SolarEdge Technologies Ltd: SE3000x {208V} outputs 3,020 W AC at 208 V, commercial single-phase (14.5 A continuous, 20 A OCPD), ranking #672 of 2,343 CEC inverters at 97.31% efficiency with a 305-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 3,020 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 20 A (12 AWG Cu)
- CEC Efficiency
- 97.31%
How Does SolarEdge Technologies Ltd: SE3000x {208V} Compare Against Peer CEC Listings?
How SolarEdge Technologies Ltd SolarEdge Technologies Ltd: SE3000x {208V} compares on 97.31% efficiency, MPPT span, and 120% busbar interconnection.
With a 305-480 V MPPT tracking band and 480 V DC ceiling, SolarEdge Technologies Ltd: SE3000x {208V} handles 3,020 W continuous AC (1,980 W below the 5,000 W 208 V median). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Installers comparing SolarEdge Technologies Ltd against ABB: PVI-30-OUTD-S-US-A {208V} (3,000 W) should verify whether listed since 2018-10-15 grid-support firmware meets local IEEE 1547 utility rules.
Where Does SolarEdge Technologies Ltd: SE3000x {208V} Fall Across Listed CEC Models?
Position of SolarEdge Technologies Ltd: SE3000x {208V} (3,020 W AC) relative to the 7,680 W CEC median inverter.
What Dataset Percentiles Define SolarEdge Technologies Ltd: SE3000x {208V}?
Percentile placement of SolarEdge Technologies Ltd: SE3000x {208V} across AC power class, conversion efficiency, and backfeed breaker size.
What Do the Dataset Ranks Show for SolarEdge Technologies Ltd: SE3000x {208V}?
Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for SolarEdge Technologies Ltd: SE3000x {208V}. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
97.31% CEC Weighted Efficiency
+0.90 pts vs the 96.41% 208 V median; overall power rank #1,727 (3,020 W, below CEC median; higher than 26.3% of peers).
20 A Required Backfeed OCPD
125% x 14.5 A = 18.1 A -> 20 A standard OCPD using 12 AWG Cu (75 C).
305 V - 480 V (Max 480 V DC)
Tracking span of 175.0 V; listed since 2018-10-15 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 3020.0W / 208 V -> 14.5 A | Breaker >= 1.25 * 14.5 = 18.1 A -> 20 A
CEC Inverters.csv for SolarEdge Technologies Ltd: SE3000x {208V}: Paco=3020.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=97.31%.
Result: Min 20 A breaker & 12 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SolarEdge Technologies Ltd: SE3000x {208V}?
Official California Energy Commission electrical test parameters, AC voltage, and DC limits for SolarEdge Technologies Ltd: SE3000x {208V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 3,020 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 305 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 8.8671 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.31% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2018-10-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to SolarEdge Technologies Ltd: SE3000x {208V} (208 V, commercial single-phase)?
Check whether SolarEdge Technologies Ltd: SE3000x {208V} (20 A breaker) fits without main breaker derate or supply-side taps.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 20 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 20 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 20 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 20 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 20 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SolarEdge Technologies Ltd: SE3000x {208V}?
Verified cold-weather (-10 C) series module counts matched to SolarEdge Technologies Ltd: SE3000x {208V}'s 480 V DC ceiling.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 8 panels (fixed) | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 10 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 9 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 11 panels (fixed) | 2.2 kW |
Which Competing Grid-Support Inverters Compare to SolarEdge Technologies Ltd: SE3000x {208V}?
Alternative CEC inverters comparable to SolarEdge Technologies Ltd: SE3000x {208V}, including ABB: PVI-30-OUTD-S-US-A {208V} (3,000 W) at 208 V, commercial single-phase.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: PVI-30-OUTD-S-US-A {208V} ABB |
3,000 W | -20 W | 208.0 V | 480.0 V | 95.47% |
| ABB: PVI-30-OUTD-S-US-Z-A {208V} ABB |
3,000 W | -20 W | 208.0 V | 480.0 V | 95.47% |
| ABB: PVI-30-OUTD-S-US-Z-M-A {208V} ABB |
3,000 W | -20 W | 208.0 V | 480.0 V | 95.47% |
| ABB: UNO-DM-33-TL-PLUS-US-SB-RA {208V} ABB |
3,000 W | -20 W | 208.0 V | 480.0 V | 95.8% |
What Are the Interconnection Limits and Best-Fit Uses for SolarEdge Technologies Ltd: SE3000x {208V}?
Check SolarEdge Technologies Ltd: SE3000x {208V} (3,020 W AC, 20 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on SolarEdge Technologies Ltd: SE3000x {208V}.
SolarEdge Technologies Ltd: SE3000x {208V} Panel & Wire Spec
Size 75 C copper conductors at 12 AWG Cu on a 20 A OCPD breaker (14.5 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.31%) and MPPT window (305-480 V) directly against ABB: PVI-30-OUTD-S-US-A {208V} (3,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SolarEdge Technologies Ltd: SE3000x {208V} by SolarEdge Technologies Ltd covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does SolarEdge Technologies Ltd: SE3000x {208V} require?
At 3,020 W continuous AC (208 V, commercial single-phase), continuous current is 14.5 A; 125% NEC 690.8/705.12 sizing requires a 20 A breaker and 12 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SolarEdge Technologies Ltd: SE3000x {208V} require?
At 3,020 W AC and 208 V, commercial single-phase, continuous line current is 14.5 A, requiring a 20 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does SolarEdge Technologies Ltd: SE3000x {208V} compare to ABB: PVI-30-OUTD-S-US-A {208V}?
SolarEdge Technologies Ltd: SE3000x {208V} delivers 3,020 W AC at 97.31% CEC efficiency with a 480 V DC ceiling, while ABB: PVI-30-OUTD-S-US-A {208V} outputs 3,000 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)