Skip to main content
WireAndSun
Calculators
CEC Grid-Support Inverter

SMA America: SI27-US208-20 {208V} — CEC Inverter Specifications

Manufacturer: SMA America Registry: CEC Verified Engineering Specification

SMA America: SI27-US208-20 {208V} outputs 27,176 W AC at 208 V, 3-phase (75.4 A continuous, 100 A OCPD), ranking #2,241 of 2,343 CEC inverters at 95.14% efficiency with a 200-980 V MPPT window and 980 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
27,176 W
AC Voltage
208 V, 3-phase
Min PV Breaker
100 A (3 AWG Cu)
CEC Efficiency
95.14%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does SMA America: SI27-US208-20 {208V} Compare Against Peer CEC Listings?

How SMA America SMA America: SI27-US208-20 {208V} compares on 95.14% efficiency, MPPT span, and 120% busbar interconnection. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

With a 200-980 V MPPT tracking band and 980 V DC ceiling, SMA America: SI27-US208-20 {208V} handles 27,176 W continuous AC (22,176 W above the 5,000 W 208 V median). Commercial 208 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Installers comparing SMA America against Chint Power Systems America: CPS SCA25KTL-DO/US-208 {208V} (25,000 W) should verify whether active in CEC directory grid-support firmware meets local IEEE 1547 utility rules.

Where Does SMA America: SI27-US208-20 {208V} Fall Across Listed CEC Models?

Position of SMA America: SI27-US208-20 {208V} (27,176 W AC) relative to the 7,680 W CEC median inverter. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where SMA America: SI27-US208-20 {208V} (27,176 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACSMA America: SI27-: 27,176 W

What Dataset Percentiles Define SMA America: SI27-US208-20 {208V}?

Percentile placement of SMA America: SI27-US208-20 {208V} across AC power class, conversion efficiency, and backfeed breaker size. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

SMA America: SI27-US208-20 {208V} Technical ThresholdsPercentile comparison for SMA America: SI27-US208-20 {208V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output27,176 WCEC Efficiency95.14%Backfeed Breaker100 A

What Do the Dataset Ranks Show for SMA America: SI27-US208-20 {208V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for SMA America: SI27-US208-20 {208V}. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Eff #2,241 / 2,343

95.14% CEC Weighted Efficiency

-1.27 pts vs the 96.41% 208 V median; overall power rank #586 (27,176 W, top 25.0%; higher than 75.0% of peers).

NEC 705.12 Check

100 A Required Backfeed OCPD

125% x 75.4 A = 94.2 A -> 100 A standard OCPD using 3 AWG Cu (75 C).

MPPT Window

200 V - 980 V (Max 980 V DC)

Tracking span of 780.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 208 V, 3-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 27175.9W / 208 V 3-phase -> 75.4 A | Breaker >= 1.25 * 75.4 = 94.2 A -> 100 A

CEC Inverters.csv for SMA America: SI27-US208-20 {208V}: Paco=27175.9 W, Vac=208 V, Vdcmax=980.0 V, Eff=95.14%.

Result: Min 100 A breaker & 3 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for SMA America: SI27-US208-20 {208V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for SMA America: SI27-US208-20 {208V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Official California Energy Commission (NREL SAM) test parameters for SMA America: SI27-US208-20 {208V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 27,176 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 208 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 980 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 200 V - 980 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 36.8583 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 95.14% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: No (Grid-Tied PV) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to SMA America: SI27-US208-20 {208V} (208 V, 3-phase)?

Check whether SMA America: SI27-US208-20 {208V} (100 A breaker) fits without main breaker derate or supply-side taps. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Evaluates SMA America: SI27-US208-20 {208V} (100 A required OCPD at 208 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (208V) 40 A 100 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (208V) 80 A 100 A Supply-Side Tap (705.11) / Dedicated Switchboard
600A Bus / 600A Main (208V) 120 A 100 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (208V) 160 A 100 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (208V) 240 A 100 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With SMA America: SI27-US208-20 {208V}?

Verified cold-weather (-10 C) series module counts matched to SMA America: SI27-US208-20 {208V}'s 980 V DC ceiling.

Sampled CEC PV modules aligned within 200.0-980.0 V MPPT and 980.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 5 to 17 panels 10.03 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 6 to 23 panels 10.12 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 6 to 21 panels 8.93 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 7 to 24 panels 4.8 kW

Which Competing Grid-Support Inverters Compare to SMA America: SI27-US208-20 {208V}?

Alternative CEC inverters comparable to SMA America: SI27-US208-20 {208V}, including Chint Power Systems America: CPS SCA25KTL-DO/US-208 {208V} (25,000 W) at 208 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Chint Power Systems America: CPS SCA25KTL-DO/US-208 {208V}
Chint Power Systems America
25,000 W -2176 W 208.0 V 850.0 V 96.26%
CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V}
CSI Solar Co Ltd
29,878 W +2702 W 208.0 V 680.0 V 96.38%
EcoFlow Inc: EF-PCS-24 {208V 24kW}
EcoFlow Inc
24,291 W -2884 W 208.0 V 480.0 V 96.01%
EG4 Electronics LLC: IV-16000-HYB-AW-FX-xx {208V}
EG4 Electronics LLC
13,899 W -13277 W 208.0 V 440.0 V 96.46%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for SMA America: SI27-US208-20 {208V}?

Check SMA America: SI27-US208-20 {208V} (27,176 W AC, 100 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 208 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 980 V DC on SMA America: SI27-US208-20 {208V}.

SMA America: SI27-US208-20 {208V} Panel & Wire Spec

Size 75 C copper conductors at 3 AWG Cu on a 100 A OCPD breaker (75.4 A continuous).

Alternative Inverter Comparison

Compare efficiency (95.14%) and MPPT window (200-980 V) directly against Chint Power Systems America: CPS SCA25KTL-DO/US-208 {208V} (25,000 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SMA America: SI27-US208-20 {208V} by SMA America covering breaker sizing, MPPT limits, and 208 V, 3-phase interconnection.

What breaker and wire size does SMA America: SI27-US208-20 {208V} require?

At 27,176 W continuous AC (208 V, 3-phase), continuous current is 75.4 A; 125% NEC 690.8/705.12 sizing requires a 100 A breaker and 3 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does SMA America: SI27-US208-20 {208V} require?

At 27,176 W AC and 208 V, 3-phase, continuous line current is 75.4 A, requiring a 100 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

How does SMA America: SI27-US208-20 {208V} compare to Chint Power Systems America: CPS SCA25KTL-DO/US-208 {208V}?

SMA America: SI27-US208-20 {208V} delivers 27,176 W AC at 95.14% CEC efficiency with a 980 V DC ceiling, while Chint Power Systems America: CPS SCA25KTL-DO/US-208 {208V} outputs 25,000 W at 208 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.