DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} outputs 1,353,700 W AC at 415 V, 3-phase (1883.3 A continuous, 2,400 A OCPD), ranking #1,120 of 2,343 CEC inverters at 96.9% efficiency with a 730-1,400 V MPPT window and 1,400 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 1,353,700 W
- AC Voltage
- 415 V, 3-phase
- Min PV Breaker
- 2,400 A (parallel Cu feeders)
- CEC Efficiency
- 96.9%
How Does DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} Compare Against Peer CEC Listings?
How DYNAPOWER COMPANY LLC DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} compares on 96.9% efficiency, MPPT span, and 120% busbar interconnection.
With a 730-1,400 V MPPT tracking band and 1,400 V DC ceiling, DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} handles 1,353,700 W continuous AC (331,226 W above the 1,022,474 W 415 V median). Commercial 415 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (415V) or NEC 705.11 supply-side tap. Installers comparing DYNAPOWER COMPANY LLC against Schneider Electric USA Inc: CS1666-3-NA {575V} (1,666,000 W) should verify whether active in CEC directory grid-support firmware meets local IEEE 1547 utility rules.
Where Does DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} Fall Across Listed CEC Models?
Position of DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} (1,353,700 W AC) relative to the 7,680 W CEC median inverter.
What Dataset Percentiles Define DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}?
Percentile placement of DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} across AC power class, conversion efficiency, and backfeed breaker size.
What Do the Dataset Ranks Show for DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}?
Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}.
96.9% CEC Weighted Efficiency
-0.40 pts vs the 97.3% 415 V median; overall power rank #140 (1,353,700 W, top 6.0%; higher than 94.0% of peers).
2,400 A Required Backfeed OCPD
125% x 1883.3 A = 2354.1 A -> 2,400 A standard OCPD using parallel Cu feeders (75 C).
730 V - 1,400 V (Max 1,400 V DC)
Tracking span of 670.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 415 V, 3-phase switchgear (200A Bus / 200A Main (415V) to 1,200A Bus / 1,200A Main (415V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 1353700.0W / 415 V 3-phase -> 1883.3 A | Breaker >= 1.25 * 1883.3 = 2354.1 A -> 2,400 A
CEC Inverters.csv for DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}: Paco=1353700.0 W, Vac=415 V, Vdcmax=1400.0 V, Eff=96.9%.
Result: Min 2,400 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (415V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}?
Official California Energy Commission electrical test parameters, AC voltage, and DC limits for DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 1,353,700 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 415 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,400 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 730 V - 1,400 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 1270.06 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.9% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} (415 V, 3-phase)?
Check whether DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} (2,400 A breaker) fits without main breaker derate or supply-side taps.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (415V) | 40 A | 2,400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (415V) | 80 A | 2,400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (415V) | 120 A | 2,400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (415V) | 160 A | 2,400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (415V) | 240 A | 2,400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}?
Verified cold-weather (-10 C) series module counts matched to DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}'s 1,400 V DC ceiling.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 18 to 24 panels | 14.16 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 22 to 33 panels | 14.52 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 22 to 31 panels | 13.18 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 26 to 34 panels | 6.8 kW |
Which Competing Grid-Support Inverters Compare to DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}?
Alternative CEC inverters comparable to DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}, including Schneider Electric USA Inc: CS1666-3-NA {575V} (1,666,000 W) at 415 V, 3-phase.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Schneider Electric USA Inc: CS1666-3-NA {575V} Schneider Electric USA Inc |
1,666,000 W | +312300 W | 575.0 V | 1200.0 V | 97.54% |
| SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V} SINENG ELECTRIC CO LTD |
1,726,700 W | +373000 W | 690.0 V | 1500.0 V | 98.32% |
| EPC Power Corp: 50-200100 {720V} EPC Power Corp |
561,806 W | -791894 W | 720.0 V | 1500.0 V | 98.58% |
| Power Electronics: FS2250CU15O3 {600V} Power Electronics |
2,420,370 W | +1066670 W | 600.0 V | 1200.0 V | 97.82% |
What Are the Interconnection Limits and Best-Fit Uses for DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}?
Check DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} (1,353,700 W AC, 2,400 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 415 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (415V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,400 V DC on DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}.
DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 2,400 A OCPD breaker (1883.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.9%) and MPPT window (730-1,400 V) directly against Schneider Electric USA Inc: CS1666-3-NA {575V} (1,666,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} by DYNAPOWER COMPANY LLC covering breaker sizing, MPPT limits, and 415 V, 3-phase interconnection.
What breaker and wire size does DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} require?
At 1,353,700 W continuous AC (415 V, 3-phase), continuous current is 1883.3 A; 125% NEC 690.8/705.12 sizing requires a 2,400 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} require?
At 1,353,700 W AC and 415 V, 3-phase, continuous line current is 1883.3 A, requiring a 2,400 A OCPD and 1,200A Bus / 1,200A Main (415V) or NEC 705.11 interconnection.
How does DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} compare to Schneider Electric USA Inc: CS1666-3-NA {575V}?
DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V} delivers 1,353,700 W AC at 96.9% CEC efficiency with a 1,400 V DC ceiling, while Schneider Electric USA Inc: CS1666-3-NA {575V} outputs 1,666,000 W at 415 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)