DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} outputs 1,146,100 W AC at 690 V, 3-phase (959.0 A continuous, 1,200 A OCPD), ranking #48 of 2,343 CEC inverters at 98.61% efficiency with a 1,020-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 1,146,100 W
- AC Voltage
- 690 V, 3-phase
- Min PV Breaker
- 1,200 A (parallel Cu feeders)
- CEC Efficiency
- 98.61%
How Does DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} Compare Against Peer CEC Listings?
CEC efficiency rank (#48), 1,020-1,500 V MPPT tracking, and panel fit for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}.
Operating at 690 V, 3-phase, DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} converts DC array energy at 98.61% CEC weighted efficiency (top 2.1%; higher than 97.9% of peers) with a 1,500 V max DC input and 929.777 A max input current for NEC 690.7 string safety. Compare this 1,146,100 W grid-tied PV inverter directly with SINENG ELECTRIC CO LTD: EH-1250-HB-UD-US {690V} (1,250,740 W). Commercial 690 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (690V) or NEC 705.11 supply-side tap.
Where Does DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} at 1,146,100 W continuous AC output. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
What Dataset Percentiles Define DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}?
Dataset percentiles comparing DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} against 2,343 certified grid-support inverters nationwide. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
What Do the Dataset Ranks Show for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}?
Engineering highlights for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} covering efficiency, parallel Cu feeders feeder, and panel compatibility.
98.61% CEC Weighted Efficiency
+0.44 pts vs the 98.17% 690 V median; overall power rank #154 (1,146,100 W, top 6.6%; higher than 93.4% of peers).
1,200 A Required Backfeed OCPD
125% x 959.0 A = 1198.8 A -> 1,200 A standard OCPD using parallel Cu feeders (75 C).
1,020 V - 1,500 V (Max 1,500 V DC)
Tracking span of 480.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 690 V, 3-phase switchgear (200A Bus / 200A Main (690V) to 1,200A Bus / 1,200A Main (690V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 1146100.0W / 690 V 3-phase -> 959.0 A | Breaker >= 1.25 * 959.0 = 1198.8 A -> 1,200 A
CEC Inverters.csv for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}: Paco=1146100.0 W, Vac=690 V, Vdcmax=1500.0 V, Eff=98.61%.
Result: Min 1,200 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (690V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}?
California Energy Commission Solar Equipment List parameters for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} (grid-tied PV inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 1,146,100 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 690 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 1,020 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 929.777 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.61% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} (690 V, 3-phase)?
Panelboard and switchgear backfeed allowances for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} (1,200 A OCPD). Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (690V) | 40 A | 1,200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (690V) | 80 A | 1,200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (690V) | 120 A | 1,200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (690V) | 160 A | 1,200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (690V) | 240 A | 1,200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 24 to 26 panels | 15.34 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 31 to 35 panels | 15.4 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 30 to 33 panels | 14.03 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 36 panels (fixed) | 7.2 kW |
Which Competing Grid-Support Inverters Compare to DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}?
Four alternative CEC inverters matched to DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} (1,146,100 W AC), led by SINENG ELECTRIC CO LTD: EH-1250-HB-UD-US {690V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| SINENG ELECTRIC CO LTD: EH-1250-HB-UD-US {690V} SINENG ELECTRIC CO LTD |
1,250,740 W | +104640 W | 690.0 V | 1500.0 V | 98.05% |
| INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1800TL U B690 {690V} INGETEAM POWER TECHNOLOGY SA |
1,300,644 W | +154544 W | 690.0 V | 1200.0 V | 97.34% |
| Power Electronics: FS1275CU15 {690V} Power Electronics |
1,389,080 W | +242980 W | 690.0 V | 1200.0 V | 97.72% |
| EPC Power Corp: 50-100100 {690V} EPC Power Corp |
1,499,860 W | +353760 W | 690.0 V | 1250.0 V | 96.33% |
What Are the Interconnection Limits and Best-Fit Uses for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}?
Check DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} (1,146,100 W AC, 1,200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 690 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (690V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}.
DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 1,200 A OCPD breaker (959.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.61%) and MPPT window (1,020-1,500 V) directly against SINENG ELECTRIC CO LTD: EH-1250-HB-UD-US {690V} (1,250,740 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} by DYNAPOWER COMPANY LLC covering breaker sizing, MPPT limits, and 690 V, 3-phase interconnection.
What breaker and wire size does DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} require?
At 1,146,100 W continuous AC (690 V, 3-phase), continuous current is 959.0 A; 125% NEC 690.8/705.12 sizing requires a 1,200 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} require?
At 1,146,100 W AC and 690 V, 3-phase, continuous line current is 959.0 A, requiring a 1,200 A OCPD and 1,200A Bus / 1,200A Main (690V) or NEC 705.11 interconnection.
How does DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} compare to SINENG ELECTRIC CO LTD: EH-1250-HB-UD-US {690V}?
DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V} delivers 1,146,100 W AC at 98.61% CEC efficiency with a 1,500 V DC ceiling, while SINENG ELECTRIC CO LTD: EH-1250-HB-UD-US {690V} outputs 1,250,740 W at 690 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)