JA Solar JAP6(BK)-60-235 is a 235.0 W STC (209.1 W PTC) Multi-c-Si solar module ranking #20,368 of 21,677 CEC listings (below all-CEC median; higher than 5.4% of peers). It delivers 14.37% efficiency, 37.34 V Voc at 25 C, and 42.1 V cold Voc at -10 C (14 panels max per 600 V string).
- STC Wattage
- 235.0 W
- PTC Wattage
- 209.1 W
- Voc @ 25C
- 37.34 V
- Efficiency
- 14.37%
How Does JA Solar JAP6(BK)-60-235 Compare Against Peer CEC Listings?
Solar engineering breakdown for JA Solar JAP6(BK)-60-235: PTC thermal retention, roof footprint, and cold Voc string bounds.
Measured at 235.0 W STC and 209.1 W PTC, JA Solar JAP6(BK)-60-235 sits -150.0 W vs all-CEC median (below all-CEC median; higher than 5.4% of peers) among 21,677 listed modules. Power density reaches 143.7 W/m2 (5.54 percentage points below 19.91% CEC median). Lower 37.34 V string voltage fits 14 panels in series at 14 F and pairs easily with microinverters, whereas 1,000 V commercial inverters handle up to 23 panels in series. Alternative peer APOS Energy AS235 rates 235.0 W.
Where Does JA Solar JAP6(BK)-60-235 Fall Across Listed CEC Models?
Distribution marker showing JA Solar JAP6(BK)-60-235 (235.0 W) relative to the 385.0 W all-CEC solar panel median.
What Dataset Percentiles Define JA Solar JAP6(BK)-60-235?
Dataset percentiles tracking JA Solar JAP6(BK)-60-235 power output, thermal retention ratio, and aperture efficiency against 21,677 models.
What Do the Dataset Ranks Show for JA Solar JAP6(BK)-60-235?
Benchmark highlights for JA Solar JAP6(BK)-60-235 covering STC output, efficiency, 8 kW footprint, and OCPD breaker size.
235.0 W STC · Higher Than 5.4%
235.0 W STC (-150.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.
14.37% Aperture Efficiency
Power density 143.7 W/m2 (5.54 percentage points below 19.91% CEC median). PTC/STC ratio: 89.0% (rank #20,637).
14 Panels Max @ -10 C (600 V)
Cold Voc reaches 42.1 V at -10 C (589.4 V string) and 43.46 V at -20 C (13 max).
35 Panels = 8,225 W STC
Occupies 57.2 m2 (616 sq ft) producing 7,318 W PTC; NEC 690.8 OCPD floor is 13.09 A (15 A breaker).
NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula
Voc_cold = 37.34 * (1 + (-0.364/100) * (-10 - 25)) = 42.1 V | OCPD = 1.56 * 8.39 = 13.09 A
Inputs from CEC Modules.csv for JA Solar JAP6(BK)-60-235: Voc=37.34 V, beta_Voc=-0.364%/C, Isc=8.39 A, STC=235.0 W, Area=1.635 m2.
Result: 14 panels max on 600 V (589.4 V); 35 panels for 8 kW (616 sq ft).
What Are the Published CEC Specifications for JA Solar JAP6(BK)-60-235?
Official CEC datasheet figures for JA Solar JAP6(BK)-60-235 (Multi-c-Si) used in utility interconnection and permit reviews.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Nameplate Power (STC) | 235.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| Real-World Output (PTC) | 209.1 W (89.0% STC) | PVUSA Test Conditions rating used for utility interconnection |
| Open-Circuit Voltage (Voc) | 37.34 V | Primary cold-weather string sizing limit under NEC 690.7 |
| Short-Circuit Current (Isc) | 8.39 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| Max Power Voltage / Current | 29.52 V / 7.96 A | Inverter MPPT operating window alignment |
| Voc Temp Coefficient (beta_Voc) | -0.364 %/C | Negative slope governing voltage rise below 25C |
| Module Efficiency & Area | 14.37% (1.635 m2) | Array roof footprint density |
| Cell Count & Technology | 60 cells (Multi-c-Si) | Monofacial backsheet |
How Many JA Solar JAP6(BK)-60-235 Panels Build a 6 kW, 8 kW, or 10 kW Array?
How many JA Solar JAP6(BK)-60-235 modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.
| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| 6 kW Class | 26 | 6.11 kW | 458 sq ft | $1,529 | $2,586 |
| 8 kW Class | 35 | 8.22 kW | 616 sq ft | $2,057 | $3,479 |
| 10 kW Class | 43 | 10.11 kW | 757 sq ft | $2,530 | $4,279 |
Which Sibling Wattage & Trim Variants Belong to This JA Solar Series?
