Perlight Solar PLM-270P-72 — CEC Solar Module Specifications

Manufacturer: Perlight Solar Registry: CEC Verified Engineering Specification

Perlight Solar PLM-270P-72 is a 270.0 W STC (240.1 W PTC) Multi-c-Si solar module ranking #18,572 of 21,677 CEC listings (below all-CEC median; higher than 12.9% of peers). It delivers 13.84% efficiency, 44.76 V Voc at 25 C, and 49.77 V cold Voc at -10 C (12 panels max per 600 V string).

STC Wattage
270.0 W
PTC Wattage
240.1 W
Voc @ 25C
44.76 V
Efficiency
13.84%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Perlight Solar PLM-270P-72 Compare Against Peer CEC Listings?

Solar engineering breakdown for Perlight Solar PLM-270P-72: PTC thermal retention, roof footprint, and cold Voc string bounds. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Across 1,407 Multi-c-Si listings from Perlight Solar and peers, Perlight Solar PLM-270P-72 stands 8.8 W below the 278.8 W Multi-c-Si median and typical 88.9% PTC-to-STC thermal output (240.1 W real-world rating). Sizing 6 kW (23 panels) to 10 kW (38 panels) yields $1,554-$2,568/yr in baseline US bill offset. Mid-range 44.76 V open-circuit voltage allows up to 12 panels per 600 V string at 14 F.

Where Does Perlight Solar PLM-270P-72 Fall Across Listed CEC Models?

Distribution marker showing Perlight Solar PLM-270P-72 (270.0 W) relative to the 385.0 W all-CEC solar panel median. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.

STC Power Distribution Across 21,677 CEC Solar ModulesMarks where Perlight Solar PLM-270P-72 (270.0 W STC) stands relative to CEC photovoltaic modules. 18-79 W STC: 68 entries1879-140 W STC: 170 entries140-202 W STC: 413 entries202-263 W STC: 1,883 entries202263-325 W STC: 4,202 entries325-386 W STC: 4,219 entries386-448 W STC: 4,695 entries386448-509 W STC: 1,584 entries509-571 W STC: 2,290 entries571-632 W STC: 1,371 entries571632-694 W STC: 534 entries694-755 W STC: 248 entries694Median 385 W STCPerlight Solar PLM: 270.0 W

What Dataset Percentiles Define Perlight Solar PLM-270P-72?

Dataset percentiles tracking Perlight Solar PLM-270P-72 power output, thermal retention ratio, and aperture efficiency against 21,677 models. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Perlight Solar PLM-270P-72 Engineering BenchmarksPercentile comparison of Perlight Solar PLM-270P-72 wattage, thermal retention, and efficiency. 0% (Low)50% Median100% (Top)STC Wattage270.0 WPTC/STC Retention88.9%Module Efficiency13.84%

What Do the Dataset Ranks Show for Perlight Solar PLM-270P-72?

Benchmark highlights for Perlight Solar PLM-270P-72 covering STC output, efficiency, 8 kW footprint, and OCPD breaker size. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Rank #18,572 / 21,677

270.0 W STC · Higher Than 12.9%

270.0 W STC (-115.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.

Eff #21,017

13.84% Aperture Efficiency

Power density 138.5 W/m2 (6.07 percentage points below 19.91% CEC median). PTC/STC ratio: 88.9% (rank #20,819).

NEC 690.7 Limit

12 Panels Max @ -10 C (600 V)

Cold Voc reaches 49.77 V at -10 C (597.2 V string) and 51.21 V at -20 C (11 max).

8 kW Reference Array

30 Panels = 8,100 W STC

Occupies 58.5 m2 (630 sq ft) producing 7,203 W PTC; NEC 690.8 OCPD floor is 13.38 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 44.76 * (1 + (-0.32/100) * (-10 - 25)) = 49.77 V | OCPD = 1.56 * 8.58 = 13.38 A

Inputs from CEC Modules.csv for Perlight Solar PLM-270P-72: Voc=44.76 V, beta_Voc=-0.32%/C, Isc=8.58 A, STC=270.0 W, Area=1.95 m2.

Result: 12 panels max on 600 V (597.2 V); 30 panels for 8 kW (630 sq ft).

What Are the Published CEC Specifications for Perlight Solar PLM-270P-72?

