Manufacturer: Shenzhen Growatt New Energy Co Ltd Registry: CEC Verified Engineering Specification

Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} outputs 5,232 W AC at 208 V, commercial single-phase (25.2 A continuous, 35 A OCPD), ranking #1,785 of 2,343 CEC inverters at 96.28% efficiency with a 230-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
5,232 W
AC Voltage
208 V, commercial single-phase
Min PV Breaker
35 A (8 AWG Cu)
CEC Efficiency
96.28%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} Compare Against Peer CEC Listings?

Breaker sizing (35 A), 8 AWG Cu wire rules, and DC input limits for Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}.

Classified as a hybrid battery-capable inverter (active in CEC directory), Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} requires 31.5 A design capacity -> 35 A breaker using 8 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 96.28% (-0.54 pts vs overall CEC median) across 2,343 CEC models, while commercial 208 v, commercial single-phase switchgear interconnection uses 1,200a bus / 1,200a main (208v) or nec 705.11 supply-side tap.

Where Does Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} Fall Across Listed CEC Models?

Output power comparison showing where Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} sits among all 2,343 CEC-listed grid-support inverters.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} (5,232 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACShenzhen Growatt N: 5,232 W

What Dataset Percentiles Define Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}?

Relative ranking of Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} Technical ThresholdsPercentile comparison for Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output5,232 WCEC Efficiency96.28%Backfeed Breaker35 A

What Do the Dataset Ranks Show for Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}?

Snapshot of Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} efficiency rank (#1,785), OCPD breaker size, MPPT span, and busbar verdict.

Eff #1,785 / 2,343

96.28% CEC Weighted Efficiency

-0.13 pts vs the 96.41% 208 V median; overall power rank #1,463 (5,232 W, below CEC median; higher than 37.6% of peers).

NEC 705.12 Check

35 A Required Backfeed OCPD

125% x 25.2 A = 31.5 A -> 35 A standard OCPD using 8 AWG Cu (75 C).

MPPT Window

230 V - 480 V (Max 480 V DC)

Tracking span of 250.0 V; active in CEC directory (hybrid battery-capable inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 5232.0W / 208 V -> 25.2 A | Breaker >= 1.25 * 25.2 = 31.5 A -> 35 A

CEC Inverters.csv for Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}: Paco=5232.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=96.28%.

Result: Min 35 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}.

Official California Energy Commission (NREL SAM) test parameters for Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 5,232 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 208 V, commercial single-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 480 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 230 V - 480 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 14.3007 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 96.28% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: Yes (Battery Capable) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} (208 V, commercial single-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} at 208 V, commercial single-phase.

Evaluates Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} (35 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (208V) 40 A 35 A PASS (120% Commercial Busbar)
400A Bus / 400A Main (208V) 80 A 35 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (208V) 120 A 35 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (208V) 160 A 35 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (208V) 240 A 35 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}?

Minimum and maximum series solar module strings fitting Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} MPPT and 480 V limits.

Sampled CEC PV modules aligned within 230.0-480.0 V MPPT and 480.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 6 to 8 panels 4.72 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 7 to 11 panels 4.84 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 7 to 10 panels 4.25 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 8 to 11 panels 2.2 kW

Which Competing Grid-Support Inverters Compare to Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}?

Peer 208 V, commercial single-phase CEC inverters near 5,232 W AC output such as Delta Electronics: SOLIVIA 52 NA G4 TL {208V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Delta Electronics: SOLIVIA 52 NA G4 TL {208V}
Delta Electronics
5,200 W -32 W 208.0 V 500.0 V 97.45%
Delta Electronics: E6_BDI {208V}
Delta Electronics
5,025 W -207 W 208.0 V 480.0 V 97.13%
ABB: PVI-5000-OUTD-US-A {208V}
ABB
5,000 W -232 W 208.0 V 480.0 V 96.0%
ABB: PVI-5000-OUTD-US-Z-A {208V}
ABB
5,000 W -232 W 208.0 V 480.0 V 96.0%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}?

Check Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} (5,232 W AC, 35 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V}.

Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} Panel & Wire Spec

Size 75 C copper conductors at 8 AWG Cu on a 35 A OCPD breaker (25.2 A continuous).

Alternative Inverter Comparison

Compare efficiency (96.28%) and MPPT window (230-480 V) directly against Delta Electronics: SOLIVIA 52 NA G4 TL {208V} (5,200 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} by Shenzhen Growatt New Energy Co Ltd covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

What breaker and wire size does Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} require?

At 5,232 W continuous AC (208 V, commercial single-phase), continuous current is 25.2 A; 125% NEC 690.8/705.12 sizing requires a 35 A breaker and 8 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} require?

At 5,232 W AC and 208 V, commercial single-phase, continuous line current is 25.2 A, requiring a 35 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

How does Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} compare to Delta Electronics: SOLIVIA 52 NA G4 TL {208V}?

Shenzhen Growatt New Energy Co Ltd: SPH 6000TL BL-US {208V} delivers 5,232 W AC at 96.28% CEC efficiency with a 480 V DC ceiling, while Delta Electronics: SOLIVIA 52 NA G4 TL {208V} outputs 5,200 W at 208 V, commercial single-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.