SMA America: SHP 125-US-21 {480V} outputs 125,000 W AC at 480 V, 3-phase (150.4 A continuous, 200 A OCPD), ranking #282 of 2,343 CEC inverters at 98.13% efficiency with a 705-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 125,000 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 200 A (3/0 AWG Cu)
- CEC Efficiency
- 98.13%
How Does SMA America: SHP 125-US-21 {480V} Compare Against Peer CEC Listings?
How SMA America SMA America: SHP 125-US-21 {480V} compares on 98.13% efficiency, MPPT span, and 120% busbar interconnection.
SMA America certifies SMA America: SHP 125-US-21 {480V} (grid-tied PV inverter, active in CEC directory) at 125,000 W AC (75,000 W above the 50,000 W 480 V median). Its 1,200 V DC ceiling pairs with an MPPT window of 705-1,200 V (span 495.0 V). Under NEC 690.8/705.12, 125% sizing demands 3/0 AWG Cu conductors on a 200 A OCPD.
Where Does SMA America: SHP 125-US-21 {480V} Fall Across Listed CEC Models?
Position of SMA America: SHP 125-US-21 {480V} (125,000 W AC) relative to the 7,680 W CEC median inverter.
What Dataset Percentiles Define SMA America: SHP 125-US-21 {480V}?
Percentile placement of SMA America: SHP 125-US-21 {480V} across AC power class, conversion efficiency, and backfeed breaker size.
What Do the Dataset Ranks Show for SMA America: SHP 125-US-21 {480V}?
Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for SMA America: SHP 125-US-21 {480V}. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
98.13% CEC Weighted Efficiency
+0.11 pts vs the 98.02% 480 V median; overall power rank #300 (125,000 W, top 13.4%; higher than 86.6% of peers).
200 A Required Backfeed OCPD
125% x 150.4 A = 188.0 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).
705 V - 1,200 V (Max 1,200 V DC)
Tracking span of 495.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 125000.0W / 480 V 3-phase -> 150.4 A | Breaker >= 1.25 * 150.4 = 188.0 A -> 200 A
CEC Inverters.csv for SMA America: SHP 125-US-21 {480V}: Paco=125000.0 W, Vac=480 V, Vdcmax=1200.0 V, Eff=98.13%.
Result: Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SMA America: SHP 125-US-21 {480V}?
Official California Energy Commission electrical test parameters, AC voltage, and DC limits for SMA America: SHP 125-US-21 {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 125,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 705 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 153.47 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.13% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to SMA America: SHP 125-US-21 {480V} (480 V, 3-phase)?
Check whether SMA America: SHP 125-US-21 {480V} (200 A breaker) fits without main breaker derate or supply-side taps.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (480V) | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (480V) | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 200 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SMA America: SHP 125-US-21 {480V}?
Verified cold-weather (-10 C) series module counts matched to SMA America: SHP 125-US-21 {480V}'s 1,200 V DC ceiling.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 17 to 21 panels | 12.39 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 22 to 28 panels | 12.32 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 21 to 26 panels | 11.05 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 25 to 29 panels | 5.8 kW |
Which Competing Grid-Support Inverters Compare to SMA America: SHP 125-US-21 {480V}?
Alternative CEC inverters comparable to SMA America: SHP 125-US-21 {480V}, including Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} (125,000 W) at 480 V, 3-phase.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} Chint Power Systems America |
125,000 W | Tie (0 W) | 480.0 V | 1100.0 V | 97.2% |
| Delta Electronics: DES10JB125K01 {480V} Delta Electronics |
125,000 W | Tie (0 W) | 480.0 V | 1000.0 V | 97.01% |
| Delta Electronics: PCS125 {480V} Delta Electronics |
125,000 W | Tie (0 W) | 480.0 V | 1000.0 V | 97.01% |
| Ginlong Technologies Co Ltd: S5-GC125K-US {480V} Ginlong Technologies Co Ltd |
124,991 W | -9 W | 480.0 V | 850.0 V | 97.88% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: SHP 125-US-21 {480V}?
Check SMA America: SHP 125-US-21 {480V} (125,000 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on SMA America: SHP 125-US-21 {480V}.
SMA America: SHP 125-US-21 {480V} Panel & Wire Spec
Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (150.4 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.13%) and MPPT window (705-1,200 V) directly against Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} (125,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: SHP 125-US-21 {480V} by SMA America covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does SMA America: SHP 125-US-21 {480V} require?
At 125,000 W continuous AC (480 V, 3-phase), continuous current is 150.4 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: SHP 125-US-21 {480V} require?
At 125,000 W AC and 480 V, 3-phase, continuous line current is 150.4 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does SMA America: SHP 125-US-21 {480V} compare to Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}?
SMA America: SHP 125-US-21 {480V} delivers 125,000 W AC at 98.13% CEC efficiency with a 1,200 V DC ceiling, while Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} outputs 125,000 W at 480 V, 3-phase.