Heliene 72P-325 — CEC Solar Module Specifications

Manufacturer: Heliene Registry: CEC Verified Engineering Specification

Heliene 72P-325 is a 325.0 W STC (290.3 W PTC) Multi-c-Si solar module ranking #14,546 of 21,677 CEC listings (below all-CEC median; higher than 31.1% of peers). It delivers 16.75% efficiency, 46.11 V Voc at 25 C, and 51.06 V cold Voc at -10 C (11 panels max per 600 V string).

STC Wattage
325.0 W
PTC Wattage
290.3 W
Voc @ 25C
46.11 V
Efficiency
16.75%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Heliene 72P-325 Compare Against Peer CEC Listings?

Solar engineering breakdown for Heliene 72P-325: PTC thermal retention, roof footprint, and cold Voc string bounds. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Across 1,407 Multi-c-Si listings from Heliene and peers, Heliene 72P-325 stands 46.2 W above the 278.8 W Multi-c-Si median and typical 89.3% PTC-to-STC thermal output (290.3 W real-world rating). Sizing 6 kW (19 panels) to 10 kW (31 panels) yields $1,544-$2,520/yr in baseline US bill offset. Mid-range 46.11 V open-circuit voltage allows up to 11 panels per 600 V string at 14 F.

Where Does Heliene 72P-325 Fall Across Listed CEC Models?

Distribution marker showing Heliene 72P-325 (325.0 W) relative to the 385.0 W all-CEC solar panel median. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

STC Power Distribution Across 21,677 CEC Solar ModulesMarks where Heliene 72P-325 (325.0 W STC) stands relative to CEC photovoltaic modules. 18-79 W STC: 68 entries1879-140 W STC: 170 entries140-202 W STC: 413 entries202-263 W STC: 1,883 entries202263-325 W STC: 4,202 entries325-386 W STC: 4,219 entries386-448 W STC: 4,695 entries386448-509 W STC: 1,584 entries509-571 W STC: 2,290 entries571-632 W STC: 1,371 entries571632-694 W STC: 534 entries694-755 W STC: 248 entries694Median 385 W STCHeliene 72P-325: 325.0 W

What Dataset Percentiles Define Heliene 72P-325?

Dataset percentiles tracking Heliene 72P-325 power output, thermal retention ratio, and aperture efficiency against 21,677 models. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Heliene 72P-325 Engineering BenchmarksPercentile comparison of Heliene 72P-325 wattage, thermal retention, and efficiency. 0% (Low)50% Median100% (Top)STC Wattage325.0 WPTC/STC Retention89.3%Module Efficiency16.75%

What Do the Dataset Ranks Show for Heliene 72P-325?

Benchmark highlights for Heliene 72P-325 covering STC output, efficiency, 8 kW footprint, and OCPD breaker size. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

Rank #14,546 / 21,677

325.0 W STC · Higher Than 31.1%

325.0 W STC (-60.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.

Eff #16,887

16.75% Aperture Efficiency

Power density 167.5 W/m2 (3.16 percentage points below 19.91% CEC median). PTC/STC ratio: 89.3% (rank #20,205).

NEC 690.7 Limit

11 Panels Max @ -10 C (600 V)

Cold Voc reaches 51.06 V at -10 C (561.7 V string) and 52.48 V at -20 C (11 max).

8 kW Reference Array

25 Panels = 8,125 W STC

Occupies 48.5 m2 (522 sq ft) producing 7,258 W PTC; NEC 690.8 OCPD floor is 14.12 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 46.11 * (1 + (-0.307/100) * (-10 - 25)) = 51.06 V | OCPD = 1.56 * 9.05 = 14.12 A

Inputs from CEC Modules.csv for Heliene 72P-325: Voc=46.11 V, beta_Voc=-0.307%/C, Isc=9.05 A, STC=325.0 W, Area=1.94 m2.

Result: 11 panels max on 600 V (561.7 V); 25 panels for 8 kW (522 sq ft).

What Are the Published CEC Specifications for Heliene 72P-325?

Official CEC datasheet figures for Heliene 72P-325 (Multi-c-Si) used in utility interconnection and permit reviews. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Official California Energy Commission (NREL SAM) test parameters for Heliene 72P-325.
ParameterMeasured / Listed ValueEngineering Significance
Nameplate Power (STC) 325.0 W Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell)
Real-World Output (PTC) 290.3 W (89.3% STC) PVUSA Test Conditions rating used for utility interconnection
Open-Circuit Voltage (Voc) 46.11 V Primary cold-weather string sizing limit under NEC 690.7
Short-Circuit Current (Isc) 9.05 A Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8
Max Power Voltage / Current 37.42 V / 8.74 A Inverter MPPT operating window alignment
Voc Temp Coefficient (beta_Voc) -0.307 %/C Negative slope governing voltage rise below 25C
Module Efficiency & Area 16.75% (1.94 m2) Array roof footprint density
Cell Count & Technology 72 cells (Multi-c-Si) Monofacial backsheet

How Many Heliene 72P-325 Panels Build a 6 kW, 8 kW, or 10 kW Array?

