JA Solar JAP6-72-330/4BB — CEC Solar Module Specifications

Manufacturer: JA Solar Registry: CEC Verified Engineering Specification

JA Solar JAP6-72-330/4BB is a 330.0 W STC (306.0 W PTC) Multi-c-Si solar module ranking #14,165 of 21,677 CEC listings (below all-CEC median; higher than 32.9% of peers). It delivers 17.02% efficiency, 46.48 V Voc at 25 C, and 51.38 V cold Voc at -10 C (11 panels max per 600 V string).

STC Wattage
330.0 W
PTC Wattage
306.0 W
Voc @ 25C
46.48 V
Efficiency
17.02%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does JA Solar JAP6-72-330/4BB Compare Against Peer CEC Listings?

How JA Solar JA Solar JAP6-72-330/4BB handles rooftop heat (306.0 W PTC), 8 kW sizing, and cold winter string voltage.

For NEC string engineering, JA Solar JAP6-72-330/4BB exhibits 9.22 A short-circuit current, requiring a 14.38 A (156%) conductor rating and 15 A OCPD under NEC 690.8. Ranked #14,165 of 21,677 (51.2 W above the 278.8 W Multi-c-Si median), this compact residential or specialty off-grid module covers 48.4 m2 for an 8 kW system (31 panels for 10 kW). Mid-range 46.48 V open-circuit voltage allows up to 11 panels per 600 V string at 14 F.

Where Does JA Solar JAP6-72-330/4BB Fall Across Listed CEC Models?

Where JA Solar JAP6-72-330/4BB (330.0 W) sits inside the 21,677-panel CEC STC wattage curve relative to the 385.0 W median.

STC Power Distribution Across 21,677 CEC Solar ModulesMarks where JA Solar JAP6-72-330/4BB (330.0 W STC) stands relative to CEC photovoltaic modules. 18-79 W STC: 68 entries1879-140 W STC: 170 entries140-202 W STC: 413 entries202-263 W STC: 1,883 entries202263-325 W STC: 4,202 entries325-386 W STC: 4,219 entries386-448 W STC: 4,695 entries386448-509 W STC: 1,584 entries509-571 W STC: 2,290 entries571-632 W STC: 1,371 entries571632-694 W STC: 534 entries694-755 W STC: 248 entries694Median 385 W STCJA Solar JAP6-72-3: 330.0 W

What Dataset Percentiles Define JA Solar JAP6-72-330/4BB?

Percentile placement of JA Solar JAP6-72-330/4BB across power density (170.3 W/m2), thermal retention, and nameplate STC wattage.

JA Solar JAP6-72-330/4BB Engineering BenchmarksPercentile comparison of JA Solar JAP6-72-330/4BB wattage, thermal retention, and efficiency. 0% (Low)50% Median100% (Top)STC Wattage330.0 WPTC/STC Retention92.7%Module Efficiency17.02%

What Do the Dataset Ranks Show for JA Solar JAP6-72-330/4BB?

Four critical engineering numbers homeowners and solar installers check first when reviewing JA Solar JAP6-72-330/4BB specifications. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.

Rank #14,165 / 21,677

330.0 W STC · Higher Than 32.9%

330.0 W STC (-55.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.

Eff #16,417

17.02% Aperture Efficiency

Power density 170.3 W/m2 (2.89 percentage points below 19.91% CEC median). PTC/STC ratio: 92.7% (rank #11,468).

NEC 690.7 Limit

11 Panels Max @ -10 C (600 V)

Cold Voc reaches 51.38 V at -10 C (565.2 V string) and 52.78 V at -20 C (11 max).

8 kW Reference Array

25 Panels = 8,250 W STC

Occupies 48.4 m2 (522 sq ft) producing 7,650 W PTC; NEC 690.8 OCPD floor is 14.38 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 46.48 * (1 + (-0.301/100) * (-10 - 25)) = 51.38 V | OCPD = 1.56 * 9.22 = 14.38 A

Inputs from CEC Modules.csv for JA Solar JAP6-72-330/4BB: Voc=46.48 V, beta_Voc=-0.301%/C, Isc=9.22 A, STC=330.0 W, Area=1.938 m2.

Result: 11 panels max on 600 V (565.2 V); 25 panels for 8 kW (522 sq ft).

What Are the Published CEC Specifications for JA Solar JAP6-72-330/4BB?

Verified electrical STC and PTC ratings, open-circuit voltage, short-circuit current, and physical area published for JA Solar JAP6-72-330/4BB.

Official California Energy Commission (NREL SAM) test parameters for JA Solar JAP6-72-330/4BB.
ParameterMeasured / Listed ValueEngineering Significance
Nameplate Power (STC) 330.0 W Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell)
Real-World Output (PTC) 306.0 W (92.7% STC) PVUSA Test Conditions rating used for utility interconnection
Open-Circuit Voltage (Voc) 46.48 V Primary cold-weather string sizing limit under NEC 690.7
Short-Circuit Current (Isc) 9.22 A Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8
Max Power Voltage / Current 37.6 V / 8.78 A Inverter MPPT operating window alignment
Voc Temp Coefficient (beta_Voc) -0.301 %/C Negative slope governing voltage rise below 25C
Module Efficiency & Area 17.02% (1.938 m2) Array roof footprint density
Cell Count & Technology 72 cells (Multi-c-Si) Monofacial backsheet

How Many JA Solar JAP6-72-330/4BB Panels Build a 6 kW, 8 kW, or 10 kW Array?