Consolidated JA Solar wattage variants sharing the JA Solar JAP6(BK)-60-235 mechanical and cell layout. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| JA Solar JAP6(BK)-60-225 | 225.0 W | 200.0 W | 37.0 V | 29.12 V | 13.76% |
| JA Solar JAP6(BK)-60-230 | 230.0 W | 204.5 W | 37.17 V | 29.32 V | 14.07% |
| JA Solar JAP6(BK)-60-235 | 235.0 W | 209.1 W | 37.34 V | 29.52 V | 14.37% |
| JA Solar JAP6(BK)-60-240 | 240.0 W | 213.7 W | 37.51 V | 29.72 V | 14.68% |
| JA Solar JAP6(BK)-60-245 | 245.0 W | 218.3 W | 37.68 V | 29.92 V | 14.98% |
How Many JA Solar JAP6(BK)-60-235 Modules Fit in a Cold-Weather String?
NEC 690.7(A) winter string table preventing overvoltage trips on JA Solar JAP6(BK)-60-235 (42.1 V at 14 F).
| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| -20 C (-4 F) | 43.46 V | 13 panels | 565.0 V | 23 panels |
| -10 C (14 F) | 42.1 V | 14 panels | 589.4 V | 23 panels |
| 0 C (32 F) | 40.74 V | 14 panels | 570.4 V | 24 panels |
| 25 C (77 F STC) | 37.34 V | 16 panels | 597.4 V | 26 panels |
Which Cross-Brand Solar Modules Compare Closest to JA Solar JAP6(BK)-60-235?
Competing CEC solar panels closest to JA Solar JAP6(BK)-60-235 in nameplate wattage and Voc, starting with APOS Energy AS235.
| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| APOS Energy AS235 APOS Energy |
235.0 W | Tie (0 W) | 37.34 V | 14.17% | 89.7% |
| Gintech Energy GTE 235M Gintech Energy |
235.0 W | Tie (0 W) | 37.32 V | 13.97% | 89.5% |
| Advance Power API-M235 Advance Power |
235.0 W | Tie (0 W) | 37.5 V | 14.35% | 89.3% |
| Auxin Solar AXN6M610T235 Auxin Solar |
235.0 W | Tie (0 W) | 37.5 V | 14.35% | 89.3% |
What Are the Design Limits and Best-Fit Uses for JA Solar JAP6(BK)-60-235?
Evaluate JA Solar JAP6(BK)-60-235 (235.0 W STC, 37.34 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.
- Winter overvoltage boundary: at -20 C (-4 F), JA Solar JAP6(BK)-60-235 reaches 43.46 V per panel—exceeding 13 panels in series voids 600 V inverter warranties.
- Footprint constraint: 35 panels for an 8 kW build require 616 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 35 panels (616 sq ft).
- 2026 tax credit baseline: cash residential installs of JA Solar JAP6(BK)-60-235 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.
JA Solar JAP6(BK)-60-235 8 kW Residential Fit
Needs 35 modules (616 sq ft) with a 15 A string OCPD, offsetting ~$2,057/yr at US average tariffs.
Cold-Climate String Design (-10 C / -20 C)
Cap 600 V series strings at 14 panels (-10 C) or 13 panels (-20 C), or compare APOS Energy AS235.
Bifacial / High-Heat Roof Check
Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 209.1 W PTC.
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Technical answers for JA Solar JAP6(BK)-60-235 by JA Solar grounded in CEC test data and NEC 690.7/690.8 limits.
How many JA Solar JAP6(BK)-60-235 panels fit on a 600 V winter solar string?
At -10 C (14 F), JA Solar JAP6(BK)-60-235 cold Voc rises from 37.34 V to 42.1 V (beta_Voc -0.364%/C), capping a 600 V string at 14 panels (589.4 V).
How much roof area does an 8 kW array of JA Solar JAP6(BK)-60-235 need?
An 8 kW DC system uses 35 JA Solar JAP6(BK)-60-235 modules (8,225 W STC / 7,318 W PTC), covering roughly 616 sq ft and saving ~$2,057/yr at 18.54 c/kWh.
How does JA Solar JAP6(BK)-60-235 compare against APOS Energy AS235?
JA Solar JAP6(BK)-60-235 outputs 235.0 W STC (37.34 V Voc, rank #20,368 of 21,677), while APOS Energy AS235 delivers 235.0 W STC; both comply with 2026 NEC 690.7 string sizing rules.
Sources
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)