ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} outputs 4,200 W AC at 208 V, commercial single-phase (20.2 A continuous, 30 A OCPD), ranking #2,131 of 2,343 CEC inverters at 95.61% efficiency with a 200-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 4,200 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 30 A (10 AWG Cu)
- CEC Efficiency
- 95.61%
How Does ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} Compare Against Peer CEC Listings?
Breaker sizing (30 A), 10 AWG Cu wire rules, and DC input limits for ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V}. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
Classified as a grid-tied PV inverter (listed since 2020-08-21), ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} requires 25.2 A design capacity -> 30 A breaker using 10 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 95.61% (-1.21 pts vs overall CEC median) across 2,343 CEC models, while commercial 208 v, commercial single-phase switchgear interconnection uses 1,200a bus / 1,200a main (208v) or nec 705.11 supply-side tap.
Where Does ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} Fall Across Listed CEC Models?
Output power comparison showing where ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} sits among all 2,343 CEC-listed grid-support inverters. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
What Dataset Percentiles Define ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V}?
Relative ranking of ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
What Do the Dataset Ranks Show for ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V}?
Snapshot of ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} efficiency rank (#2,131), OCPD breaker size, MPPT span, and busbar verdict. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
95.61% CEC Weighted Efficiency
-0.80 pts vs the 96.41% 208 V median; overall power rank #1,605 (4,200 W, below CEC median; higher than 30.9% of peers).
30 A Required Backfeed OCPD
125% x 20.2 A = 25.2 A -> 30 A standard OCPD using 10 AWG Cu (75 C).
200 V - 480 V (Max 480 V DC)
Tracking span of 280.0 V; listed since 2020-08-21 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 4200.0W / 208 V -> 20.2 A | Breaker >= 1.25 * 20.2 = 25.2 A -> 30 A
CEC Inverters.csv for ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V}: Paco=4200.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=95.61%.
Result: Min 30 A breaker & 10 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V}. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 4,200 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 200 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 12.9199 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 95.61% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2020-08-21 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} (208 V, commercial single-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} at 208 V, commercial single-phase. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 30 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 30 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 30 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 30 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 30 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V}?
Minimum and maximum series solar module strings fitting ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} MPPT and 480 V limits. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 5 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 6 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 6 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 7 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V}?
Peer 208 V, commercial single-phase CEC inverters near 4,200 W AC output such as Delta Electronics: M5-TL-US {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: M5-TL-US {208V} Delta Electronics |
4,160 W | -40 W | 208.0 V | 480.0 V | 97.35% |
| Delta Electronics: M6-TL-US {208V} Delta Electronics |
4,990 W | +790 W | 208.0 V | 480.0 V | 97.13% |
| Delta Electronics: E6-TL-US {208V} Delta Electronics |
4,992 W | +792 W | 208.0 V | 480.0 V | 97.13% |
| Delta Electronics: E6-TL-US(AC) {208V} Delta Electronics |
5,000 W | +800 W | 208.0 V | 480.0 V | 97.6% |
What Are the Interconnection Limits and Best-Fit Uses for ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V}?
Check ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} (4,200 W AC, 30 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V}.
ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} Panel & Wire Spec
Size 75 C copper conductors at 10 AWG Cu on a 30 A OCPD breaker (20.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (95.61%) and MPPT window (200-480 V) directly against Delta Electronics: M5-TL-US {208V} (4,160 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} by ABB covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} require?
At 4,200 W continuous AC (208 V, commercial single-phase), continuous current is 20.2 A; 125% NEC 690.8/705.12 sizing requires a 30 A breaker and 10 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} require?
At 4,200 W AC and 208 V, commercial single-phase, continuous line current is 20.2 A, requiring a 30 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} compare to Delta Electronics: M5-TL-US {208V}?
ABB: UNO-DM-46-TL-PLUS-US-SE-RA {208V} delivers 4,200 W AC at 95.61% CEC efficiency with a 480 V DC ceiling, while Delta Electronics: M5-TL-US {208V} outputs 4,160 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)