SMA America: SC 2800 UP-US 630V 2566A {630V} outputs 2,747,472 W AC at 630 V, 3-phase (2517.9 A continuous, 3,150 A OCPD), ranking #1,405 of 2,343 CEC inverters at 96.6% efficiency with a 921-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 2,747,472 W
- AC Voltage
- 630 V, 3-phase
- Min PV Breaker
- 3,150 A (parallel Cu feeders)
- CEC Efficiency
- 96.6%
How Does SMA America: SC 2800 UP-US 630V 2566A {630V} Compare Against Peer CEC Listings?
Breaker sizing (3,150 A), parallel Cu feeders wire rules, and DC input limits for SMA America: SC 2800 UP-US 630V 2566A {630V}.
For NEC 705.12 solar interconnection, SMA America: SC 2800 UP-US 630V 2566A {630V} outputs 2517.9 A continuous AC at 630 V, 3-phase and needs a 3,150 A backfeed breaker on parallel Cu feeders (75 C). Commercial 630 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (630V) or NEC 705.11 supply-side tap. Conversion efficiency scores 96.6% (#1,405 of 2,343, -0.22 pts vs overall CEC median).
Where Does SMA America: SC 2800 UP-US 630V 2566A {630V} Fall Across Listed CEC Models?
Output power comparison showing where SMA America: SC 2800 UP-US 630V 2566A {630V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define SMA America: SC 2800 UP-US 630V 2566A {630V}?
Relative ranking of SMA America: SC 2800 UP-US 630V 2566A {630V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for SMA America: SC 2800 UP-US 630V 2566A {630V}?
Snapshot of SMA America: SC 2800 UP-US 630V 2566A {630V} efficiency rank (#1,405), OCPD breaker size, MPPT span, and busbar verdict.
96.6% CEC Weighted Efficiency
-1.34 pts vs the 97.94% 630 V median; overall power rank #68 (2,747,472 W, top 2.9%; higher than 97.1% of peers).
3,150 A Required Backfeed OCPD
125% x 2517.9 A = 3147.4 A -> 3,150 A standard OCPD using parallel Cu feeders (75 C).
921 V - 1,200 V (Max 1,200 V DC)
Tracking span of 279.0 V; active in CEC directory (hybrid battery-capable inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 630 V, 3-phase switchgear (200A Bus / 200A Main (630V) to 1,200A Bus / 1,200A Main (630V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 2747472.0W / 630 V 3-phase -> 2517.9 A | Breaker >= 1.25 * 2517.9 = 3147.4 A -> 3,150 A
CEC Inverters.csv for SMA America: SC 2800 UP-US 630V 2566A {630V}: Paco=2747472.0 W, Vac=630 V, Vdcmax=1200.0 V, Eff=96.6%.
Result: Min 3,150 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (630V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for SMA America: SC 2800 UP-US 630V 2566A {630V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SMA America: SC 2800 UP-US 630V 2566A {630V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 2,747,472 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 630 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 921 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 2844.22 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.6% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to SMA America: SC 2800 UP-US 630V 2566A {630V} (630 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for SMA America: SC 2800 UP-US 630V 2566A {630V} at 630 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (630V) | 40 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (630V) | 80 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (630V) | 120 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (630V) | 160 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (630V) | 240 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With SMA America: SC 2800 UP-US 630V 2566A {630V}?
Minimum and maximum series solar module strings fitting SMA America: SC 2800 UP-US 630V 2566A {630V} MPPT and 1,200 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 28 panels (fixed) | 12.32 kW |
Which Competing Grid-Support Inverters Compare to SMA America: SC 2800 UP-US 630V 2566A {630V}?
Peer 630 V, 3-phase CEC inverters near 2,747,472 W AC output such as Sungrow Power Supply Co Ltd: SG3150U {630V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Sungrow Power Supply Co Ltd: SG3150U {630V} Sungrow Power Supply Co Ltd |
3,154,300 W | +406828 W | 630.0 V | 1300.0 V | 97.49% |
| Sichuan Clou Energy Electric Co Ltd: NEPCSH-3200 {630V} Sichuan Clou Energy Electric Co Ltd |
3,200,570 W | +453098 W | 630.0 V | 1500.0 V | 98.43% |
| INGETEAM POWER TECHNOLOGY SA: INGECON SUN 3825TL U C630 {630V} INGETEAM POWER TECHNOLOGY SA |
3,239,420 W | +491948 W | 630.0 V | 1300.0 V | 97.47% |
| INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3660TL U C630 {630V} INGETEAM POWER TECHNOLOGY SA |
3,239,420 W | +491948 W | 630.0 V | 1300.0 V | 97.47% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: SC 2800 UP-US 630V 2566A {630V}?
Check SMA America: SC 2800 UP-US 630V 2566A {630V} (2,747,472 W AC, 3,150 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 630 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (630V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on SMA America: SC 2800 UP-US 630V 2566A {630V}.
SMA America: SC 2800 UP-US 630V 2566A {630V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 3,150 A OCPD breaker (2517.9 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.6%) and MPPT window (921-1,200 V) directly against Sungrow Power Supply Co Ltd: SG3150U {630V} (3,154,300 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: SC 2800 UP-US 630V 2566A {630V} by SMA America covering breaker sizing, MPPT limits, and 630 V, 3-phase interconnection.
What breaker and wire size does SMA America: SC 2800 UP-US 630V 2566A {630V} require?
At 2,747,472 W continuous AC (630 V, 3-phase), continuous current is 2517.9 A; 125% NEC 690.8/705.12 sizing requires a 3,150 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: SC 2800 UP-US 630V 2566A {630V} require?
At 2,747,472 W AC and 630 V, 3-phase, continuous line current is 2517.9 A, requiring a 3,150 A OCPD and 1,200A Bus / 1,200A Main (630V) or NEC 705.11 interconnection.
How does SMA America: SC 2800 UP-US 630V 2566A {630V} compare to Sungrow Power Supply Co Ltd: SG3150U {630V}?
SMA America: SC 2800 UP-US 630V 2566A {630V} delivers 2,747,472 W AC at 96.6% CEC efficiency with a 1,200 V DC ceiling, while Sungrow Power Supply Co Ltd: SG3150U {630V} outputs 3,154,300 W at 630 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)