SMA America: SHP FLEX-US-21 {380V} outputs 100,842 W AC at 380 V, 3-phase (153.2 A continuous, 200 A OCPD), ranking #422 of 2,343 CEC inverters at 97.8% efficiency with a 582-1,195 V MPPT window and 1,195 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 100,842 W
- AC Voltage
- 380 V, 3-phase
- Min PV Breaker
- 200 A (3/0 AWG Cu)
- CEC Efficiency
- 97.8%
How Does SMA America: SHP FLEX-US-21 {380V} Compare Against Peer CEC Listings?
CEC efficiency rank (#422), 582-1,195 V MPPT tracking, and panel fit for SMA America: SHP FLEX-US-21 {380V}. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
SMA America: SHP FLEX-US-21 {380V} from SMA America outputs 153.2 A continuous AC at 380 V, 3-phase (100,842 W AC, rank #329). Paired with 3/0 AWG Cu conductors and a 200 A OCPD, its 97.8% CEC efficiency compares closely with Yaskawa Solectria Solar: PVI-100TL-480 {480V} (100,000 W). Keep NEC 690.7 winter string Voc below 1,195 V DC.
Where Does SMA America: SHP FLEX-US-21 {380V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting SMA America: SHP FLEX-US-21 {380V} at 100,842 W continuous AC output. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
What Dataset Percentiles Define SMA America: SHP FLEX-US-21 {380V}?
Dataset percentiles comparing SMA America: SHP FLEX-US-21 {380V} against 2,343 certified grid-support inverters nationwide. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
What Do the Dataset Ranks Show for SMA America: SHP FLEX-US-21 {380V}?
Engineering highlights for SMA America: SHP FLEX-US-21 {380V} covering efficiency, 3/0 AWG Cu feeder, and panel compatibility.
97.8% CEC Weighted Efficiency
+0.72 pts vs the 97.08% 380 V median; overall power rank #329 (100,842 W, top 14.1%; higher than 85.9% of peers).
200 A Required Backfeed OCPD
125% x 153.2 A = 191.5 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).
582 V - 1,195 V (Max 1,195 V DC)
Tracking span of 613.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 380 V, 3-phase switchgear (200A Bus / 200A Main (380V) to 1,200A Bus / 1,200A Main (380V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 100842.0W / 380 V 3-phase -> 153.2 A | Breaker >= 1.25 * 153.2 = 191.5 A -> 200 A
CEC Inverters.csv for SMA America: SHP FLEX-US-21 {380V}: Paco=100842.0 W, Vac=380 V, Vdcmax=1195.0 V, Eff=97.8%.
Result: Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (380V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SMA America: SHP FLEX-US-21 {380V}?
California Energy Commission Solar Equipment List parameters for SMA America: SHP FLEX-US-21 {380V} (grid-tied PV inverter) interconnection. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 100,842 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 380 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,195 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 582 V - 1,195 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 138.403 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.8% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to SMA America: SHP FLEX-US-21 {380V} (380 V, 3-phase)?
Panelboard and switchgear backfeed allowances for SMA America: SHP FLEX-US-21 {380V} (200 A OCPD). Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (380V) | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (380V) | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (380V) | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (380V) | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (380V) | 240 A | 200 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SMA America: SHP FLEX-US-21 {380V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for SMA America: SHP FLEX-US-21 {380V}. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 14 to 21 panels | 12.39 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 18 to 28 panels | 12.32 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 17 to 26 panels | 11.05 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 21 to 29 panels | 5.8 kW |
Which Competing Grid-Support Inverters Compare to SMA America: SHP FLEX-US-21 {380V}?
Four alternative CEC inverters matched to SMA America: SHP FLEX-US-21 {380V} (100,842 W AC), led by Yaskawa Solectria Solar: PVI-100TL-480 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Yaskawa Solectria Solar: PVI-100TL-480 {480V} Yaskawa Solectria Solar |
100,000 W | -842 W | 480.0 V | 850.0 V | 98.06% |
| Ginlong Technologies Co Ltd: S5-GC90K-US {480V} Ginlong Technologies Co Ltd |
89,449 W | -11393 W | 480.0 V | 850.0 V | 97.99% |
| Shenzhen Growatt New Energy Co Ltd: WIT 75K-HU-US {480V} Shenzhen Growatt New Energy Co Ltd |
74,589 W | -26253 W | 480.0 V | 800.0 V | 96.76% |
| CSI Solar Co Ltd: CSI-75K-T480GL03-U {480V} CSI Solar Co Ltd |
74,574 W | -26268 W | 480.0 V | 850.0 V | 98.17% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: SHP FLEX-US-21 {380V}?
Check SMA America: SHP FLEX-US-21 {380V} (100,842 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 380 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (380V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,195 V DC on SMA America: SHP FLEX-US-21 {380V}.
SMA America: SHP FLEX-US-21 {380V} Panel & Wire Spec
Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (153.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.8%) and MPPT window (582-1,195 V) directly against Yaskawa Solectria Solar: PVI-100TL-480 {480V} (100,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: SHP FLEX-US-21 {380V} by SMA America covering breaker sizing, MPPT limits, and 380 V, 3-phase interconnection.
What breaker and wire size does SMA America: SHP FLEX-US-21 {380V} require?
At 100,842 W continuous AC (380 V, 3-phase), continuous current is 153.2 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: SHP FLEX-US-21 {380V} require?
At 100,842 W AC and 380 V, 3-phase, continuous line current is 153.2 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (380V) or NEC 705.11 interconnection.
How does SMA America: SHP FLEX-US-21 {380V} compare to Yaskawa Solectria Solar: PVI-100TL-480 {480V}?
SMA America: SHP FLEX-US-21 {380V} delivers 100,842 W AC at 97.8% CEC efficiency with a 1,195 V DC ceiling, while Yaskawa Solectria Solar: PVI-100TL-480 {480V} outputs 100,000 W at 380 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)