Official CEC datasheet figures for Perlight Solar PLM-270P-72 (Multi-c-Si) used in utility interconnection and permit reviews. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Official California Energy Commission (NREL SAM) test parameters for Perlight Solar PLM-270P-72.
ParameterMeasured / Listed ValueEngineering Significance
Nameplate Power (STC) 270.0 W Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell)
Real-World Output (PTC) 240.1 W (88.9% STC) PVUSA Test Conditions rating used for utility interconnection
Open-Circuit Voltage (Voc) 44.76 V Primary cold-weather string sizing limit under NEC 690.7
Short-Circuit Current (Isc) 8.58 A Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8
Max Power Voltage / Current 35.29 V / 7.94 A Inverter MPPT operating window alignment
Voc Temp Coefficient (beta_Voc) -0.32 %/C Negative slope governing voltage rise below 25C
Module Efficiency & Area 13.84% (1.95 m2) Array roof footprint density
Cell Count & Technology 72 cells (Multi-c-Si) Monofacial backsheet

How Many Perlight Solar PLM-270P-72 Panels Build a 6 kW, 8 kW, or 10 kW Array?

How many Perlight Solar PLM-270P-72 modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).
Target ArrayPanelsActual DCRoof AreaUS Avg ($/yr)CA High ($/yr)
6 kW Class 23 6.21 kW 483 sq ft $1,554 $2,628
8 kW Class 30 8.1 kW 630 sq ft $2,027 $3,428
10 kW Class 38 10.26 kW 798 sq ft $2,568 $4,342

How Many Perlight Solar PLM-270P-72 Modules Fit in a Cold-Weather String?

NEC 690.7(A) winter string table preventing overvoltage trips on Perlight Solar PLM-270P-72 (49.77 V at 14 F).

Computed from Voc=44.76V and beta_Voc=-0.32%/C across design ambient temperatures.
Ambient Min TempCold Voc / PanelMax Panels (600 V)600 V String VocMax Panels (1000 V)
-20 C (-4 F) 51.21 V 11 panels 563.3 V 19 panels
-10 C (14 F) 49.77 V 12 panels 597.2 V 20 panels
0 C (32 F) 48.34 V 12 panels 580.1 V 20 panels
25 C (77 F STC) 44.76 V 13 panels 581.9 V 22 panels

Which Cross-Brand Solar Modules Compare Closest to Perlight Solar PLM-270P-72?

Competing CEC solar panels closest to Perlight Solar PLM-270P-72 in nameplate wattage and Voc, starting with Advance Power API-M270.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.
Alternative ModuleSTC (W)Delta vs ThisVoc (V)Eff (%)PTC/STC
Advance Power API-M270
Advance Power
270.0 W Tie (0 W) 44.64 V 13.84% 89.0%
Auxin Solar AXN6M612T270
Auxin Solar
270.0 W Tie (0 W) 44.64 V 13.84% 89.0%
AXITEC AC-270P/156-72S
AXITEC
270.0 W Tie (0 W) 44.18 V 13.94% 89.9%
Centrosolar America DP72 270
Centrosolar America
270.0 W Tie (0 W) 43.85 V 13.89% 88.4%
What to Check & Best-Fit Scenarios

What Are the Design Limits and Best-Fit Uses for Perlight Solar PLM-270P-72?

Evaluate Perlight Solar PLM-270P-72 (270.0 W STC, 44.76 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

  • Winter overvoltage boundary: at -20 C (-4 F), Perlight Solar PLM-270P-72 reaches 51.21 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
  • Footprint constraint: 30 panels for an 8 kW build require 630 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 30 panels (630 sq ft).
  • 2026 tax credit baseline: cash residential installs of Perlight Solar PLM-270P-72 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

Perlight Solar PLM-270P-72 8 kW Residential Fit

Needs 30 modules (630 sq ft) with a 15 A string OCPD, offsetting ~$2,027/yr at US average tariffs.

Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 12 panels (-10 C) or 11 panels (-20 C), or compare Advance Power API-M270.

Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 240.1 W PTC.

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for Perlight Solar PLM-270P-72 by Perlight Solar grounded in CEC test data and NEC 690.7/690.8 limits.

What fuse or breaker size does NEC 690.8 require for Perlight Solar PLM-270P-72?

Multiplying Perlight Solar PLM-270P-72's 8.58 A short-circuit current by 1.56 equals 13.38 A minimum ampacity, requiring at least a 15 A overcurrent fuse or breaker.

Can Perlight Solar PLM-270P-72 pair with microinverters instead of a 600 V string inverter?

Yes—if the microinverter DC input ceiling exceeds 49.77 V cold Voc at 14 F and handles 8.58 A Isc; string inverters cap Perlight Solar PLM-270P-72 at 12 panels on 600 V.

Is Perlight Solar PLM-270P-72 eligible for the 30% federal 25D solar credit in 2026?

No. Federal Section 25D expired December 31, 2025 under Public Law 119-21, so 2026 cash installs of Perlight Solar PLM-270P-72 rely on utility bill offset (~$2,027/yr at 8 kW) rather than 25D.

Sources

  1. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.