SMA America: SHP 165-US-21 {630V} outputs 165,000 W AC at 630 V, 3-phase (151.2 A continuous, 200 A OCPD), ranking #60 of 2,343 CEC inverters at 98.57% efficiency with a 925-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 165,000 W
- AC Voltage
- 630 V, 3-phase
- Min PV Breaker
- 200 A (3/0 AWG Cu)
- CEC Efficiency
- 98.57%
How Does SMA America: SHP 165-US-21 {630V} Compare Against Peer CEC Listings?
Breaker sizing (200 A), 3/0 AWG Cu wire rules, and DC input limits for SMA America: SHP 165-US-21 {630V}.
For NEC 705.12 solar interconnection, SMA America: SHP 165-US-21 {630V} outputs 151.2 A continuous AC at 630 V, 3-phase and needs a 200 A backfeed breaker on 3/0 AWG Cu (75 C). Commercial 630 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (630V) or NEC 705.11 supply-side tap. Conversion efficiency scores 98.57% (#60 of 2,343, +1.75 pts vs overall CEC median).
Where Does SMA America: SHP 165-US-21 {630V} Fall Across Listed CEC Models?
Output power comparison showing where SMA America: SHP 165-US-21 {630V} sits among all 2,343 CEC-listed grid-support inverters. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
What Dataset Percentiles Define SMA America: SHP 165-US-21 {630V}?
Relative ranking of SMA America: SHP 165-US-21 {630V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for SMA America: SHP 165-US-21 {630V}?
Snapshot of SMA America: SHP 165-US-21 {630V} efficiency rank (#60), OCPD breaker size, MPPT span, and busbar verdict.
98.57% CEC Weighted Efficiency
+0.63 pts vs the 97.94% 630 V median; overall power rank #268 (165,000 W, top 11.4%; higher than 88.6% of peers).
200 A Required Backfeed OCPD
125% x 151.2 A = 189.0 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).
925 V - 1,200 V (Max 1,200 V DC)
Tracking span of 275.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 630 V, 3-phase switchgear (200A Bus / 200A Main (630V) to 1,200A Bus / 1,200A Main (630V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 165000.0W / 630 V 3-phase -> 151.2 A | Breaker >= 1.25 * 151.2 = 189.0 A -> 200 A
CEC Inverters.csv for SMA America: SHP 165-US-21 {630V}: Paco=165000.0 W, Vac=630 V, Vdcmax=1200.0 V, Eff=98.57%.
Result: Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (630V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SMA America: SHP 165-US-21 {630V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SMA America: SHP 165-US-21 {630V}. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 165,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 630 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 925 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 168.411 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.57% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to SMA America: SHP 165-US-21 {630V} (630 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for SMA America: SHP 165-US-21 {630V} at 630 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (630V) | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (630V) | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (630V) | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (630V) | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (630V) | 240 A | 200 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SMA America: SHP 165-US-21 {630V}?
Minimum and maximum series solar module strings fitting SMA America: SHP 165-US-21 {630V} MPPT and 1,200 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 28 panels (fixed) | 12.32 kW |
Which Competing Grid-Support Inverters Compare to SMA America: SHP 165-US-21 {630V}?
Peer 630 V, 3-phase CEC inverters near 165,000 W AC output such as EPC Power Corp: 50-200100 {630V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| EPC Power Corp: 50-200100 {630V} EPC Power Corp |
491,262 W | +326262 W | 630.0 V | 1500.0 V | 98.39% |
| TMEIC: PVU-L0840GR {630V} TMEIC |
794,693 W | +629693 W | 630.0 V | 1200.0 V | 98.34% |
| TMEIC Corporation: PVU-L0840URN {630V} TMEIC Corporation |
796,468 W | +631468 W | 630.0 V | 1200.0 V | 98.51% |
| Sungrow Power Supply Co Ltd: SC1575UD-US {630V} Sungrow Power Supply Co Ltd |
1,582,996 W | +1417996 W | 630.0 V | 1500.0 V | 98.28% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: SHP 165-US-21 {630V}?
Check SMA America: SHP 165-US-21 {630V} (165,000 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 630 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (630V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on SMA America: SHP 165-US-21 {630V}.
SMA America: SHP 165-US-21 {630V} Panel & Wire Spec
Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (151.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.57%) and MPPT window (925-1,200 V) directly against EPC Power Corp: 50-200100 {630V} (491,262 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: SHP 165-US-21 {630V} by SMA America covering breaker sizing, MPPT limits, and 630 V, 3-phase interconnection.
What breaker and wire size does SMA America: SHP 165-US-21 {630V} require?
At 165,000 W continuous AC (630 V, 3-phase), continuous current is 151.2 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: SHP 165-US-21 {630V} require?
At 165,000 W AC and 630 V, 3-phase, continuous line current is 151.2 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (630V) or NEC 705.11 interconnection.
How does SMA America: SHP 165-US-21 {630V} compare to EPC Power Corp: 50-200100 {630V}?
SMA America: SHP 165-US-21 {630V} delivers 165,000 W AC at 98.57% CEC efficiency with a 1,200 V DC ceiling, while EPC Power Corp: 50-200100 {630V} outputs 491,262 W at 630 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)