How many Heliene 72P-325 modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).
Target ArrayPanelsActual DCRoof AreaUS Avg ($/yr)CA High ($/yr)
6 kW Class 19 6.17 kW 397 sq ft $1,544 $2,611
8 kW Class 25 8.12 kW 522 sq ft $2,032 $3,437
10 kW Class 31 10.07 kW 647 sq ft $2,520 $4,262

How Many Heliene 72P-325 Modules Fit in a Cold-Weather String?

NEC 690.7(A) winter string table preventing overvoltage trips on Heliene 72P-325 (51.06 V at 14 F). Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Computed from Voc=46.11V and beta_Voc=-0.307%/C across design ambient temperatures.
Ambient Min TempCold Voc / PanelMax Panels (600 V)600 V String VocMax Panels (1000 V)
-20 C (-4 F) 52.48 V 11 panels 577.3 V 19 panels
-10 C (14 F) 51.06 V 11 panels 561.7 V 19 panels
0 C (32 F) 49.65 V 12 panels 595.8 V 20 panels
25 C (77 F STC) 46.11 V 13 panels 599.4 V 21 panels

Which Cross-Brand Solar Modules Compare Closest to Heliene 72P-325?

Competing CEC solar panels closest to Heliene 72P-325 in nameplate wattage and Voc, starting with GCL System Integration Technology Co Ltd GCL-M6/72325.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.
Alternative ModuleSTC (W)Delta vs ThisVoc (V)Eff (%)PTC/STC
GCL System Integration Technology Co Ltd GCL-M6/72325
GCL System Integration Technology Co Ltd
325.0 W Tie (0 W) 46.0 V 16.75% 90.4%
GCL System Integration Technology Co Ltd GCL-P6/72325
GCL System Integration Technology Co Ltd
325.0 W Tie (0 W) 46.0 V 16.75% 90.7%
CertainTeed CT325P00-01
CertainTeed
325.0 W Tie (0 W) 45.9 V 17.96% 91.8%
Chinaland Solar Energy HSE325-72M
Chinaland Solar Energy
325.0 W Tie (0 W) 45.9 V 16.84% 90.4%
What to Check & Best-Fit Scenarios

What Are the Design Limits and Best-Fit Uses for Heliene 72P-325?

Evaluate Heliene 72P-325 (325.0 W STC, 46.11 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

  • Winter overvoltage boundary: at -20 C (-4 F), Heliene 72P-325 reaches 52.48 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
  • Footprint constraint: 25 panels for an 8 kW build require 522 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 25 panels (522 sq ft).
  • 2026 tax credit baseline: cash residential installs of Heliene 72P-325 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

Heliene 72P-325 8 kW Residential Fit

Needs 25 modules (522 sq ft) with a 15 A string OCPD, offsetting ~$2,032/yr at US average tariffs.

Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 11 panels (-10 C) or 11 panels (-20 C), or compare GCL System Integration Technology Co Ltd GCL-M6/72325.

Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 290.3 W PTC.

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for Heliene 72P-325 by Heliene grounded in CEC test data and NEC 690.7/690.8 limits. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

What fuse or breaker size does NEC 690.8 require for Heliene 72P-325?

Multiplying Heliene 72P-325's 9.05 A short-circuit current by 1.56 equals 14.12 A minimum ampacity, requiring at least a 15 A overcurrent fuse or breaker. Check local building department permit requirements for Heliene 72P-325 before finalizing component orders.

Can Heliene 72P-325 pair with microinverters instead of a 600 V string inverter?

Yes—if the microinverter DC input ceiling exceeds 51.06 V cold Voc at 14 F and handles 9.05 A Isc; string inverters cap Heliene 72P-325 at 11 panels on 600 V.

Is Heliene 72P-325 eligible for the 30% federal 25D solar credit in 2026?

No. Federal Section 25D expired December 31, 2025 under Public Law 119-21, so 2026 cash installs of Heliene 72P-325 rely on utility bill offset (~$2,032/yr at 8 kW) rather than 25D.

Sources

  1. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.