Perlight Solar PLM-270P-72 is a 270.0 W STC (240.1 W PTC) Multi-c-Si solar module ranking #18,572 of 21,677 CEC listings (below all-CEC median; higher than 12.9% of peers). It delivers 13.84% efficiency, 44.76 V Voc at 25 C, and 49.77 V cold Voc at -10 C (12 panels max per 600 V string).
- STC Wattage
- 270.0 W
- PTC Wattage
- 240.1 W
- Voc @ 25C
- 44.76 V
- Efficiency
- 13.84%
How Does Perlight Solar PLM-270P-72 Compare Against Peer CEC Listings?
Solar engineering breakdown for Perlight Solar PLM-270P-72: PTC thermal retention, roof footprint, and cold Voc string bounds. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
Across 1,407 Multi-c-Si listings from Perlight Solar and peers, Perlight Solar PLM-270P-72 stands 8.8 W below the 278.8 W Multi-c-Si median and typical 88.9% PTC-to-STC thermal output (240.1 W real-world rating). Sizing 6 kW (23 panels) to 10 kW (38 panels) yields $1,554-$2,568/yr in baseline US bill offset. Mid-range 44.76 V open-circuit voltage allows up to 12 panels per 600 V string at 14 F.
Where Does Perlight Solar PLM-270P-72 Fall Across Listed CEC Models?
Distribution marker showing Perlight Solar PLM-270P-72 (270.0 W) relative to the 385.0 W all-CEC solar panel median. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
What Dataset Percentiles Define Perlight Solar PLM-270P-72?
Dataset percentiles tracking Perlight Solar PLM-270P-72 power output, thermal retention ratio, and aperture efficiency against 21,677 models. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
What Do the Dataset Ranks Show for Perlight Solar PLM-270P-72?
Benchmark highlights for Perlight Solar PLM-270P-72 covering STC output, efficiency, 8 kW footprint, and OCPD breaker size. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
270.0 W STC · Higher Than 12.9%
270.0 W STC (-115.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.
13.84% Aperture Efficiency
Power density 138.5 W/m2 (6.07 percentage points below 19.91% CEC median). PTC/STC ratio: 88.9% (rank #20,819).
12 Panels Max @ -10 C (600 V)
Cold Voc reaches 49.77 V at -10 C (597.2 V string) and 51.21 V at -20 C (11 max).
30 Panels = 8,100 W STC
Occupies 58.5 m2 (630 sq ft) producing 7,203 W PTC; NEC 690.8 OCPD floor is 13.38 A (15 A breaker).
NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula
Voc_cold = 44.76 * (1 + (-0.32/100) * (-10 - 25)) = 49.77 V | OCPD = 1.56 * 8.58 = 13.38 A
Inputs from CEC Modules.csv for Perlight Solar PLM-270P-72: Voc=44.76 V, beta_Voc=-0.32%/C, Isc=8.58 A, STC=270.0 W, Area=1.95 m2.
Result: 12 panels max on 600 V (597.2 V); 30 panels for 8 kW (630 sq ft).
What Are the Published CEC Specifications for Perlight Solar PLM-270P-72?
Official CEC datasheet figures for Perlight Solar PLM-270P-72 (Multi-c-Si) used in utility interconnection and permit reviews. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Nameplate Power (STC) | 270.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| Real-World Output (PTC) | 240.1 W (88.9% STC) | PVUSA Test Conditions rating used for utility interconnection |
| Open-Circuit Voltage (Voc) | 44.76 V | Primary cold-weather string sizing limit under NEC 690.7 |
| Short-Circuit Current (Isc) | 8.58 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| Max Power Voltage / Current | 35.29 V / 7.94 A | Inverter MPPT operating window alignment |
| Voc Temp Coefficient (beta_Voc) | -0.32 %/C | Negative slope governing voltage rise below 25C |
| Module Efficiency & Area | 13.84% (1.95 m2) | Array roof footprint density |
| Cell Count & Technology | 72 cells (Multi-c-Si) | Monofacial backsheet |
How Many Perlight Solar PLM-270P-72 Panels Build a 6 kW, 8 kW, or 10 kW Array?
