SMA America: SHP FLEX-US-21 {385V} outputs 100,842 W AC at 385 V, 3-phase (151.2 A continuous, 200 A OCPD), ranking #422 of 2,343 CEC inverters at 97.8% efficiency with a 582-1,195 V MPPT window and 1,195 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 100,842 W
- AC Voltage
- 385 V, 3-phase
- Min PV Breaker
- 200 A (3/0 AWG Cu)
- CEC Efficiency
- 97.8%
How Does SMA America: SHP FLEX-US-21 {385V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 385 V, 3-phase grid-support overview for SMA America: SHP FLEX-US-21 {385V}.
Rated at 100,842 W AC (151.2 A continuous), SMA America: SHP FLEX-US-21 {385V} ranks #422 of 2,343 CEC units at 97.8% efficiency (+0.96 pts vs the 96.84% 385 V median). Minimum 75 C copper conductor sizing for its 200 A circuit is 3/0 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 1,195 V DC at record local winter lows.
Where Does SMA America: SHP FLEX-US-21 {385V} Fall Across Listed CEC Models?
Marks SMA America: SHP FLEX-US-21 {385V} (100,842 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define SMA America: SHP FLEX-US-21 {385V}?
Benchmarks SMA America: SHP FLEX-US-21 {385V} continuous AC output, 97.8% CEC weighted efficiency, and 200 A OCPD breaker demand.
What Do the Dataset Ranks Show for SMA America: SHP FLEX-US-21 {385V}?
Four key NEC 705.12 and California Energy Commission metrics defining SMA America: SHP FLEX-US-21 {385V} by SMA America.
97.8% CEC Weighted Efficiency
+0.96 pts vs the 96.84% 385 V median; overall power rank #329 (100,842 W, top 14.1%; higher than 85.9% of peers).
200 A Required Backfeed OCPD
125% x 151.2 A = 189.0 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).
582 V - 1,195 V (Max 1,195 V DC)
Tracking span of 613.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 385 V, 3-phase switchgear (200A Bus / 200A Main (385V) to 1,200A Bus / 1,200A Main (385V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 100842.0W / 385 V 3-phase -> 151.2 A | Breaker >= 1.25 * 151.2 = 189.0 A -> 200 A
CEC Inverters.csv for SMA America: SHP FLEX-US-21 {385V}: Paco=100842.0 W, Vac=385 V, Vdcmax=1195.0 V, Eff=97.8%.
Result: Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (385V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SMA America: SHP FLEX-US-21 {385V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for SMA America: SHP FLEX-US-21 {385V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 100,842 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 385 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,195 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 582 V - 1,195 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 138.403 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.8% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to SMA America: SHP FLEX-US-21 {385V} (385 V, 3-phase)?
Evaluates SMA America: SHP FLEX-US-21 {385V} (200 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (385V) | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (385V) | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (385V) | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (385V) | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (385V) | 240 A | 200 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SMA America: SHP FLEX-US-21 {385V}?
Sample PV string lengths aligned within 582-1,195 V MPPT and 1,195 V DC max at -10 C. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 14 to 21 panels | 12.39 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 18 to 28 panels | 12.32 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 17 to 26 panels | 11.05 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 21 to 29 panels | 5.8 kW |
Which Competing Grid-Support Inverters Compare to SMA America: SHP FLEX-US-21 {385V}?
Competing CEC grid-support inverters near 100,842 W AC and 385 V, 3-phase, led by Yaskawa Solectria Solar: PVI-100TL-480 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Yaskawa Solectria Solar: PVI-100TL-480 {480V} Yaskawa Solectria Solar |
100,000 W | -842 W | 480.0 V | 850.0 V | 98.06% |
| Ginlong Technologies Co Ltd: S5-GC90K-US {480V} Ginlong Technologies Co Ltd |
89,449 W | -11393 W | 480.0 V | 850.0 V | 97.99% |
| Shenzhen Growatt New Energy Co Ltd: WIT 75K-HU-US {480V} Shenzhen Growatt New Energy Co Ltd |
74,589 W | -26253 W | 480.0 V | 800.0 V | 96.76% |
| CSI Solar Co Ltd: CSI-75K-T480GL03-U {480V} CSI Solar Co Ltd |
74,574 W | -26268 W | 480.0 V | 850.0 V | 98.17% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: SHP FLEX-US-21 {385V}?
Check SMA America: SHP FLEX-US-21 {385V} (100,842 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 385 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (385V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,195 V DC on SMA America: SHP FLEX-US-21 {385V}.
SMA America: SHP FLEX-US-21 {385V} Panel & Wire Spec
Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (151.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.8%) and MPPT window (582-1,195 V) directly against Yaskawa Solectria Solar: PVI-100TL-480 {480V} (100,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: SHP FLEX-US-21 {385V} by SMA America covering breaker sizing, MPPT limits, and 385 V, 3-phase interconnection.
What breaker and wire size does SMA America: SHP FLEX-US-21 {385V} require?
At 100,842 W continuous AC (385 V, 3-phase), continuous current is 151.2 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: SHP FLEX-US-21 {385V} require?
At 100,842 W AC and 385 V, 3-phase, continuous line current is 151.2 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (385V) or NEC 705.11 interconnection.
How does SMA America: SHP FLEX-US-21 {385V} compare to Yaskawa Solectria Solar: PVI-100TL-480 {480V}?
SMA America: SHP FLEX-US-21 {385V} delivers 100,842 W AC at 97.8% CEC efficiency with a 1,195 V DC ceiling, while Yaskawa Solectria Solar: PVI-100TL-480 {480V} outputs 100,000 W at 385 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)