Compare 6 kW, 8 kW, and 10 kW array footprints and Year-1 utility savings using JA Solar JAP6-72-330/4BB (330.0 W).

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).
Target ArrayPanelsActual DCRoof AreaUS Avg ($/yr)CA High ($/yr)
6 kW Class 19 6.27 kW 396 sq ft $1,569 $2,654
8 kW Class 25 8.25 kW 522 sq ft $2,065 $3,492
10 kW Class 31 10.23 kW 647 sq ft $2,560 $4,330

Which Sibling Wattage & Trim Variants Belong to This JA Solar Series?

All closely matched JA Solar wattages and cosmetic trims sharing the JA Solar JAP6-72-330/4BB architecture. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

Sibling CEC listings grouped into the JA Solar JAP6-72-330/4BB wattage tier to avoid duplicate 5W/trim datasheets.
Model VariantSTC (W)PTC (W)Voc (V)Vmp (V)Eff (%)
JA Solar JAP6-72-325/4BB 325.0 W 301.2 W 46.48 V 37.49 V 16.77%
JA Solar JAP6-72-330/4BB 330.0 W 306.0 W 46.48 V 37.6 V 17.02%

How Many JA Solar JAP6-72-330/4BB Modules Fit in a Cold-Weather String?

Maximum series module counts for JA Solar JAP6-72-330/4BB from 25 C down to -20 C (-4 F) under NEC 690.7.

Computed from Voc=46.48V and beta_Voc=-0.301%/C across design ambient temperatures.
Ambient Min TempCold Voc / PanelMax Panels (600 V)600 V String VocMax Panels (1000 V)
-20 C (-4 F) 52.78 V 11 panels 580.6 V 18 panels
-10 C (14 F) 51.38 V 11 panels 565.2 V 19 panels
0 C (32 F) 49.98 V 12 panels 599.8 V 20 panels
25 C (77 F STC) 46.48 V 12 panels 557.8 V 21 panels

Which Cross-Brand Solar Modules Compare Closest to JA Solar JAP6-72-330/4BB?

Alternative CEC solar modules from competing brands near JA Solar JAP6-72-330/4BB (330.0 W), including Amerisolar-Worldwide Energy and Manufacturing USA Co Ltd AS-6P-330W.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.
Alternative ModuleSTC (W)Delta vs ThisVoc (V)Eff (%)PTC/STC
Amerisolar-Worldwide Energy and Manufacturing USA Co Ltd AS-6P-330W
Amerisolar-Worldwide Energy and Manufacturing USA Co Ltd
330.0 W Tie (0 W) 46.65 V 17.16% 91.3%
Centrosolar America EP72 330BW
Centrosolar America
330.0 W Tie (0 W) 46.65 V 17.16% 91.3%
Centrosolar America EP72 330SW
Centrosolar America
330.0 W Tie (0 W) 46.65 V 17.16% 91.3%
GCL System Integration Technology Co Ltd GCL-M6/72330
GCL System Integration Technology Co Ltd
330.0 W Tie (0 W) 46.2 V 17.01% 90.4%
What to Check & Best-Fit Scenarios

What Are the Design Limits and Best-Fit Uses for JA Solar JAP6-72-330/4BB?

Evaluate JA Solar JAP6-72-330/4BB (330.0 W STC, 46.48 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

  • Winter overvoltage boundary: at -20 C (-4 F), JA Solar JAP6-72-330/4BB reaches 52.78 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
  • Footprint constraint: 25 panels for an 8 kW build require 522 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 25 panels (522 sq ft).
  • 2026 tax credit baseline: cash residential installs of JA Solar JAP6-72-330/4BB carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

JA Solar JAP6-72-330/4BB 8 kW Residential Fit

Needs 25 modules (522 sq ft) with a 15 A string OCPD, offsetting ~$2,065/yr at US average tariffs.

Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 11 panels (-10 C) or 11 panels (-20 C), or compare Amerisolar-Worldwide Energy and Manufacturing USA Co Ltd AS-6P-330W.

Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 306.0 W PTC.

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for JA Solar JAP6-72-330/4BB by JA Solar grounded in CEC test data and NEC 690.7/690.8 limits.

Why is JA Solar JAP6-72-330/4BB PTC wattage (306.0 W) lower than STC (330.0 W)?

Laboratory STC tests at 25 C cell temperature, whereas real rooftop heat lowers voltage to 306.0 W PTC (92.7% retention) across JA Solar JAP6-72-330/4BB's 1.938 m2 aperture.

Who should skip JA Solar JAP6-72-330/4BB on a complex residential roof?

Homes with chopped dormers or heavy chimney shade should compare smaller modules or microinverters if 25 JA Solar JAP6-72-330/4BB panels (522 sq ft) leave unusable roof gaps vs. Amerisolar-Worldwide Energy and Manufacturing USA Co Ltd AS-6P-330W.

What is the 1,000 V commercial string limit for JA Solar JAP6-72-330/4BB?

On 1,000 V commercial inverters at -10 C (51.38 V cold Voc), JA Solar JAP6-72-330/4BB fits up to 19 panels per series string. Review current municipal Authority Having Jurisdiction (AHJ) code amendments affecting JA Solar JAP6-72-330/4BB.

Sources

  1. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.