Manufacturer: Shenzhen Growatt New Energy Co Ltd Registry: CEC Verified Engineering Specification

Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} outputs 99,370 W AC at 480Y/277 V, 3-phase (119.5 A continuous, 150 A OCPD), ranking #1,467 of 2,343 CEC inverters at 96.56% efficiency with a 520-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
99,370 W
AC Voltage
480Y/277 V, 3-phase
Min PV Breaker
150 A (1/0 AWG Cu)
CEC Efficiency
96.56%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} Compare Against Peer CEC Listings?

Breaker sizing (150 A), 1/0 AWG Cu wire rules, and DC input limits for Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}.

For NEC 705.12 solar interconnection, Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} outputs 119.5 A continuous AC at 480Y/277 V, 3-phase and needs a 150 A backfeed breaker on 1/0 AWG Cu (75 C). Commercial 480Y/277 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (277V) or NEC 705.11 supply-side tap. Conversion efficiency scores 96.56% (#1,467 of 2,343, -0.26 pts vs overall CEC median).

Where Does Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} Fall Across Listed CEC Models?

Output power comparison showing where Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} sits among all 2,343 CEC-listed grid-support inverters.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} (99,370 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACShenzhen Growatt N: 99,370 W

What Dataset Percentiles Define Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}?

Relative ranking of Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} Technical ThresholdsPercentile comparison for Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output99,370 WCEC Efficiency96.56%Backfeed Breaker150 A

What Do the Dataset Ranks Show for Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}?

Snapshot of Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} efficiency rank (#1,467), OCPD breaker size, MPPT span, and busbar verdict.

Eff #1,467 / 2,343

96.56% CEC Weighted Efficiency

-0.26 pts vs the 96.82% 277 V median; overall power rank #344 (99,370 W, top 14.8%; higher than 85.2% of peers).

NEC 705.12 Check

150 A Required Backfeed OCPD

125% x 119.5 A = 149.4 A -> 150 A standard OCPD using 1/0 AWG Cu (75 C).

MPPT Window

520 V - 800 V (Max 800 V DC)

Tracking span of 280.0 V; active in CEC directory (hybrid battery-capable inverter).

Commercial / 3-Phase Fit

Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480Y/277 V, 3-phase switchgear (200A Bus / 200A Main (277V) to 1,200A Bus / 1,200A Main (277V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 99370.3W / 480 V 3-phase -> 119.5 A | Breaker >= 1.25 * 119.5 = 149.4 A -> 150 A

CEC Inverters.csv for Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}: Paco=99370.3 W, Vac=277 V, Vdcmax=800.0 V, Eff=96.56%.

Result: Min 150 A breaker & 1/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (277V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}.

Official California Energy Commission (NREL SAM) test parameters for Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 99,370 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480Y/277 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 800 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 520 V - 800 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 155.929 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 96.56% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: Yes (Battery Capable) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} (480Y/277 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} at 480Y/277 V, 3-phase.

Evaluates Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} (150 A required OCPD at 480Y/277 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (277V) 40 A 150 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (277V) 80 A 150 A Supply-Side Tap (705.11) / Dedicated Switchboard
600A Bus / 600A Main (277V) 120 A 150 A Supply-Side Tap (705.11) / Dedicated Switchboard
800A Bus / 800A Main (277V) 160 A 150 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (277V) 240 A 150 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}?

Minimum and maximum series solar module strings fitting Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} MPPT and 800 V limits.

Sampled CEC PV modules aligned within 520.0-800.0 V MPPT and 800.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 13 to 14 panels 8.26 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 16 to 18 panels 7.92 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 16 to 17 panels 7.22 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 18 to 19 panels 3.8 kW

Which Competing Grid-Support Inverters Compare to Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}?

Peer 480Y/277 V, 3-phase CEC inverters near 99,370 W AC output such as Power Center: Max Hybrid 60 {277V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Power Center: Max Hybrid 60 {277V}
Power Center
60,050 W -39320 W 277.0 V 850.0 V 96.86%
Sol-Ark: 60K-3P-480V {277V}
Sol-Ark
60,050 W -39320 W 277.0 V 850.0 V 96.86%
Delta Electronics: E30-TL {277V}
Delta Electronics
30,488 W -68882 W 277.0 V 830.0 V 98.24%
ABB: UNO-86-TL-OUTD-S-US-A {277V}
ABB
8,600 W -90770 W 277.0 V 480.0 V 97.18%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}?

Check Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} (99,370 W AC, 150 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480Y/277 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (277V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V}.

Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} Panel & Wire Spec

Size 75 C copper conductors at 1/0 AWG Cu on a 150 A OCPD breaker (119.5 A continuous).

Alternative Inverter Comparison

Compare efficiency (96.56%) and MPPT window (520-800 V) directly against Power Center: Max Hybrid 60 {277V} (60,050 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} by Shenzhen Growatt New Energy Co Ltd covering breaker sizing, MPPT limits, and 480Y/277 V, 3-phase interconnection.

What breaker and wire size does Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} require?

At 99,370 W continuous AC (480Y/277 V, 3-phase), continuous current is 119.5 A; 125% NEC 690.8/705.12 sizing requires a 150 A breaker and 1/0 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} require?

At 99,370 W AC and 480Y/277 V, 3-phase, continuous line current is 119.5 A, requiring a 150 A OCPD and 1,200A Bus / 1,200A Main (277V) or NEC 705.11 interconnection.

How does Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} compare to Power Center: Max Hybrid 60 {277V}?

Shenzhen Growatt New Energy Co Ltd: WIT 100K-HU-US {277V} delivers 99,370 W AC at 96.56% CEC efficiency with a 800 V DC ceiling, while Power Center: Max Hybrid 60 {277V} outputs 60,050 W at 480Y/277 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.