How many Perlight Solar PLM-270P-72 modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.
| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| 6 kW Class | 23 | 6.21 kW | 483 sq ft | $1,554 | $2,628 |
| 8 kW Class | 30 | 8.1 kW | 630 sq ft | $2,027 | $3,428 |
| 10 kW Class | 38 | 10.26 kW | 798 sq ft | $2,568 | $4,342 |
How Many Perlight Solar PLM-270P-72 Modules Fit in a Cold-Weather String?
NEC 690.7(A) winter string table preventing overvoltage trips on Perlight Solar PLM-270P-72 (49.77 V at 14 F).
| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| -20 C (-4 F) | 51.21 V | 11 panels | 563.3 V | 19 panels |
| -10 C (14 F) | 49.77 V | 12 panels | 597.2 V | 20 panels |
| 0 C (32 F) | 48.34 V | 12 panels | 580.1 V | 20 panels |
| 25 C (77 F STC) | 44.76 V | 13 panels | 581.9 V | 22 panels |
Which Cross-Brand Solar Modules Compare Closest to Perlight Solar PLM-270P-72?
Competing CEC solar panels closest to Perlight Solar PLM-270P-72 in nameplate wattage and Voc, starting with Advance Power API-M270.
| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| Advance Power API-M270 Advance Power |
270.0 W | Tie (0 W) | 44.64 V | 13.84% | 89.0% |
| Auxin Solar AXN6M612T270 Auxin Solar |
270.0 W | Tie (0 W) | 44.64 V | 13.84% | 89.0% |
| AXITEC AC-270P/156-72S AXITEC |
270.0 W | Tie (0 W) | 44.18 V | 13.94% | 89.9% |
| Centrosolar America DP72 270 Centrosolar America |
270.0 W | Tie (0 W) | 43.85 V | 13.89% | 88.4% |
What Are the Design Limits and Best-Fit Uses for Perlight Solar PLM-270P-72?
Evaluate Perlight Solar PLM-270P-72 (270.0 W STC, 44.76 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.
- Winter overvoltage boundary: at -20 C (-4 F), Perlight Solar PLM-270P-72 reaches 51.21 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
- Footprint constraint: 30 panels for an 8 kW build require 630 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 30 panels (630 sq ft).
- 2026 tax credit baseline: cash residential installs of Perlight Solar PLM-270P-72 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.
Perlight Solar PLM-270P-72 8 kW Residential Fit
Needs 30 modules (630 sq ft) with a 15 A string OCPD, offsetting ~$2,027/yr at US average tariffs.
Cold-Climate String Design (-10 C / -20 C)
Cap 600 V series strings at 12 panels (-10 C) or 11 panels (-20 C), or compare Advance Power API-M270.
Bifacial / High-Heat Roof Check
Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 240.1 W PTC.
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Technical answers for Perlight Solar PLM-270P-72 by Perlight Solar grounded in CEC test data and NEC 690.7/690.8 limits.
What fuse or breaker size does NEC 690.8 require for Perlight Solar PLM-270P-72?
Multiplying Perlight Solar PLM-270P-72's 8.58 A short-circuit current by 1.56 equals 13.38 A minimum ampacity, requiring at least a 15 A overcurrent fuse or breaker.
Can Perlight Solar PLM-270P-72 pair with microinverters instead of a 600 V string inverter?
Yes—if the microinverter DC input ceiling exceeds 49.77 V cold Voc at 14 F and handles 8.58 A Isc; string inverters cap Perlight Solar PLM-270P-72 at 12 panels on 600 V.
Is Perlight Solar PLM-270P-72 eligible for the 30% federal 25D solar credit in 2026?
No. Federal Section 25D expired December 31, 2025 under Public Law 119-21, so 2026 cash installs of Perlight Solar PLM-270P-72 rely on utility bill offset (~$2,027/yr at 8 kW) rather than 25D.
Sources
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)