DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} outputs 691,248 W AC at 415 V, 3-phase (961.7 A continuous, 1,250 A OCPD), ranking #472 of 2,343 CEC inverters at 97.69% efficiency with a 630-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 691,248 W
- AC Voltage
- 415 V, 3-phase
- Min PV Breaker
- 1,250 A (parallel Cu feeders)
- CEC Efficiency
- 97.69%
How Does DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} Compare Against Peer CEC Listings?
Breaker sizing (1,250 A), parallel Cu feeders wire rules, and DC input limits for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V}.
Classified as a grid-tied PV inverter (active in CEC directory), DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} requires 1202.1 A design capacity -> 1,250 A breaker using parallel Cu feeders copper at 75 C terminals. Weighted efficiency sits at 97.69% (+0.87 pts vs overall CEC median) across 2,343 CEC models, while commercial 415 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (415v) or nec 705.11 supply-side tap.
Where Does DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} Fall Across Listed CEC Models?
Output power comparison showing where DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V}?
Relative ranking of DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V}?
Snapshot of DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} efficiency rank (#472), OCPD breaker size, MPPT span, and busbar verdict.
97.69% CEC Weighted Efficiency
+0.39 pts vs the 97.3% 415 V median; overall power rank #185 (691,248 W, top 7.9%; higher than 92.1% of peers).
1,250 A Required Backfeed OCPD
125% x 961.7 A = 1202.1 A -> 1,250 A standard OCPD using parallel Cu feeders (75 C).
630 V - 1,500 V (Max 1,500 V DC)
Tracking span of 870.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 415 V, 3-phase switchgear (200A Bus / 200A Main (415V) to 1,200A Bus / 1,200A Main (415V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 691248.0W / 415 V 3-phase -> 961.7 A | Breaker >= 1.25 * 961.7 = 1202.1 A -> 1,250 A
CEC Inverters.csv for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V}: Paco=691248.0 W, Vac=415 V, Vdcmax=1500.0 V, Eff=97.69%.
Result: Min 1,250 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (415V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 691,248 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 415 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 630 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 673.899 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.69% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} (415 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} at 415 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (415V) | 40 A | 1,250 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (415V) | 80 A | 1,250 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (415V) | 120 A | 1,250 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (415V) | 160 A | 1,250 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (415V) | 240 A | 1,250 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V}?
Minimum and maximum series solar module strings fitting DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} MPPT and 1,500 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 15 to 26 panels | 15.34 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 19 to 35 panels | 15.4 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 19 to 33 panels | 14.03 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 22 to 36 panels | 7.2 kW |
Which Competing Grid-Support Inverters Compare to DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V}?
Peer 415 V, 3-phase CEC inverters near 691,248 W AC output such as EPC Power Corp: 50-200100 {720V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| EPC Power Corp: 50-200100 {720V} EPC Power Corp |
561,806 W | -129442 W | 720.0 V | 1500.0 V | 98.58% |
| ABB: PVS-175-TL-POWER-MODULE-1-US {800V} ABB |
179,574 W | -511674 W | 800.0 V | 1200.0 V | 97.39% |
| LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V} LS Energy Solutions LLC |
139,449 W | -551799 W | 600.0 V | 1350.0 V | 98.27% |
| JingTsing Technology Ltd: JTES-PCS125K-1000/480-L03C1 {480V} JingTsing Technology Ltd |
127,819 W | -563429 W | 480.0 V | 950.0 V | 98.0% |
What Are the Interconnection Limits and Best-Fit Uses for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V}?
Check DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} (691,248 W AC, 1,250 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 415 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (415V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V}.
DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 1,250 A OCPD breaker (961.7 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.69%) and MPPT window (630-1,500 V) directly against EPC Power Corp: 50-200100 {720V} (561,806 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} by DYNAPOWER COMPANY LLC covering breaker sizing, MPPT limits, and 415 V, 3-phase interconnection.
What breaker and wire size does DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} require?
At 691,248 W continuous AC (415 V, 3-phase), continuous current is 961.7 A; 125% NEC 690.8/705.12 sizing requires a 1,250 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} require?
At 691,248 W AC and 415 V, 3-phase, continuous line current is 961.7 A, requiring a 1,250 A OCPD and 1,200A Bus / 1,200A Main (415V) or NEC 705.11 interconnection.
How does DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} compare to EPC Power Corp: 50-200100 {720V}?
DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {415V} delivers 691,248 W AC at 97.69% CEC efficiency with a 1,500 V DC ceiling, while EPC Power Corp: 50-200100 {720V} outputs 561,806 W at 415 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)