 30-US-50 {480V} require?

At 30,000 W continuous AC (480 V, 3-phase), continuous current is 36.1 A; 125% NEC 690.8/705.12 sizing requires a 50 A breaker and 8 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does SMA America: STP 30-US-50 {480V} require?

At 30,000 W AC and 480 V, 3-phase, continuous line current is 36.1 A, requiring a 50 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

How does SMA America: STP 30-US-50 {480V} compare to Canadian Solar Inc: CSI-30KTL-GS-FL {480V}?

SMA America: STP 30-US-50 {480V} delivers 30,000 W AC at 98.04% CEC efficiency with a 800 V DC ceiling, while Canadian Solar Inc: CSI-30KTL-GS-FL {480V} outputs 30,000 W at 480 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.