SMA America: SC-1850-US {385V} outputs 1,661,000 W AC at 385 V, 3-phase (2490.9 A continuous, 3,150 A OCPD), ranking #876 of 2,343 CEC inverters at 97.11% efficiency with a 570-950 V MPPT window and 950 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 1,661,000 W
- AC Voltage
- 385 V, 3-phase
- Min PV Breaker
- 3,150 A (parallel Cu feeders)
- CEC Efficiency
- 97.11%
How Does SMA America: SC-1850-US {385V} Compare Against Peer CEC Listings?
Breaker sizing (3,150 A), parallel Cu feeders wire rules, and DC input limits for SMA America: SC-1850-US {385V}.
Classified as a grid-tied PV inverter (listed since 2019-02-15), SMA America: SC-1850-US {385V} requires 3113.6 A design capacity -> 3,150 A breaker using parallel Cu feeders copper at 75 C terminals. Weighted efficiency sits at 97.11% (+0.29 pts vs overall CEC median) across 2,343 CEC models, while commercial 385 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (385v) or nec 705.11 supply-side tap.
Where Does SMA America: SC-1850-US {385V} Fall Across Listed CEC Models?
Output power comparison showing where SMA America: SC-1850-US {385V} sits among all 2,343 CEC-listed grid-support inverters. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
What Dataset Percentiles Define SMA America: SC-1850-US {385V}?
Relative ranking of SMA America: SC-1850-US {385V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for SMA America: SC-1850-US {385V}?
Snapshot of SMA America: SC-1850-US {385V} efficiency rank (#876), OCPD breaker size, MPPT span, and busbar verdict. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
97.11% CEC Weighted Efficiency
+0.27 pts vs the 96.84% 385 V median; overall power rank #123 (1,661,000 W, top 5.2%; higher than 94.8% of peers).
3,150 A Required Backfeed OCPD
125% x 2490.9 A = 3113.6 A -> 3,150 A standard OCPD using parallel Cu feeders (75 C).
570 V - 950 V (Max 950 V DC)
Tracking span of 380.0 V; listed since 2019-02-15 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 385 V, 3-phase switchgear (200A Bus / 200A Main (385V) to 1,200A Bus / 1,200A Main (385V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 1661000.0W / 385 V 3-phase -> 2490.9 A | Breaker >= 1.25 * 2490.9 = 3113.6 A -> 3,150 A
CEC Inverters.csv for SMA America: SC-1850-US {385V}: Paco=1661000.0 W, Vac=385 V, Vdcmax=950.0 V, Eff=97.11%.
Result: Min 3,150 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (385V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for SMA America: SC-1850-US {385V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SMA America: SC-1850-US {385V}. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 1,661,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 385 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 950 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 570 V - 950 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 2572.0 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.11% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2019-02-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to SMA America: SC-1850-US {385V} (385 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for SMA America: SC-1850-US {385V} at 385 V, 3-phase. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (385V) | 40 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (385V) | 80 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (385V) | 120 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (385V) | 160 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (385V) | 240 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With SMA America: SC-1850-US {385V}?
Minimum and maximum series solar module strings fitting SMA America: SC-1850-US {385V} MPPT and 950 V limits. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 14 to 16 panels | 9.44 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 18 to 22 panels | 9.68 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 17 to 21 panels | 8.93 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 20 to 23 panels | 4.6 kW |
Which Competing Grid-Support Inverters Compare to SMA America: SC-1850-US {385V}?
Peer 385 V, 3-phase CEC inverters near 1,661,000 W AC output such as Schneider Electric USA Inc: CS1666-3-NA {575V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Schneider Electric USA Inc: CS1666-3-NA {575V} Schneider Electric USA Inc |
1,666,000 W | +5000 W | 575.0 V | 1200.0 V | 97.54% |
| SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V} SINENG ELECTRIC CO LTD |
1,726,700 W | +65700 W | 690.0 V | 1500.0 V | 98.32% |
| Power Electronics: FS2250CU15O3 {600V} Power Electronics |
2,420,370 W | +759370 W | 600.0 V | 1200.0 V | 97.82% |
| INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3660TL U C480 {480V} INGETEAM POWER TECHNOLOGY SA |
2,467,620 W | +806620 W | 480.0 V | 1300.0 V | 96.63% |
What Are the Interconnection Limits and Best-Fit Uses for SMA America: SC-1850-US {385V}?
Check SMA America: SC-1850-US {385V} (1,661,000 W AC, 3,150 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 385 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (385V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 950 V DC on SMA America: SC-1850-US {385V}.
SMA America: SC-1850-US {385V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 3,150 A OCPD breaker (2490.9 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.11%) and MPPT window (570-950 V) directly against Schneider Electric USA Inc: CS1666-3-NA {575V} (1,666,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SMA America: SC-1850-US {385V} by SMA America covering breaker sizing, MPPT limits, and 385 V, 3-phase interconnection.
What breaker and wire size does SMA America: SC-1850-US {385V} require?
At 1,661,000 W continuous AC (385 V, 3-phase), continuous current is 2490.9 A; 125% NEC 690.8/705.12 sizing requires a 3,150 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does SMA America: SC-1850-US {385V} require?
At 1,661,000 W AC and 385 V, 3-phase, continuous line current is 2490.9 A, requiring a 3,150 A OCPD and 1,200A Bus / 1,200A Main (385V) or NEC 705.11 interconnection.
How does SMA America: SC-1850-US {385V} compare to Schneider Electric USA Inc: CS1666-3-NA {575V}?
SMA America: SC-1850-US {385V} delivers 1,661,000 W AC at 97.11% CEC efficiency with a 950 V DC ceiling, while Schneider Electric USA Inc: CS1666-3-NA {575V} outputs 1,666,000 W at 385 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)